Instruction Manual IM-106-880, Rev 2.0 September 2009 OCX 8800 Oxygen/Combustibles Transmitter http://www.raihome.
HIGHLIGHTS OF CHANGES Effective September 2009, Rev 2.0 Page/Section Summary Throughout IM Included coverage of all General Purpose OCX 8800 configurations/options into this single Instruction Manual. Added FOUNDATION Fieldbus communications option. Added coverage of optional COe Purge/Zero function equipment illustrations with related installation and operating procedures. Added coverage of three optional in-situ filters. Added coverage of optional wall-mount or rack-mount blowback panel.
Instruction Manual IM-106-880, Rev 2.0 September 2009 OCX 8800 Table of Contents Essential Instructions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . i SECTION i Introduction Preface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Definitions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Instruction Manual OCX 8800 IM-106-880, Rev 2.0 September 2009 SECTION 6 Field Communicator Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-1 Field Communicator Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-1 Off-Line and On-Line Operations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-4 Hart Menu Tree . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-5 Fieldbus Menu Tree. .
Instruction Manual IM-106-880, Rev 2.0 September 2009 OCX 8800 Status Handling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-44 Application Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-45 Application Examples . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-46 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-51 Arithmetic (ARTHM) Function Block . . . . . . . . . . . . . . . .
Instruction Manual OCX 8800 IM-106-880, Rev 2.0 September 2009 APPENDIX A Safety Data Safety Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-2 Safety Data Sheet for Ceramic Fiber Products . . . . . . . . . . . . . . . . . A-24 High Pressure Gas Cylinders . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-30 APPENDIX B SPA with HART Alarm Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Instruction Manual IM-106-880, Rev 2.0 September 2009 OCX 8800 Oxygen/Combustibles Transmitter ESSENTIAL INSTRUCTIONS READ THIS PAGE BEFORE PROCEEDING! Emerson Process Management designs, manufactures and tests its products to meet many national and international standards. Because these instruments are sophisticated technical products, you MUST properly install, use, and maintain them to ensure they continue to operate within their normal specifications.
Instruction Manual OCX 8800 ii IM-106-880, Rev 2.
Instruction Manual IM-106-880, Rev 2.0 September 2009 Section i OCX 8800 Introduction Preface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page iii Definitions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page iii Symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Instruction Manual OCX 8800 IM-106-880, Rev 2.0 September 2009 SYMBOLS NOTE TO USERS The number in the lower right corner of each illustration in this publication is a manual illustration number. It is not a part number, and is not related to the illustration in any technical manner. NOTE Read this manual before working with the product.
Instruction Manual IM-106-880, Rev 2.0 September 2009 Section 1 OCX 8800 Description and Specifications Component Checklist . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 1-1 System Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 1-3 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 1-12 Product Matrix - OCX 8800 . . . . . . . . . . . . . . . . . . . . . . . . .
Instruction Manual OCX 8800 Figure 1-1. Typical System Package 1. Instruction Manual 2. Field Communicator Package (optional) 3. Adapter Plate with Mounting Hardware and Gasket 4. Reference Air and Calibration Set (optional) 5. Blowback Hardware (optional) 6. OCX 8800 with Remote Electronics 7. OCX 8800 with Integral Electronics 1-2 IM-106-880, Rev 2.
Instruction Manual IM-106-880, Rev 2.0 September 2009 SYSTEM OVERVIEW OCX 8800 Scope This Instruction Manual supplies details needed to install, startup, operate, and maintain the OCX 8800. Signal conditioning electronics outputs a digital signal representing oxygen (O2) and combustibles (COe) values. This information, plus additional details, can be accessed with the 375 Field communicator or Emerson Process Management AMS software.
Instruction Manual IM-106-880, Rev 2.0 September 2009 OCX 8800 The OCX 8800 measures net oxygen concentration in the presence of all the products of combustion, including water vapor. Therefore, it may be considered an analysis on a "wet" basis. In comparison with older methods, such as the portable apparatus, which provides an analysis on a "dry" gas basis, the "wet" analysis will, in general, indicate a lower percentage of oxygen.
Instruction Manual IM-106-880, Rev 2.0 September 2009 OCX 8800 The power supply can accept voltages of 100 to 240 VAC and 50 to 60 Hz. The electronics accepts millivolt signals generated by the sensors and produces the outputs to be used by remotely connected devices. Refer to Section 3, Configuration and Startup for specific instructions upon initial power up. System Features 1. The O2 cell output voltage and sensitivity increase as the oxygen concentration decreases. 2.
Instruction Manual IM-106-880, Rev 2.0 September 2009 OCX 8800 System Operation Figure 1-2 shows the relationship between the components of the OCX 8800. The sensors and the electronics are contained in separate housings. The sensor housing and probe mounts to a duct or process wall so that the probe protrudes into the flue gas stream.
Instruction Manual IM-106-880, Rev 2.0 September 2009 OCX 8800 Handling the OCX 8800 It is important that printed circuit boards and integrated circuits are handled only when adequate antistatic precautions have been taken to prevent possible equipment damage. The OCX 8800 is designed for industrial application. Treat each component of the system with care to avoid physical damage. The probe may contain components made from ceramics, which are susceptible to shock when mishandled.
Instruction Manual IM-106-880, Rev 2.0 September 2009 OCX 8800 Figure 1-3. Communication Connections and AMS Application - OCX 8800 with Integral Electronics Model 375 Field Communicator OCX 8800 with Integral Electronics Signal Output (Twisted Pairs) Customer’s Laptop with AMS 38850003 Termination in Control Room 3 calibration gas lines by Instrument customer [300 ft (91 m) max.) Air AMS Figure 1-4.
Instruction Manual IM-106-880, Rev 2.0 September 2009 OCX 8800 Figure 1-5. Typical System Installation - Integral Electronics Gases Adapter Plate OCX 8800 with INTEGRAL ELECTRONICS Duct Stack Signal Outputs (Twisted Pairs) Test Gas Flow Meter Line Voltage High O2 Test Gas Low O2 Test Gas CO Test Gas 37390063 Dilution Air Flow Meter Instrument Air Pressure Supply Regulator (Reference Gas) Figure 1-6.
Instruction Manual OCX 8800 Figure 1-7. Optional Sample Tube Support 1-10 IM-106-880, Rev 2.
Instruction Manual IM-106-880, Rev 2.0 September 2009 OCX 8800 Figure 1-8. Optional InSitu Filters 1/4-18 NPT 1.3 (33) 7.3 (186) InSitu Stainless Steel or Hastolloy Filter 1/4-18 NPT 1.8 (46) 39930006 2.0 (50) 4.0 (102) InSitu High Surface Area Stainless Steel Filter Figure 1-9. Optional Panel Mounted Blowback and Calibration/Reference Air Set (19” Rack or Wall Mount) 5.00 (127) 19.00 (482.6) DILUTION GAS 6.
Instruction Manual IM-106-880, Rev 2.0 September 2009 OCX 8800 SPECIFICATIONS Specifications Net O2 Range Combustibles Accuracy Oxygen Combustibles System Response to Test Gas Oxygen Combustibles Temperature Limits Process Sensors Housing Electronics Housing Local Operator Interface Nominal and Approximate Shipping Weights 18 in. (457 mm) probe package 3 ft (0.91 m) probe package 6 ft (1.83 m) probe package 9 ft (2.
Instruction Manual IM-106-880, Rev 2.0 September 2009 OCX 8800 Specifications Blowback Air (optional) Sensors Housing Electronics Housing Clean, dry, instrument-quality air (20.
Instruction Manual IM-106-880, Rev 2.0 September 2009 OCX 8800 Table 1-1. Product Matrix - OCX 8800 OCX88A O2/Combustibles Transmitter Code 00 11 12 13 14 21 22 23 24 31 32 Probe Length and Material No Probe or Exhaust Tube 18 in. (457 mm) 316 SST 3 ft (0.91 m) 316 SST 6 ft (1.83 m) 316 SST 9 ft (2.7 m) 316 SST 18 in. (457 mm) Inconel 600 3 ft (0.91 m) Inconel 600 6 ft (1.83 m) Inconel 600 9 ft (2.7 m) Inconel 600 18 in. (457 mm) Ceramic 3 ft (0.
