Application Guide

Section 5876 Installation Instructions
Issue AT, April 26, 2013 Spec. No. 582140000 (Models 802
NLDB, 802NLEB and 802NL-B)
Page 4-40 Chapter 4. Making Electrical Connections
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
To Optional Bullet Device Panel
(TLS/TPS Fuses and Bullet Nose-Type Circuit Breakers)
Refer to Figure 4-13 for load lug landing locations.
When lugs are secured using 1/4 inch hardware, recommended torque is 60 in-lbs when
a Belleville lock washer is used, and 84 in-lbs when a standard flat washer and lock
washer are used.
Connect load leads to the busbars provided on the List C Fuse/Circuit Breaker Panel.
These busbars provide 1/4-20 threaded holes on 5/8" centers for installation of customer
provided two-hole lugs.
Load Side
Customer must provide lug mounting bolts and additional hardware.
Bolt length: 3/4”.
Load return leads are terminated outside the bay to customer provided return busbars.
Load Return Side
Figure 4-13
Load Connections to Optional Bullet Device Panel
(TLS/TPS Fuses and Bullet Nose-Type Circuit Breakers)
Note: Load leads are connected to load busbars.
These busbars provide 1/4-20 threaded holes
on 5/8" centers for installation of customer
provided two-hole lugs. Customer must
provide lug mounting bolts and additional
hardware. Bolt length: 3/4".
Recm. Torque
1/4" Hardware
using Belleville
Lock Washer,
60 in-lbs
1/4" Hardware
using flat washer
and lock washer,
84 in-lbs