Page 5-24 Chapter 5. Installing the Rectifiers and Initially Starting the System
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
20) Repeatedly press and release the FUNCTION SELECT DOWN arrow key until
CHANGE CONFIGURATION PARAMETERS is displayed.
21) Press and release the FUNCTION SET ENTER key.
22) Repeatedly press and release the FUNCTION SELECT DOWN arrow key until
TEST/EQUALIZE STOP IS MANUAL is displayed.
23) Press and release the ALARM CUTOFF and FUNCTION SET ENTER keys
simultaneously. Line 2 of the display is replaced by "CHANGE THE VARIABLE".
24) Press the FUNCTION SET NO (-) key until the value displayed is decreased to 1,
then release the key.
25) Press and release the ALARM CUTOFF and FUNCTION SET ENTER keys
simultaneously.
26) “ARE YOU SURE?” is displayed. Press and release the FUNCTION SET YES
(+) key.
27) Press and release the FUNCTION SET YES (+) and NO (-) keys simultaneously,
to return to the beginning of the MCA menu tree.
28) Press and release the FUNCTION SET ENTER key.
29) Press and release the FUNCTION SELECT DOWN arrow key to display FLOAT
MODE IS ACTIVE SET TEST/EQ.
30) Press and release the ALARM CUTOFF and FUNCTION SET ENTER keys
simultaneously.
31) “ARE YOU SURE?” is displayed. Press and release the FUNCTION SET YES
(+) key.
a) Requirement: System output voltage goes to the test/equalize setting.
b) Requirement: MCA TEST/EQ indicator goes yellow.
c) Requirement: External test/equalize alarms activate (if configured).
d) Requirement: In one hour, the following occurs ...
1) Requirement: System output voltage goes to the float setting.
2) Requirement: MCA TEST/EQ indicator goes out.
3) Requirement: External test/equalize alarms reset (if configured).
32) Press and release the FUNCTION SET YES (+) and NO (-) keys simultaneously,
to return to the beginning of the MCA menu tree.
33) Press and release the FUNCTION SET ENTER key.
34) Repeatedly press and release the FUNCTION SELECT DOWN arrow key until
CHANGE CONFIGURATION PARAMETERS is displayed.
35) Press and release the FUNCTION SET ENTER key.
36) Repeatedly press and release the FUNCTION SELECT DOWN arrow key until
MANUAL TEST/EQUALIZE = hh HOURS is displayed.
37) Press and release the ALARM CUTOFF and FUNCTION SET ENTER keys
simultaneously. Line 2 of the display is replaced by "CHANGE THE VARIABLE".
38) Press the FUNCTION SET YES (+) key until the value displayed increases to the
value recorded in step 5), then release the key. If TEST/EQUALIZE STOP IS
MANUAL was being displayed in step 5), press the FUNCTION SET YES (+) key
until the value displayed increases above 99.