Instruction Manual IM-106-880, Rev 2.0 September 2009 OCX 8800 Cont’d Code 0 1 2 3 . In-Situ Filter None Stainless Steel High Surface Area Stainless Steel Hastelloy Code 0 2 3 OCX88A 11 10 1 1 H3 06 0 4 Accessories None Cal. Gas/Flow Rotometers & Ref. Gas Set Cal. Gas/Flow Rotometers & Ref. Gas Set w/ Blowback Cal. Gas/Flow Rotometers & Ref.
Instruction Manual IM-106-880, Rev 2.0 September 2009 OCX 8800 Table 1-2. Accessories PART NUMBER 1A99119H01 1-16 DESCRIPTION Oxygen test gas bottle; 0.4% O2, balance N2 1A99119H02 Oxygen test gas bottle; 8.
Instruction Manual IM-106-880, Rev 2.0 September 2009 Section 2 OCX 8800 Installation Mechanical Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . page 2-1 Electrical Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 2-8 Pneumatic Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 2-13 Initial Startup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Instruction Manual IM-106-880, Rev 2.0 September 2009 OCX 8800 Do not allow the temperature of the electronics housing to exceed 185°F (85°C) or damage to the electronics may result. Whenever a positive stack pressure exists at the installation site, be sure to connect all pneumatic lines prior to installing the OCX 8800 in the stack or ductwork. Failure to connect the pneumatic lines can allow the flow of contaminants into the OCX 8800 ports. Installation 1.
Instruction Manual IM-106-880, Rev 2.0 September 2009 OCX 8800 Enclosures The OCX 8800 enclosures are designed to meet ingress conditions of Type 4X and IP66. Each enclosure cover is threaded to its base and sealed with an o-ring that isolates the threads from external contaminants. Each cover is secured by a clip attached to the base that engages the cover between the ribs of the cover sidewall. The clip is held in place by an Allen head cap screw and lockwasher mounted in a recess.
Instruction Manual OCX 8800 Figure 2-2. Installation, OCX 8800 with Remote Electronics 2-4 IM-106-880, Rev 2.
Instruction Manual IM-106-880, Rev 2.0 September 2009 OCX 8800 Figure 2-3.
Instruction Manual OCX 8800 Figure 2-4. Wall or Pipe Mounting of Electronics Housing 2-6 IM-106-880, Rev 2.
Instruction Manual IM-106-880, Rev 2.0 September 2009 OCX 8800 Figure 2-5.
Instruction Manual IM-106-880, Rev 2.0 September 2009 OCX 8800 ELECTRICAL INSTALLATION All wiring must conform to local and national codes. For reference, factory wired solenoid power connections are shown in Figure 2-6. Disconnect and lock out power before connecting the unit to the power supply. Failure to lock out power could result in serious injury or death. Install all protective equipment covers and safety ground leads after installation.
Instruction Manual IM-106-880, Rev 2.0 September 2009 OCX 8800 Connect Line Voltage The OCX 8800 operates on 100 to 240 VAC line voltage at 50 to 60 Hz. The power supply requires no setup. Connect the line (L wire) to the L terminal, and the neutral (N wire) to the N terminal on the AC power input terminal block in the electronics housing. Connect the ground (G wire) to the ground stud in the electronics housing as shown in Figure 2-6.
Instruction Manual IM-106-880, Rev 2.0 September 2009 OCX 8800 Figure 2-6.
Instruction Manual IM-106-880, Rev 2.0 September 2009 OCX 8800 #1 2HTR CO 1HTR CO 2HTR O2 1HTR O2 2HTR SB 1HTR SB YEL RED BLK ORG WHT BLU SHIELD GRN Figure 2-7.
Instruction Manual IM-106-880, Rev 2.0 September 2009 OCX 8800 Figure 2-8. Customer-Furnished Interconnect Wiring or Cables SIGNAL WIRING OR CABLE NOTE: For RFI/CE compliance, the connector must provide 360 degrees of electrical contact to the cable shield. ELECTRONICS END 7.25 ±0.10 Strip Wire Ends 3/16” Typical Heat Shrink Tubing 2” Long 1/2” Size PROBE END 12.5 ±0.10 3/4 NPT Hub Size, Liquid-tight Strain Relief Connector 10.375 ±0.10 Heat Shrink Tubing 2” Long 1/2” Size 0.5 Typ. 6.875 ±0.
Instruction Manual IM-106-880, Rev 2.0 September 2009 PNEUMATIC INSTALLATION OCX 8800 Pneumatic system connections depend on whether reference air set, calibration solenoids, and/or blowback equipment options are equipped on your transmitter. Refer to the following paragraphs and select the option that applies to your transmitter configuration.
Instruction Manual IM-106-880, Rev 2.0 September 2009 OCX 8800 Figure 2-9. Pneumatic Installation, OCX with Reference Air Set without Autocalibration Sensor Housing CAL Gas In Reference Air In ( CAL Gas Flow Meter 7 scfh, 20-30 psig Recommended ( Eductor Air In 3 Dilution Air In 4 Dilution Air Flow Meter 0.
Instruction Manual IM-106-880, Rev 2.0 September 2009 OCX 8800 Figure 2-10. Pneumatic Installation, OCX with Reference Air Set, Solenoids and Autocalibration, without COe Zero Function Sensor Housing 3 CAL Gas In ( ( CAL Gas Flow Meter 7 scfh, 20-30 psig Recommended Reference Air In Eductor Air In 4 Dilution Air In Electronics Housing 1 2 Instrument Air Supply Pressure Regulator/Filter 35 psig - General Purpose 2-Stage Regulators 1 2 3 4 2” Pressure Gage Combination Filter-Reg.
Instruction Manual OCX 8800 IM-106-880, Rev 2.0 September 2009 4. Connect the CO high gas to the CAL GAS HI COe inlet fitting. Install a shutoff valve and pressure regulator with gage in the CO high supply line. 5. Connect the CAL GAS outlet fitting of the electronics housing to the inlet port of the CAL GAS flow meter. Install an air line between the flow meter outlet port and the CAL GAS inlet fitting on the sensor housing.
Instruction Manual IM-106-880, Rev 2.0 September 2009 OCX 8800 Reference Air Set, Solenoids, and Blowback Option with COe Zero Function Figure 2-13 shows the piping arrangement for the OCX 8800 with the blowback and autocalibration options when the COe Zero Function is used. The arrangement is similar to Figure 2-12 except instrument air is used as the Hi O2 test gas. Refer to Sectio 3 for details of the function.
Instruction Manual OCX 8800 IM-106-880, Rev 2.0 September 2009 Figure 2-12.
Instruction Manual IM-106-880, Rev 2.0 September 2009 OCX 8800 Figure 2-13. Pneumatic Installation, OCX with Reference Air Set, Solenoids, Blowback and Autocalibration, with COe Zero Function Reference Air Set, Solenoids, and Blowback Option with COe Zero Function Figure 2-13 shows the piping arrangement for the OCX 8800 with the blowback and autocalibration options when COe Zero Function is used. The arrangement is similar to Figure 2-12 except instrument air is used as the Hi O2 test gas.
Instruction Manual IM-106-880, Rev 2.0 September 2009 OCX 8800 Figure 2-14. Pneumatic Installation, OCX with Reference Air Set and Blowback without Autocalibration CAUTION 7 Check Valve Sensor Housing Pressure regulator with 1/8” inlet port is factory set for 35 psig. Regulator with 1/4” inlet port is factory set for 55 psig. If regulators are not installed in correct locations, the OCX 8800 will not work.
Instruction Manual IM-106-880, Rev 2.0 September 2009 OCX 8800 Reference Air Set and Blowback Panels An optional blowback panel is shown in Figure 1-9. Piping arrangement for blowback panel without autocalibration without COe Zero Function is shown in Figure 2-15. Piping arangement for blowback panel with autocalibration without COe Zero Function is shown in Figure 2-16. Piping arrangement for blowback panel with autocalibration with COe Zero Function is shown in Figure 2-17. Figure 2-15.
Instruction Manual IM-106-880, Rev 2.0 September 2009 OCX 8800 Figure 2-16.
Instruction Manual IM-106-880, Rev 2.0 September 2009 OCX 8800 Figure 2-17.
