Application Guide

Section 5876 Installation Instructions
Issue AT, April 26, 2013 Spec. No. 582140000 (Models 802
NLDB, 802NLEB and 802NL-B)
Page 2-20 Chapter 2. Placing the Bays and Installing Internal/External Busbars
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Figure 2-10
Installing Power/Distribution Bay to Power/Distribution Bay Negative and Positive Busbar Links
(Lists 1 and 11)
3/8-16 x 1-1/2" Bolt
3/8" Belleville Lock Washer
3/8" Belleville Lock Washer
(concave side of Belleville
Lock Washers face each other)
3/8” Hardened Flat Washer
(10 Places per Busbar)
POSITIVE
BUSBAR LINK
NEGATIVE
BUSBAR LINK
Slide Busbar Links Under
Bays' Upright Channels.
Use Bolt Holes as Shown
in Illustration.
Torque to 180 in-lbs.