Controlinc 1746-C (Version 5.21) Network Master Users Guide (2004-11-18)
Words [4 17] (control/configuration parameters set by the PLC)
1. Word [4]: Set the Number of Valves on the Network.
2. Word [5]: Set the Scan Period value (# scans before a communication diagnostic scan)
3. Word [6]: Set the T/F control flag whether or not to poll for totalizers on network scans.
4. Word [7]: Set the additional number of valves to poll in the network-scan time slice.
5. Word [8]: Set the Additional Message response delay to expect from actuators
(10ms increments)
(FUNCTION: Poll specified additional register from all actuators on network)
6. Word [9]: Set the specified additional register to poll from all actuators on the network.
7. Word [10]: Set the T/F control flag whether or not to start polling all actuators for the additional
register.
(FUNCTION: Poll block of registers from one specific actuator on the network)
8. Word [11]: Set the specific actuator to get the block of holding registers from
9. Word [12]: Set the starting register number in the block of holding registers to be requested
10. Word [13]: Set the total number of holding registers being requested
11. Word [14]: Set the T/F control flag whether or not to start polling the specific actuator for the
block of registers.
(FUNCTION: Reset Scan Period Counter/Accumulator)
12. Word [15]: Set the T/F control flag whether or not to manually reset the Scan Period Counter.
13. Word [16]: Value that will always reset the scan period counter.
(FUNCTION: Poll TEC2000 Input Registers 1000 – 1003)
14. Word [17]: Set the T/F control flag whether or not to poll the input registers if the system is
determined to be a TEC2000 system.
Remember …
Currently, Words [18
46] in table [0] are unused and
should be considered “reserved” for future use.