Instruction Manual OCX 8800 INITIAL STARTUP IM-106-880, Rev 2.0 September 2009 Observe the following Caution and Note. Refer to Section 3: Configuration and Startup, for OCX 8800 startup information. Upon completing installation, make sure that the OCX 8800 is turned on and operating prior to firing up the combustion process. Damage can result from having a cold OCX 8800 exposed to the process gases.
Instruction Manual IM-106-880, Rev 2.0 October 2009 Section 3 OCX 8800 Configuration and Startup Verify Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3-1 Initial Power Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3-4 Set Test Gas Values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3-4 Calibration Solenoids . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3-5 Blowback Feature . . . . . . . . . . . . . . .
Instruction Manual IM-106-880, Rev 2.0 September 2009 OCX 8800 Verify Configuration - HART Electronics There are three switches on the microprocessor board which are user configurable for the OCX 8800 with HART electronics (Figure 3-1). SW1 determines if the O2 4-20 mA signal is internally or externally powered. SW2 determines if the COe 4-20 mA signal is internally or externally powered. SW3 sets the rail limits for the O2 and COe 4-20 mA signals and configures the sample line heater control circuit.
Instruction Manual IM-106-880, Rev 2.0 September 2009 OCX 8800 Verify that the following switch settings are correct for your OCX 8800 installation: SW1 The two settings are internally or externally powering the O2 4-20 mA signal. The factory setting is for the O2 4-20 mA signal to be internally powered. SW2 The two settings are internally or externally powering the COe 4-20 mA signal. The factory setting is for the COe 4-20 mA signal to be internally powered.
Instruction Manual OCX 8800 IM-106-880, Rev 2.0 September 2009 Figure 3-2. OCX 8800 Defaults Fieldbus Electronics INITIAL POWER UP Allow adequate time (approximately 60 minutes) for the heaters to begin operation and for the OCX 8800 to reach normal operating temperature on power up. Normal operating temperature for the O2 cell is 736°C. Normal operating temperature for the combustibles cell is 300°C. The normal sample line temperature is 170°C.
Instruction Manual IM-106-880, Rev 2.0 September 2009 OCX 8800 Setting Test Gas Values with Fieldbus Communicator 1. Use the 375 Field Communicator software to access the Fieldbus menu. 2. From the TRANSDUCER menu, select O2 CAL. 3. From O2 CAL menu select O2 CAL SETUP. 4. From O2 CAL SETUP, select O2 HIGH GAS. Enter the percent O2 used for the high test gas. 5. From O2 CAL SETUP, select O2 LOW GAS. Enter the percent O2 used for the low test gas 6. From the TRANSDUCER menu select COe CAL SETUP. 7.
Instruction Manual IM-106-880, Rev 2.0 September 2009 OCX 8800 Configuring the Calibration Solenoids with the LOI 1. Use the "Z" pattern to enter the LOI menu tree. 2. From the SYSTEM menu, select Calib Setup. 3. From the Calib Setup menu, select Use Solenoids. Select Yes to enable the solenoids. BLOWBACK FEATURE The blowback feature blows instrument air back through the center of the internal filter and out the sample tube of the probe.
Instruction Manual IM-106-880, Rev 2.0 September 2009 OCX 8800 Blowback Purge Time - Length of time after blowback is complete before oxygem/combustibles readings are considered valid (Set as required by the application). Initiate Blowback - Initiates a blow back event manually. Configuring Blowback with the LOI 1. Use the "Z" pattern to enter the LOI menu tree. 2. From the SYSTEM menu, select Blow Back. 3. From the Blow Back menu, select Blow Bk Enable. Select Yes to enable blowback.
Instruction Manual IM-106-880, Rev 2.0 September 2009 OCX 8800 Purge Gas - Initiates a delay for the specified purge time before oxygen/combustibles readings are considered valid. NOTE: A Purge will automatically follow a gas flow. Performing a Calibration Verify with the Field Communicator - Fieldbus 1. Use the 375 Field Communicator or AMS software to access the Fieldbus menu. 2. From the TRANSDUCER block menu, select METHODS. 3.
Instruction Manual IM-106-880, Rev 2.0 September 2009 CALIBRATION TOLERANCE FEATURE OCX 8800 The calibration tolerance feature provides a mechanism to fail a calibration if the calibration measurement does not fall within a specific tolerance of the test gas value. The tolerance is preset within the OCX 8800 software and is not user adjustable. The tolerance is different between the oxygen and combustibles test gases.
Instruction Manual OCX 8800 COe PURGE / ZERO FEATURE IM-106-880, Rev 2.0 September 2009 This feature provides a way to periodically flood the COe sensor with air to perform two functions; a) provide additional oxygen to help burn off any combustible residue from the COe sensor, and b) allow for optional adjustment of the COe calibration constant. If the OCX8800 is configured to update the COe calibration constant, only the constant is updated. The COe calibration slope is not affected.
Instruction Manual IM-106-880, Rev 2.0 September 2009 OCX 8800 Zero Flow - Length of time COe zero gas flows. Range is 120 to 600 seconds. Default is 120 seconds. Zero Purge - Length of time after COe zero is complete before oxygen/combustibles readings are considered valid. Range is 60 to 180 seconds. Default is 60 seconds. Total duration of this function is flow time plus purge time. Zero Tracks - Determines if the analog output signals track or hold during the function.
Instruction Manual IM-106-880, Rev 2.0 September 2009 OCX 8800 COe Zero Purge - Length of time after COe zero is complete before oxygen/combustibles readings are considered valid. Range is 60 to 180 seconds. Default is 60 seconds. Total duration of this function is flow time plus purge time. COe Zero Tracks - Determines if the analog output signals track or hold during the function. Valid choices are None, Both, COe, and O2.
Instruction Manual IM-106-880, Rev 2.0 October 2009 Section 4 OCX 8800 Using the LOI Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 4-1 Display Orientation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 4-1 LOI Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 4-2 LOI Menu Tree . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Instruction Manual IM-106-880, Rev 2.0 September 2009 OCX 8800 LOI CONTROLS Overview The LOI, shown in Figure 4-2, utilizes a bright blue gas-fluorescent display. Intensity is adjustable. There is an Infrared LED source and a detector for each key. The detectors can detect a finger placed above the button through the glass window. There is no need to open the instrument in bad weather or in hazardous areas in order to access the electronics.
Instruction Manual IM-106-880, Rev 2.0 October 2009 OCX 8800 Lockout The LOI has a lockout feature that prevents nuisance actuation by someone brushing against the glass window, raindrops, dirt, insects, etc. This lockout mode is automatically established when no buttons are pushed for 30 seconds (default). This countdown to lockout is configurable. In order to unlock the display, input a "Z" pattern (Figure 4-3). First, touch the top left (gray) Enter key.
Instruction Manual IM-106-880, Rev 2.0 September 2009 OCX 8800 LOI MENU TREE This section consists of a menu tree for the LOI on the OCX 8800, Figure 4-4. This menu is specific to the OCX 8800. First Column Submenus From the operating display (O2% and COe ppm), the left-pointing Enter key is the only option to move into the first column submenus of the LOI menu tree. The first column contains three submenus: SENSOR DATA, Figure 4-4 sheet 1 of 4, CALIBRATION, sheet 2 of 4, and SYSTEM, sheets 3 and 4 of 4.
Instruction Manual IM-106-880, Rev 2.0 October 2009 OCX 8800 Figure 4-4.
Instruction Manual OCX 8800 Figure 4-4. LOI Menu Tree (Sheet 3 of 4) 4-6 IM-106-880, Rev 2.
Instruction Manual IM-106-880, Rev 2.0 October 2009 OCX 8800 Figure 4-4.
Instruction Manual OCX 8800 4-8 IM-106-880, Rev 2.
Instruction Manual IM-106-880, Rev 2.0 October 2009 Section 5 OCX 8800 Calibration Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 5-1 Fully Automatic Calibration . . . . . . . . . . . . . . . . . . . . . . . . page 5-1 Operator - Initiated Autocalibration . . . . . . . . . . . . . . . . . page 5-3 Manual Calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 5-4 D/A Trim Procedures - LOI . . . . . . . . . . . . . . . . . . . . . . . . .
