Application Guide

SAG584622100, SAG584622200
SAG584622300, SAG584622400
System Application Guide
Spec. Nos. 584622100, 584622200,
584622300, 584622400 (Model DCS48375)
Issue AC, July 3, 2012
Page 1 of 34
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SYSTEM OVERVIEW
Description: +24VDC to -48VDC @ up to 375A
converter system.
The NetSureDCS48375 Converter
System is comprised of a main shelf
and up to two (2) expansion shelves.
Each shelf provides mounting positions
for up to four (4) converter modules.
Each shelf also provides a 15-position
distribution row (19” version) or
20-position distribution row (23”
version) which accepts bullet nose
circuit breakers and TPS/TLS
fuseholders. A GMT fuse block option
is also available.
Note: Refer to UM1C24481500
(Converter Module User
Instructions) for converter
module information.
Family: NetSure
Spec. Nos.: 584622100 (Main Shelf 19” version)
584622200 (Expansion Shelf 19” version)
584622300 (Main Shelf 23” version)
584622400 (Expansion Shelf 23” version)
Model: DCS48375
Shelves per System: (1) Main Shelf, up to (2) Expansion Shelves
Input Voltage Nominal +24VDC
Output Voltage: -48VDC, -50VDC, -52VDC, or -54VDC
(User Selectable)
Output Capacity:
per Converter Module: 31A (1500W)
per Shelf: 125A, maximum (Converter Output)
per Distribution Row: 250A, maximum (Distribution Load)
System: 375A, maximum (Converter Output + Distribution Load)
Agency Approval: UL 60950 Recognized (“c UR”), NEBS
(see “1.4 System Compliance Informationunder SPECIFICATIONS)
Mounting Type: Nominal 19” or 23” Relay Rack or Equipment Rack Mounting
Mounting Depth: 18.750 (w/out Expansion Wiring Cover)
20.375 (with Expansion Wiring Cover)
6” Front Projection
Mounting Height: 6.968 (4U) (w/out optional 1U Wiring Space Access Cover)
7.718 (5U) (with optional 1U Wiring Space Access Cover)