Ordering Guides

2 095ORB-GMCSS / 0614
Indoor Solution With DC Power
The indoor site solution combines a NetSure
211 -48 VDC
power system with reliable rectifiers, an advanced Ethernet-
accessible controller, flexible distribution and high power
density. An enclosed battery cabinet is included that can be
mounted on the wall or in a relay rack. A 40 A battery disconnect
is included with the battery cabinet and can be connected in
parallel with other cabinets to provide additional backup time.
n Supports Ethernet and
SNMP communication
interfaces, enabling remote
control and monitoring
n NetSure
rectifiers are
designed to operate from
-40 °C to +75 °C, providing
500 W output at 45 °C, suitable
for harsh environmental conditions
n Extremely wide AC voltage range
window, 85 VAC to 300 VAC
Application
The Indoor Solution With DC Power is designed for deployment
in wireless sites, central office, POP sites, co-location sites,
customer premises, outdoor cabinets, CEVs, vaults or portable
shelters. Specific applications include: Alternative Access Vendor
(AAV), wireless backhaul and other site solutions such as, DAS,
DLC, xDSL, DSLAM, FTTx electronics, broadband communica-
tions, multiplexers, LTE, WiMAX, microwave and PBX.
Compact Indoor and Outdoor Cell Site Solutions
Indoor Solution
(shown without cover)
Dimensions
17.5"
17.7"
15.6"
10.5"
1.9"
1.7"
6.9"
5.0"
Technical Specifications
Electrical
System Voltage
120 VAC single phase (nominal)
Output Voltage -42 VDC to -58 VDC
System Capacity 19" 1 RU up to 10 A
Rectifier Capacity 0.5 kW @ 120 VAC
DC Distribution Wallmount GMT fuse panel with (10) fuses, up to 15 A
Controller SCU+ controller
Physical Characteristics
Framework Type
Relay rack
Available Space
1 RU 19" W
Dimensions
(H x W x D)
DC power system: 1.7" x 19" x 12"
Solution: 10.5" x 19" x 15.6"
Mounting
Rack or wall mount
Weight, Equipped
System: 35.5 lb., w/out batteries
Four (4) batteries: 36 lb. total
Access
Front for batteries, control and distribution, rear for AC
Environmental
Climate System Fan-cooled front to rear
Operating Temp. -40 °C to +75 °C*
Storage Temp. -40 °C to +75 °C
Relative Humidity 0% to 95% non-condensing
EMI/RFI Conforms to FCC rules Part 15, Subpart B, Class B and EN55022
Class B, radiated and conducted
Safety Compliance cULus 60950 recognized NEBS Level 3 Compliance
*
See rectifier specification for any derating. Operating and storage temperatures for
batteries installed in the battery cabinet are provided by the battery manufacturer.
Ordering Information
Emerson
Part Number
Description
582136600SK010 Indoor Solution w/DC Power
Equipped with the following:
1 EA NetSure
211 power system
2 EA 500 W rectifiers
1 EA 19" rack-mount, slide-out tray
1 EA Battery cabinet
1 EA Wall mount bracket
Accessories
547681 Battery, EnerSys NP12-12, 12 AH bat mod, 4 EA