Instruction Manual IM-106-880, Rev 2.0 September 2009 OCX 8800 4. Scroll down to the last item Use Solenoids. If the unit is equipped with calibration solenoids and timed automatic calibration is desired, select Yes. 5. Use the up-pointing key to select the item O2 Out Tracks. Select Yes or No to determine if updates to the O2 lock value will take place. 6. Use the down-pointing key to select the item COe Out Tracks. Select Yes or No to define if updates to the COe lock value will take place. 7.
Instruction Manual IM-106-880, Rev 2.0 September 2009 OCX 8800 Autocalibration Setup using the Field Communicator - Fieldbus NOTE Automatic calibration is only available on units equipped with calibration solenoids. Use the following procedure to specify a time interval (in hours) at which the OCX 8800 will automatically calibrate. 1. From the Transducer screen select O2 Cal or COe Cal. 2. From the O2 Cal or COe Cal screen, select O2 Cal Setup or COe Setup. 3.
Instruction Manual IM-106-880, Rev 2.0 September 2009 OCX 8800 Autocalibration using the Field Communicator - Fieldbus To initiate an automatic calibration using 375 Field Communicator, perform the following steps. Refer to Section 6, Field Communicator, for the FOUNDATION Fieldbus menu tree. 1. From Transducer screen select Methods. 2. Select OCX Calibration from the Methods menu. 3.
Instruction Manual IM-106-880, Rev 2.0 September 2009 OCX 8800 13. Press the right-pointing key when the CO reading is stable. 14. Turn off the CO test gas and press the right-pointing key to start the CO gas purge. 15. When the purge period expires, the LOI display reverts to the normal operation display. If the calibration failed, the display will indicate an alarm condition.
Instruction Manual OCX 8800 IM-106-880, Rev 2.0 September 2009 10. Select START CAL/STEP CAL to start applying the O2 Low Gas. The time to apply the test gas is specified by the Gas Time. 11. The Calibration Status should be automatically changed to FlowO2Low and then ReadO2Low for a period of time. During this period, if an attempt is made to go to the next calibration step by pressing OK and selecting START CAL/STEP CAL, you will be prompted with Operator step command is not accepted at this time. 12.
Instruction Manual IM-106-880, Rev 2.0 September 2009 OCX 8800 Manual COe Calibration using the Field Communicator - HART To perform a manual COe calibration using the 375 Field Communicator, use the following procedure. If necessary, refer to Section 6, Field Communicator, for the HART menu tree. NOTE To select a menu item, either use the up and down arrow keys to scroll to the menu item and press the right arrow key or use the number keypad to select the menu item number.
Instruction Manual IM-106-880, Rev 2.0 September 2009 OCX 8800 11. Select START CAL/STEP CAL to start applying the COe High Gas. The time to apply the test gas is specified by the Gas Time. 12. The calibration status should automatically change to FlowCOeHI and then ReadCOeHigh for a period of time. During this period, if an attempt is made to go to the next calibration step by pressing OK and selecting START CAL/STEP CAL, you will be prompted with Operator step command is not accepted at this time. 13.
Instruction Manual IM-106-880, Rev 2.0 September 2009 OCX 8800 8. From the SELECT ACTION screen, select START CAL/STEP CAL to continue calibration, select ABORT CAL to abort calibration or EXIT CAL to exit calibration method. Select one from the list and press ENTER. OCX: TAG NAME SELECT ACTION 1. START CAL/STEP CAL 2. ABORT CAL 3. EXIT CAL 9. When the Calibration Status is at the AppO2Low step, switch on O2 Low Gas. Verify the O2 concentration measured matches the O2 LOW GAS parameter in Setup CAL.
Instruction Manual IM-106-880, Rev 2.0 September 2009 OCX 8800 Manual O2/COe Calibration using the Field Communicator - Fieldbus To perform a manual O2/COe calibration using the 375 Field Communicator, use the following procedure. If necessary, refer to Section 6, Field Communicator, for the Fieldbus menu tree. NOTE To select a menu item, either use the up and down arrow keys to scroll to the menu item and press the right arrow key or use the number keypad to select the menu item number.
Instruction Manual IM-106-880, Rev 2.0 September 2009 OCX 8800 9. When the calibration status is at the Apply O2 Low Gas/ Apply Comb Low Gas step, switch on O2 Low Gas/COe Low Gas. Verify the O2 concentration measured matches the O2 Low Gas parameter in the setup. The unit samples reference air as the COe Low Gas. Press OK when ready. 10. Select Next Calibration Step and press OK to start applying the test gas. The time to apply the test gas is specified by the Gas Time. 11.
Instruction Manual IM-106-880, Rev 2.0 September 2009 OCX 8800 D/A TRIM PROCEDURES - LOI O2 D/A trim procedure using the LOI Use the following procedure to perform the O2 D/A trim procedure at the LOI. Refer to the LOI menu tree in Figure 4-4. To avoid a potentially dangerous operating condition, the OCX 8800 must be removed from the automatic combustion control loop before you start the D/A trim procedure. 1. From the operating display use the left-pointing key to select the first column submenu.
Instruction Manual IM-106-880, Rev 2.0 September 2009 OCX 8800 COe D/A trim procedure using the LOI Use the following procedure to perform the COe D/A trim procedure at the LOI. Refer to the LOI menu tree in Figure 4-4. To avoid a potentially dangerous operating condition, the OCX 8800 must be removed from the automatic combustion control loop before you start the D/A trim procedure. 1. From the operating display use the left-pointing key to select the first column submenu.
Instruction Manual IM-106-880, Rev 2.0 September 2009 OCX 8800 D/A TRIM PROCEDURES - HART O2 D/A trim procedure using HART Use the following procedure to perform the O2 D/A trim procedure using the Field Communicator. If necessary, refer to Section 6, Field Communicator, for the HART menu tree. NOTE To select a menu item, either use the up and down arrow keys to scroll to the menu item and press the right arrow key or use the number keypad to select the menu item number.
Instruction Manual IM-106-880, Rev 2.0 September 2009 OCX 8800 COe D/A trim procedure using HART Use the following procedure to perform the COe D/A trim procedure using the Field Communicator. If necessary, refer to Section 6, Field Communicator, Field Communicator, for the HART menu tree. NOTE To select a menu item, either use the up and down arrow keys to scroll to the menu item and press the right arrow key or use the number keypad to select the menu item number.
Instruction Manual OCX 8800 5-16 IM-106-880, Rev 2.
Instruction Manual IM-106-880, Rev 2.0 October 2009 Section 6 OCX 8800 Field Communicator Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 6-1 Field Communicator Connections . . . . . . . . . . . . . . . . . . page 6-1 Hart Menu Tree . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 6-5 Fieldbus Menu Tree . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Instruction Manual IM-106-880, Rev 2.0 October 2009 OCX 8800 Figure 6-1. 375 Communicator Connections - HART 4-20 mA Terminal Block in Electronics Housing 1 RL ³ 250W O2 4-20 mA Signal Line A OUT 1 + A OUT 1 - Analog Output Device Field Communicator Model 375 Field Communicator Rear Panel Lead Set 38850006 Loop Connectors Connecting to a Fieldbus Segment Connect 375 Field Communicator with the supplied lead set in parallel with the device to a Fieldbus segment, Figure 6-2.
Instruction Manual IM-106-880, Rev 2.0 October 2009 OCX 8800 Figure 6-2. 375 Communicator Conections - Fieldbus Fieldbus Signal { OCX 8800 Electronics OUT1 OUT1+ #1 NOTE: Devices shown are not to scale.
Instruction Manual OCX 8800 OFF-LINE AND ON-LINE OPERATIONS IM-106-880, Rev 2.0 October 2009 The Field Communicator can be operated both off-line and on-line. Off-line operations are those in which the communicator is not connected to the OCX 8800. Off-line operations can include interfacing the Field Communicator with a PC (refer to applicable Field Communicator documentation regarding Model 375/PC applications). In the on-line mode the communicator is connected to a fieldbus terminal block.
Instruction Manual IM-106-880, Rev 2.0 October 2009 HART MENU TREE OCX 8800 This section provides a menu tree for the Field Communicator. This menu is specific to the OCX 8800 applications. Figure 6-3.
Instruction Manual IM-106-880, Rev 2.0 October 2009 OCX 8800 Figure 6-4.
