Application Guide

Section 5876 Installation Instructions
Issue AT, April 26, 2013 Spec. No. 582140000 (Models 802
NLDB, 802NLEB and 802NL-B)
Page 3-12 Chapter 3. Installing Distribution Devices and MCA/LMS Circuit Cards
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Figure 3-5A
218 Circuit Breakers Lug Adapter Kits
1-Pole 218 Circuit
Breakers Assemblies
Load Lug Adapter Plate
for 1-Pole Devices
1.000"
3/8" Clearance Holes
Lug Adapter P/N 513700,
Kit P/N 520891
(see Notes 1, 2, 3)
2-Pole 218 Circuit
Breaker Assemblies
Load Lug Adapter Plate
for 2-Pole Devices
3/8" Clearance Holes
Lug Adapter P/N 513701,
Kit P/N 520892
(see Notes 1, 2, 3)
NO LUG ADAPTER KITS
REQUIRED WHEN USED IN
DISTRIBUTION ONLY BAYS
Lug Adapter Kits
Power/Distribution Bays
Lug Adapter Kits
Distribution Only Bays
2-Position
Lug Adapter Kit
P/N 529132
(see Notes 4, 6, 7, 8)
Lug Adapter Kits
Power/Distribution Bays
Lug Adapter Kits
Distribution Only Bays
Notes:
1. Maximum size of wire to be connected to a single lug position is 750 kcmil.
2. Maximum lug width is 1.937 inches.
3. Kit includes Load Lug Adapter Plate, plus 1/4" and 3/8" mtg. hardware.
4. Lug adapter accepts a maximum of (2) 750 kcmil or (4) 350 kcmil lugs.
5. Lug adapter accepts a maximum of (4) 750 kcmil lugs.
6. Lugs are not part of the kit, shown for illustration only.
7. Bay busbars are not part of the kit, shown for illustration only.
8. Two (2) kits shown for illustration of the kit installed on busbars with tops
even with each other and staggered.
1.000"
3/8" Clearance Hole
1.000"