Brochures and Data Sheets

2
Key Features
n
Supports Ethernet, SNMP,
and RS485 communication
interfaces – enables remote
control and monitoring
n
NetSure
rectifiers are designed
to operate from -40°C to +75°C,
providing 600W output at 65°C
suitable for harsh
environmental conditions
n
Extremely wide AC voltage
range window – 85VAC to
300VAC
n
Several distribution configura-
tion options – battery disconnect
breakers, load breakers, and
GMT fuses up to 15A to meet
application needs
n
NEBS Level 3 compliant and
UL Listed – to meet industry
standards
n
Monitoring and battery test and
charge functions – advanced
battery management features
and AC service monitoring
n
Configuration file capability
minimizes installation time
and allows planned network
conformity
Description
The NetSure
211 DC Power Solution is a flexible system capable of providing DC
power through the use of 500W or 1000W rectifiers and a variety of output distribu-
tion options. The system is available in an integrated distribution configuration. The
NetSure
211 is available in both 19" and 23" 1RU & 2RU rack-mount congurations,
suited for up to 6kW power requirements in the most harsh environments. The
system is supported by a single SCU+ or ACU+ controller (ACU+ for 2RU systems only)
that provides all control and operational conditions, as well as historical site data and
external signal conditioning and monitoring. Each rectier shelf includes a slot for
the controller and space for the rectifiers. Distribution is provided by breakers or
fuses located in the power shelf.
Distribution options include load low-voltage disconnect (LLVD), battery low-voltage
disconnect (BLVD), or no low-voltage disconnect. Plug-in rectifiers, AC connectivity
and DC load outputs enhance the overall flexibility of the system by minimizing
installation and start-up time. This dynamic system also offers alternative AC input
configurations, relay rack configurations, battery tray options, battery box options
and pre-configured output load kits.
The NetSure
211 is designed for up to 4kW loads (19") or 6kW loads (23"). This
cost-effective solution is NEBS Level 3 compliant and UL Listed. Rated for continuous
operation from -40°C to +75°C, this system is designed for the harsh outside plant
environment, as well as customer premise FTTx, wireless back-haul, microwave, and
DLC applications.