Instruction Manual IM-106-880, Rev 2.0 October 2009 OCX 8800 Figure 6-5.
Instruction Manual IM-106-880, Rev 2.0 October 2009 OCX 8800 Figure 6-6.
Instruction Manual IM-106-880, Rev 2.0 October 2009 FIELDBUS MENU TREE OCX 8800 This section consists of a menu for the Field Communicator. This menu is specific for the OCX 8800 Applications. Refer to the Fieldbus Parameter Descriptions for the applicable range, units, and description for the fieldbus menu parameters. Figure 6-7.
Instruction Manual IM-106-880, Rev 2.0 October 2009 OCX 8800 Figure 6-8.
Instruction Manual IM-106-880, Rev 2.0 October 2009 OCX 8800 Figure 6-9.
Instruction Manual OCX 8800 6-12 IM-106-880, Rev 2.
Instruction Manual IM-106-880, Rev 2.0 October 2009 Section 7 OCX 8800 Foundation Fieldbus Foundation Fieldbus Technology . . . . . . . . . . . . . . . . . . . page 7-1 Resource Block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 7-6 Transducer Block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 7-13 Analog Input (AI) Function Block . . . . . . . . . . . . . . . . . . . page 7-23 Proportional/ Integral/Derivative (PID) Function Block . .
Instruction Manual IM-106-880, Rev 2.0 October 2009 OCX 8800 NOTE: The following descriptions and definitions are not intended as a training guide for FOUNDATION Fieldbus technology but are presented as an overview for those not familiar with Fieldbus and to define device specific attributes for the Fieldbus system engineer.
Instruction Manual IM-106-880, Rev 2.0 October 2009 OCX 8800 Once the inputs are snapped, the algorithm operates on them, generating outputs as itprogresses. Algorithm executions are controlled through the setting of containedparameters. Contained parameters are internal to function blocks and do not appear asnormal input and output parameters. However, they may be accessed and modified remtely, as specified by the fundtion block. Input events may affect the operation of the algorithm.
Instruction Manual IM-106-880, Rev 2.0 October 2009 OCX 8800 such as operator consoles and computers, do not have to be programmed specifically for each type of device on the bus. Instead their displays and interactions with devices are driven from the device descriptions. Device descriptions may also include a set of processing routines called methods. Methods provide a procedure for accessing and manipulating parameters within a device.
Instruction Manual IM-106-880, Rev 2.0 October 2009 OCX 8800 Figure 7-2. Single Link Fieldbus Network Link Master Basic Devices and/or LinkMaster Devices 39930017 Fieldbus Link LAS (Link Active Scheduler) Link Active Scheduler (LAS) All links have one and only one Link Active Scheduler (LAS). The LAS operates as the us arbiter for the link. The LAS does the following: • recognizes and adds new devices to the link. • removes non-responsive devices from the link.
Instruction Manual IM-106-880, Rev 2.0 October 2009 OCX 8800 OCX FUNCTION BLOCKS Table 7-1. OCX Implemented Function Blocks Implemented Function Blocks Shows the OCX Implemented Function Blocks.
Instruction Manual IM-106-880, Rev 2.0 October 2009 OCX 8800 Mapping of PWA Description of the PlantWeb Alerts that are supported by the OCX 8800 Fieldbus Output Board are listed in Table 7-3. Figure 7-3. Description of PlantWeb Alerts . Alerts Alarms AMS Tab Sensor Malfunction Transducer Block: Sensor Alerts This alert is active when the sensor is indicating a very high or unexpected output. Sensor Alerts This alert is Replace the oxygen active when the cell.
Instruction Manual IM-106-880, Rev 2.0 October 2009 OCX 8800 AMS Tab What does the alert indicate? Recommended Action Alerts Alarms Sensor Heater Malfunction Transducer Block 1) O2 Heater Failure 2) Comb Heater Failure 3) SB Heater Failure 4) O2 Heater Ramp Rate Exceeded 5) Comb Heater Ramp Rate Exceeded 6) SB Heater Ramp Rate Exceeded 7) Heater Relay Failed Transducer Block: 1) O2 Cell Temp. Very High 2) Comb Temp. Very High 3) SB Temp Very High Transducer Block: 1) O2 Cell Temp.
Instruction Manual IM-106-880, Rev 2.0 October 2009 Alerts Alarms NV Memory Failure Transducer Block: EEPROM Corrupt NV Writes Deferred High Electronics Temperature OCX 8800 AMS Tab What does the alert indicate? Recommended Action FF/ Device Alerts The non-volatile parameter storage on the CPU board has become unreliable. At startup, wait 2 minutes with power applied and then cycle power again or reset device.
Instruction Manual IM-106-880, Rev 2.0 October 2009 OCX 8800 Alerts Alarms AMS Tab What does the alert indicate? Line Input Out of Range Transducer Block: Device Alerts This alert indicates that the line input power to the device is outside the proper operating limits. FF/ Device Alerts This alert indicates a communication failure between the FF board and the device.
Instruction Manual IM-106-880, Rev 2.0 October 2009 OCX 8800 1. Run "Transmitter Options" method. 2. In the "Transmitter Options" menu, select either "Simulate Switch" or "PWA Simulate". 3. Select "Enable" to enable the simulation feature or "Disable" to disable the simulation feature. 4. Once the method is complete, select the "Simulate PWA" tab in the Resource Block, Figure 7-4. If the simulation is enabled, the "PlantWeb Alarm Simulate" parameter is configurable otherwise it is read-only. 5.
Instruction Manual IM-106-880, Rev 2.0 October 2009 OCX 8800 Configure Simulation with the Model 375 Field Communicator Use the following procedure to configure PWA simulation using the Model 375 Field Communicator. 1. Run "Transmitter Options" method in the Resource Block (Resource | Methods). 2. In the "Transmitter Options" menu, select either "Simulate Switch" or "PWA Simulate". 3. Select "Enable" to enable PWA simulation or "Disable" to disable the simulation feature. 4.
Instruction Manual IM-106-880, Rev 2.0 October 2009 OCX 8800 Input Failure Set whenever there is a communication error between the Fieldbus card and the OCX. Simulation Active Set whenever the Fieldbus Simulate Switch is set to ON at the Fieldbus card or software simulate option enabled. Other Error Set whenever XD_ERROR is non-zero. TRANSDUCER BLOCK The Transducer Block was designed to provide the information necessary to interface OCX 8800 to the Fieldbus.
Instruction Manual IM-106-880, Rev 2.0 October 2009 OCX 8800 Parameter Mnemonic Valid Range Units COMB _SENSOR_CAL_WHO Description See FF-903 section 3.3. COMB_AUTOCAL_ INTERVAL 0-9999 Hours The time between automatic calibrations of the combustibles sensor. COMB_CAL_POINT 0-55000 PPM The value of the combustibles test gas. COMB_CONSTANT -99.0-99.0 PPM The combustibles calibration constant. COMB_DELTA_ RESISTANCE Ohms The raw value of the combustibles level input.
Instruction Manual IM-106-880, Rev 2.0 October 2009 Parameter Mnemonic OCX 8800 Valid Range Units COZERO_PURGE_TIME 60-180 COZERO_STATE 0, 1, 2 COZERO_UPDATE 0: Off – 1: On Enumerated Indicates whether the Combustibles calibration constants should be updated after Combustibles sensor zero. DETAILED_STATUS_1 0-16777215 Bit Enum A bit-enumerated value used to communicate the status of the OCX. (This is similar in nature to the command 48 status bits in HART).
Instruction Manual IM-106-880, Rev 2.0 October 2009 OCX 8800 Parameter Mnemonic Valid Range O2_SETPOINT Units Description °C O2 heater temperature set point. O2_SLOPE 34.5-57.5 mV/Decade The O2 calibration slope. O2_T90 0-300 Seconds The amount of time that the O2 process variable will take to reach 90% of the actual process variable. O2_TEMP_MAX °C The highest O2 temperature read since power on. O2_THERMOCOUPLE_ INPUT mV The raw value of the O2 temperature input.
Instruction Manual IM-106-880, Rev 2.0 October 2009 Transducer Block Enumerations Table 7-4. Calibration StateValues OCX 8800 Calibration States During a running calibration procedure, the states below reflect the current step that the calibration is running in. Refer to Table 7-4. Index CAL_STATE Description Operator Ack Required to Continue Idle 1 Apply O2 Low Gas Yes, cal can also be initiated from internally generated events.
