User manual

Accessing an RPC2 Communications Module via the Web Interface
33 Emerson
®
RPC2
To configure e-mail and SMS event consolidation:
1. From the side navigation bar of the System tab, click Notification>Messaging>Customize
Message.
2. Under Configure Email/SMS Event Consolidation, check the boxes to enable e-mail or SMS
consolidation.
3. Enter the consolidation time limit in number of seconds and enter the consolidation event limit in
number of events.
4. Click the Save icon, , at the top of the page.
Syslog
Syslog notifications can be sent to up to four IPv4 or IPv6 addresses. To enable Syslog notifications:
1. Log in with the privileges required to change these settings.
2. From the side navigation bar of the System tab, click Notification>Syslog.
3. Check the box to enable either IPv4 or IPv6 addressing and enter up to four addresses.
4. Click the Save icon, .
Datalog
An administrator can enable data logging for rack PDUs, branches or receptacles and export the data
log to an FTP site. To enable data logging:
1. Log in with the privileges required to change these settings.
2. From the side navigation bar of the System tab, click Notification>Datalog.
3. Under the Datalog heading, check the box to enable data logging.
4. Use the drop-down menus to enable or disable PDU, branch or receptacle data logging.
5. Use the drop-down menu to enter the data logging interval in number of minutes.
6. Click the Save icon, , when finished.
To export a data log:
1. Log in with the privileges required to change these settings.
2. From the side navigation bar of the System tab, click Notification>Datalog.
3. Under the Export heading, enter the IP address, username and password for the FTP site where
the data log will be exported.
4. Enter the path and filename for the data log.
5. Click the Export icon when finished.
Clicking the Flush or Download icon at the top of the screen will either clear or download
the data log.
NOTE
The default filename is sys-data.log.