Instruction Manual IM-106-880, Rev 2.0 October 2009 OCX 8800 Blowback States Table 7-6. Blowback State Enumerations BLOWBACK_STATE Description Idle Blow Purge Alarm Events Table 7-7. Alarm Event Enumerations ALARM_RELAY_EVENT Description Off In Calibration O2 Cell Temp Error O2 Heater Open O2 Cell Bad Cal Failed Cal Warn High Electronics Temp Unit Failure SL Temp Error Comb Cell Temp Error Power Input Error In COe Zero All Operating Mode Table 7-8.
Instruction Manual IM-106-880, Rev 2.0 October 2009 OCX 8800 Sensor Housing Type Table 7-9. Sensor Housing Enumerations SENSOR_HOUSING_TYPE Description TYPE 1 TYPE 2 TYPE 3 Cal Results Table 7-10.
Instruction Manual IM-106-880, Rev 2.0 October 2009 OCX 8800 COe Zero States Table 7-13. COe Zero State Enumerations COZERO_STATE Description Idle Flowing Purging COe Out Tracks Table 7-14. COe Out Tracks Enumerations COZERO_OUTTRAK Description None O2 CO2 Both Detailed Status Table 7-15.
Instruction Manual IM-106-880, Rev 2.
Instruction Manual IM-106-880, Rev 2.0 October 2009 OCX 8800 Transducer Block Channel Status The status of channel 1 to 4 are affected by the state of unit alarm. In all cases, the channel will read what it believes the correct sensor values. Self-Clearing alarms are reset when the alarm condition goes away. All others require the device be restarted. Table 7-18 indicates channel status under indicated device conditions (Occurence).
Instruction Manual IM-106-880, Rev 2.0 October 2009 OCX 8800 ANALOG INPUT (AI) FUNCTION BLOCK Introduction The OCX 8800 has four transducer block Input/Output channels (Table 7-20) for the AI function blocks. The status of channel values are defined in Table 7-22. The Analog Input (AI) function block (Figure 7-5) processes field device measurements and makes them available to other function blocks.
Instruction Manual IM-106-880, Rev 2.0 October 2009 OCX 8800 Table 7-19. Definitions of Analog Input Function Block System Parameters Parameter Index Number Units Description ACK_OPTION 23 None ALARM_HYS 24 Percent ALARM_SEL 38 None Used to select the process alarm conditions that will cause the OUT_D parameter to be set. ALARM_SUM 22 None The summary alarm is used for all process alarms in the block. The cause of the alert is entered in the subcode field.
Instruction Manual IM-106-880, Rev 2.0 October 2009 OCX 8800 Parameter Index Number Units Description MODE_BLK 05 None The actual, target, permitted, and normal modes of the block. Target: The mode to “go to” Actual: The mode the “block is currently in” Permitted: Allowed modes that target may take on Normal: Most common mode for target OUT 08 EU of OUT_SCALE OUT_D 37 None Discrete output to indicate a selected alarm condition.
Instruction Manual IM-106-880, Rev 2.0 October 2009 OCX 8800 Figure 7-6. Analog Input Function Block Schematic Analog Measurement ALARM_TYPE Access Analog Meas. HI_HI_LIM HI_LIM LO_LO_LIM LO_LIM CHANNEL Alarm Detection OUT_D ALARM_HYS LOW_CUT Cutoff Convert SIMULATE L_TYPE FIELD_VAL PV Filter PV_FTIME IO_OPTS Status Calc. OUT MODE STATUS_OPTS 38740080 OUT_SCALE XD_SCALE NOTES: OUT = block output value and status. OUT_D = discrete output that signals a selected alarm condition.
Instruction Manual IM-106-880, Rev 2.0 October 2009 FIELD_VAL= 100 x (Channel Value – EU*@0%) (EU*@100% – EU*@0%) * XD_SCALE values 38740082 OCX 8800 You can choose from direct, indirect, or indirect square root signal conversion with the L_TYPE parameter. Direct Direct signal conversion allows the signal to pass through the accessed channel input value (or the simulated value when simulation is enabled).
Instruction Manual IM-106-880, Rev 2.0 October 2009 OCX 8800 Table 7-20. BLOCK_ERR Conditions Condition Number 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 Modes Condition Name and Description Other Block Configuration Error: the selected channel carries a measurement that is incompatible with the engineering units selected in XD_SCALE, the L_TYPE parameter is not configured, or CHANNEL = zero.
Instruction Manual IM-106-880, Rev 2.0 October 2009 OCX 8800 Alarms are grouped into five levels of priority: Priority Number Status Handling Priority Description 0 The priority of an alarm condition changes to 0 after the condition that caused the alarm is corrected. 1 An alarm condition with a priority of 1 is recognized by the system, but is not reported to the operator.
Instruction Manual IM-106-880, Rev 2.0 October 2009 OCX 8800 Advanced Features The AI function block provided with Fisher-Rosemount fieldbus devices provides added capability through the addition of the following parameters: ALARM_TYPE – Allows one or more of the process alarm conditions detected by the AI function block to be used in setting its OUT_D parameter. OUT_D – Discrete output of the AI function block based on the detection of process alarm condition(s).
Instruction Manual IM-106-880, Rev 2.0 October 2009 OCX 8800 Figure 7-8. Analog Input Function Block Configuration for a Typical Temperature Transmitter Temperature Measurement OUT_D OUT To Another Function Block 38740085 AI Function Block Pressure Transmitter used to Measure Level in an Open Tank Situation #1 The level of an open tank is to be measured using a pressure tap at the bottom of the tank. The level measurement will be used to control the level of liquid in the tank.
Instruction Manual IM-106-880, Rev 2.0 October 2009 OCX 8800 Analog Measurement AI Function Block OUT_D OUT BKCAL_OUT BKCAL_IN PID Function Block OUT CAS_IN AO Function Block CAS_IN Situation #2 The transmitter in situation #1 is installed below the tank in a position where the liquid column in the impulse line, when the tank is empty, is equivalent to 2.0 psi (Figure 7-11). Figure 7-11. Situation #2 Diagram 16 ft Empty Tank 2.
Instruction Manual IM-106-880, Rev 2.0 October 2009 OCX 8800 Differential Pressure Transmitter to Measure Flow Situation The liquid flow in a line is to be measured using the differential pressure across an orifice plate in the line, and the flow measurement will be used in a flow control loop.
Instruction Manual IM-106-880, Rev 2.0 October 2009 OCX 8800 Troubleshooting Refer to Table 7-25 to troubleshoot any problems that you encounter. Table 7-25. Troubleshooting Symptom Possible Cause Corrective Action Mode will not leave OOS 1. Target mode not set 1. Set target mode to something other than OOS. 2. Configuration error 2. BLOCK_ERR will show the configuration error bit set. The following are parameters that must be set before the block is allowed out of OOS: a.
Instruction Manual IM-106-880, Rev 2.0 October 2009 OCX 8800 PROPORTIONAL/ INTEGRAL/DERIVATIVE (PID) FUNCTION BLOCK BKCAL_IN BKCAL_OUT CAS_IN FF_VAL PID IN OUT TRK_IN_D TRK_VAL FF_VAL IN TRK_IN_D TRK_VAL = Initiates the external tracking function. = The value after scaling applied to OUTin Local Override mode. BKCAL_OUT = The value and status required by the BKCAL_IN input of another function block to prevent reset windup and to provide bumpless transfer to closed loop control.
Instruction Manual IM-106-880, Rev 2.0 October 2009 OCX 8800 Table 7-26. PID Function Block System Parameters Parameter Index Number Units Description Used to set auto acknowledgment of alarms. ACK_OPTION 46 None ALARM_HYS 47 Percent ALARM_SUM 45 None The summary alarm is used for all process alarms in the block. The cause of the alert is entered in the subcode field. The first alert to become active will set the Active status in the Status parameter.
Instruction Manual IM-106-880, Rev 2.0 October 2009 OCX 8800 Index Number Units Description FF_GAIN 42 None The feedforward gain value. FF_VAL is multiplied by FF_GAIN before it is added to the calculated control output. FF_SCALE 41 None The high and low scale values, engineering units code, and number of digits to the right of the decimal point associated with the feedforward value (FF_VAL). FF_VAL 40 EU of FF_SCALE GAIN 23 None The proportional gain value. This value cannot = 0.
Instruction Manual IM-106-880, Rev 2.0 October 2009 OCX 8800 Index Number Units ROUT_OUT 36 EU of OUT_SCALE SHED_OPT 34 None SP 08 EU of PV_SCALE SP_FTIME 69 Seconds SP_HI_LIM 21 EU of PV_SCALE The highest SP value allowed. SP_LO_LIM 22 EU of PV_SCALE The lowest SP value allowed. SP_RATE_DN 19 EU of PV_SCALE per second Ramp rate for downward SP changes. When the ramp rate is set to zero, the SP is used immediately.
Instruction Manual IM-106-880, Rev 2.0 October 2009 OCX 8800 Figure 7-13.
Instruction Manual IM-106-880, Rev 2.0 October 2009 OCX 8800 Operator Setpoint Auto Man Cas SP_HI_LIM SP_LO_LIM SP_RATE_UP SP_RATE_DN Setpoint Limiting Rate Limiting Auto Man Cas 38740093 Figure 7-14. PID Function Block Setpoint Selection Filtering The filtering feature changes the response time of the device to smooth variations in output readings caused by rapid changes in input.
Instruction Manual IM-106-880, Rev 2.0 October 2009 OCX 8800 You can select the value that a master controller uses for tracking by configuring the Use PV for BKCAL_OUT control option. The BKCAL_OUT value tracks the PV value. BKCAL_IN on a master controller connected to BKCAL_OUT on the PID block in an open cascade strategy forces its OUT to match BKCAL_IN, thus tracking the PV from the slave PID block into its cascade input connection (CAS_IN).
Instruction Manual IM-106-880, Rev 2.0 October 2009 OCX 8800 Table 7-27. BLOCK _ERR Conditions Condition Number 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 Modes Condition Name and Description Other Block Configuration Error: The BY_PASS parameter is not configured and is set to 0, the SP_HI_LIM is less than the SP_LO_LIM, or the OUT_HI_LIM is less than the OUT_LO_LIM. Link Configuration Error Simulate Active Local Override: The actual mode is LO.
Instruction Manual IM-106-880, Rev 2.0 October 2009 Alarm Detection OCX 8800 A block alarm will be generated whenever the BLOCK_ERR has an error bit set. The types of block error for the AI block are defined above. Process alarm detection is based on the PV value.
Instruction Manual IM-106-880, Rev 2.0 October 2009 OCX 8800 Application Information The PID function block is a powerful, flexible control algorithm that is designed to work in a variety of control strategies. The PID block is configured differently for different applications. The following examples describe the use of the PID block for closed-loop control (basic PID loop), feedforward control, cascade control with master and slave, and complex cascade control with override.
Instruction Manual IM-106-880, Rev 2.0 October 2009 OCX 8800 • Local Override is a non-target mode that instructs the block to revert to Local Override when the tracking or fail-safe control options are activated. • Out of Service mode disables the block for maintenance. Abrupt changes in the quality of the input signal can result in unexpected loop behavior. To prevent the output from changing abruptly and upsetting the process, select the SP-PV Track in Man I/O option.
Instruction Manual IM-106-880, Rev 2.0 October 2009 OCX 8800 Figure 7-16. PID Function Block Diagram for Steam Heater Control Example BKCAL_OUT BKCAL_IN AI Function Block PID Function Block OUT OUT CAS_IN AO Function Block IN TCV101 TC101 TT101 OUT 38740096 Outlet Temperature Input Feedforward Control Situation In the previous example, control problems can arise because of a time delay caused by thermal inertia between the two flow streams (TT100 and TT101).
Instruction Manual IM-106-880, Rev 2.0 October 2009 OCX 8800 Figure 7-18.
Instruction Manual IM-106-880, Rev 2.0 October 2009 OCX 8800 Solution If the flow is controlled, steam pressure variations will be compensated before they significantly affect the heat exchanger temperature. The output from the master temperature loop is used as the setpoint for the slave steam flow loop.
Instruction Manual IM-106-880, Rev 2.0 October 2009 OCX 8800 If the instrument connected to the AI block fails, you can place the AI block in Manual mode and set the output to some nominal value for use in the Integrator function block. In this case, IN at the slave PID block is constant and prevents the integral term from increasing or decreasing. Figure 7-21.
Instruction Manual IM-106-880, Rev 2.0 October 2009 OCX 8800 Troubleshooting Refer to Table 7-28 to troubleshoot any problems that you encounter. Table 7-28. Troubleshooting Symptom Possible Causes Corrective Action Mode will not leave OOS 1. Target mode not set 1. Set target mode to something other than OOS. 2. Configuration error 2. BLOCK_ERR will show the configuration error bit set. The following are parameters that must be set before the block is allowed out of OOS: a.
Instruction Manual IM-106-880, Rev 2.0 October 2009 OCX 8800 Symptom Possible Causes Mode sheds from RCAS to AUTO 1. Remote Cascade Value 1. Host system is not writing RCAS_IN with a quality and status of “good cascade” within shed time (see 2 below). Mode sheds from ROUT to MAN Process and/or block alarms will not work Corrective Action 2. Shed Timer 2. The mode shed timer, SHED_RCAS in the resource block is set too low. Increase the value. 1. Remote output value 1.
Instruction Manual IM-106-880, Rev 2.0 October 2009 OCX 8800 Table 7-29.
Instruction Manual IM-106-880, Rev 2.0 October 2009 OCX 8800 Index Number Parameter Units 10 PV_SCALE None 19 20 3 RANGE_HI RANGE_LO STRATEGY None None None 1 ST_REV None 2 35 TAG_DESC UPDATE_EVT None None Description The high and low scale values, engineering units code, and number of digits to the right of the decimal point associated with OUT. The high limit for IN. The low limit for IN. If IN is less than RANGE_LO, then IN_LO is used.
Instruction Manual IM-106-880, Rev 2.0 October 2009 OCX 8800 Condition Number Modes Condition Name and Description 9 Memory Failure 10 Lost Static Data 11 Lost NV Data 12 Readback Check Failed 13 Device Needs Maintenance Now 14 Power Up: The device was just powered-up. 15 Out of Service: The actual mode is out of service. The ARTHM block supports the following modes: • Manual (Man) – The block output (OUT) may be set manually.
Instruction Manual IM-106-880, Rev 2.0 October 2009 OCX 8800 Compensation Input Calculations For each of the inputs IN_1, IN_3, IN_4 there is a gain and bias. The compensation terms (t) are calculated as follows: • When IN_(k) is usable: t(k) = GAIN_IN(k) * (BIAS_IN(k) + IN_(k)) • When IN_(k) is not usable, then t(k) gets the value of the last t(k) computed with a usable input.
Instruction Manual IM-106-880, Rev 2.0 October 2009 OCX 8800 This allows a ratio to be set up that increases the level indication at block output for an increase in the tank temperature relative to ambient temperature. Figure 7-25.
Instruction Manual IM-106-880, Rev 2.0 October 2009 OCX 8800 Troubleshooting Refer to Table 7-32 to troubleshoot any problems that you encounter. Table 7-32. Troubleshooting Symptom Possible Causes Model will not leave OOS Target model not set Corrective Action Set target mode to something other than OOS. Configuration error Status of outputs is BAD Inputs BLOCK_ERR will show the configuration error set. ARITH_TYPE must be set to a valid value and cannot be left at 0.
Instruction Manual IM-106-880, Rev 2.0 October 2009 OCX 8800 Table 7-33. Input Selector Function Block System Parameters Parameter Index Number Units Description ALERT_KEY 4 None BLOCK_ALM 24 None BLOCK_ERR 6 None DISABLE_1 DISABLE_2 DISABLE_3 DISABLE_4 GRANT_DENY 15 16 17 18 9 None None None None None IN_1 11 IN_2 12 IN_3 13 IN_4 14 MIN_GOOD 20 Determined by source Determined by source Determined by source Determined by source None The identification number of the plant unit.
Instruction Manual IM-106-880, Rev 2.0 October 2009 OCX 8800 Figure 7-27. Input Selector Function Block Schematic IN_1 Selection Algorithm IN_2 OUT IN_3 IN_4 DISABLE_1 DISABLE_2 SELECTOR DISABLE_4 SEL_TYPE OP_SELECT MIN_GOOD Block Errors Table 7-34. Block Error Conditions Table 7-34 lists the conditions reported in the BLOCK_ERR parameter. Conditions in italics are inactive for the ISEL block and are listed for reference only.
Instruction Manual IM-106-880, Rev 2.0 October 2009 OCX 8800 Alarms are grouped into five levels of priority, Table 7-35. Table 7-35. Alarm Priorities Priority Block Execution Priority Description Number 0 The priority of an alarm condition changes to 0 after the condition that caused the alarm is corrected. 1 An alarm condition with a priority of 1 is recognized by the system, but is not reported to the operator.
Instruction Manual IM-106-880, Rev 2.0 October 2009 OCX 8800 The instrument must be in Manual or Out of Service mode to set the status option. Application Information The ISEL function block can be used to select the maximum temperature input from four inputs and send it to a PID function block to control a process water chiller (Table 7-28) or it can use the block to calculate the average temperature of the four inputs (Table 7-29). Figure 7-28.
Instruction Manual IM-106-880, Rev 2.0 October 2009 OCX 8800 Troubleshooting Table 7-37. Troubleshooting ISEL Block Symptom Mode w= ill not leave OOS Possible Causes 1. Target mode not set 2. Configuration error 3. Resource block 4. Schedule Status of output is bad 1. Inputs 2. OP selected 3. Min good Block Alarms will not work 1. Features 2. Notification 1. Status Options Corrective Action 1. Set target mode to something other than OOS. 2. BLOCK_ERR will show the configuration error bit set.
Instruction Manual IM-106-880, Rev 2.0 October 2009 OCX 8800 • From the list, select “Add Device Definition”... This should give you a “Browse for folder” selection box. Browse to the directory that contains the 7 files needed to “register” a new device with DeltaV. These file will consist of 3 *.dll files, *.sym, *.ffo, *.fhx and *.reg file. The files probably will be on a floppy disk or a CD-ROM that accompanies your device.
Instruction Manual OCX 8800 7-64 IM-106-880, Rev 2.
Instruction Manual IM-106-880, Rev 2.0 October 2009 Section 8 OCX 8800 Troubleshooting Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 8-1 Diagnostic Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 8-2 Fault Isolation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 8-3 Alarm Relay Events . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Instruction Manual IM-106-880, Rev 2.0 October 2009 OCX 8800 Total Power Loss In the event that the OCX 8800 will not power up at all, check the incoming power supply to make sure power is being delivered to the OCX 8800. If the incoming power supply is good, then check fuses F1 and F6 in the electronics housing. Refer to Figure 8-1 for fuse locations. Figure 8-1.
Instruction Manual IM-106-880, Rev 2.0 October 2009 FAULT ISOLATION OCX 8800 Faults in the OCX 8800 Transmitter are indicated by messages displayed on the 375 Field Communicator or LOI. Fault indications that can appear are listed in Table 8-1, Troubleshooting. If a fault is indicated on the Field Communicator or LOI, locate the fault indication in Table 8-1. For each fault listed, there are related Probable Causes and Recommended Corrective Actions.
Instruction Manual IM-106-880, Rev 2.0 October 2009 OCX 8800 SB Temp Hi (Sample block heater temperature high, > 190ºC) Probable Cause Recommended Corrective Action High noise in OCX power supply Check power supply for line noise or voltage fluctuations. Install power line filter kit (PN 6A00171G01) or high quality line filter for input power.
Instruction Manual IM-106-880, Rev 2.0 October 2009 OCX 8800 SB TC Open (Sample block heater thermocouple open) Probable Cause Recommended Corrective Action Sample block thermocouple or thermocouple circuit open Check sample block thermocouple and circuit wires for breaks or loose connections per Figure 8-3 and Figure 9-8. Repair breaks or loose connections or replace failed thermocouple. Perform Reset procedure in Section 3, Configuration and Startup to continue operation.
Instruction Manual IM-106-880, Rev 2.0 October 2009 OCX 8800 ADC Failure (Voltage to digital conversion could not complete) ADC Ref Error (Voltage to digital conversion not accurate) Probable Cause Recommended Corrective Action Incorrect wiring between electronics and sensor housings Electronics package failure Check all wiring between the electronics and sensor housings per Figure 8-3. Correct wiring faults. Replace electronics package.
Instruction Manual IM-106-880, Rev 2.0 October 2009 OCX 8800 Cal Warning (Calibration warning) Cal Failed (Calibration failed) Probable Cause Recommended Corrective Action COe sensor degraded Replace COe sensor or increase warning level (SYSTEM, CALIB SETUP, COe Slope Warn via HART.
Instruction Manual IM-106-880, Rev 2.0 October 2009 OCX 8800 Board Temp Hi (Electronics temperature maximum exceeded, > 85ºC) Probable Cause Recommended Corrective Action Electronics housing exposed to high ambient temperature Insulate housing from source of high temperature and/or install cooling fan to remove heat from housing. Perform Reset procedure in Section 3, Configuration and Startup to continue operation.
Instruction Manual IM-106-880, Rev 2.0 October 2009 OCX 8800 Line Voltage High (AC power line voltage above maximum, > 278 VAC) Probable Cause Recommended Corrective Action High noise or voltage fluctuations in power supply Electronics package failure Check power supply for line noise or voltage fluctuations. Install power line filter kit (PN 6A00171G01) or high quality line filter for input power. Check power supply voltage and compare with line voltage.
Instruction Manual IM-106-880, Rev 2.0 October 2009 OCX 8800 #1 2HTR CO 1HTR CO 2HTR O2 1HTR O2 2HTR SB 1HTR SB YEL RED BLK ORG WHT BLU SHIELD GRN Figure 8-3.
Instruction Manual IM-106-880, Rev 2.0 October 2009 ALARM RELAY EVENTS OCX 8800 The OCX 8800 contains an alarm relay that can be configured to activate on one of twelve different groups of events. These event groups, and the conditions that trigger them, are listed in Table 8-2, Alarm Relay Event Groups. Table 8-2.
Instruction Manual OCX 8800 8-12 IM-106-880, Rev 2.
Instruction Manual IM-106-880, Rev 2.0 September 2009 Section 9 OCX 8800 Maintenance and Service Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 9-1 OCX 8800 Removal and Installation . . . . . . . . . . . . . . . . . page 9-1 Repair Sensor Housing . . . . . . . . . . . . . . . . . . . . . . . . . . . page 9-10 Repair Electronics Housing . . . . . . . . . . . . . . . . . . . . . . . . page 9-29 Replace Tube Fittings . . . . . . . . . . . . . . . . . . . . . . .
Instruction Manual IM-106-880, Rev 2.0 September 2009 OCX 8800 OCX with Integral Electronics Remove OCX 8800 1. Turn off power to the system. 2. Shut off the test gases at the cylinders and shut off the instrument air. 3. Disconnect the test gas and instrument air lines from the electronics housing, Figure 9-1. Figure 9-1.
Instruction Manual IM-106-880, Rev 2.0 September 2009 OCX 8800 Figure 9-2.
Instruction Manual IM-106-880, Rev 2.0 September 2009 OCX 8800 Install OCX 8800 Observe the following cautions when installing the OCX 8800 in a hot process stack. If the process is shut down and cooled, the transmitter can be installed in the stack prior to connecting the pneumatics and wiring. Whenever a positive stack pressure exists at the installation site, be sure to connect all pneumatic lines prior to installing the OCX 8800 in the stack or ductwork.
Instruction Manual IM-106-880, Rev 2.0 September 2009 OCX with Remote Electronics OCX 8800 Remove Sensor Housing 1. Turn off power to the system. 2. Shut off the test gasses at the cylinders and close the instrument air valve. 3. Disconnect the calibration gas, reference air, eductor air, and dilution air lines from the sensor housing, Figure 9-3. Figure 9-3.
Instruction Manual OCX 8800 IM-106-880, Rev 2.0 September 2009 4. Remove the cover from the sensor housing to expose the sensor housing terminal blocks, Figure 9-4. 5. Disconnect the signal cable from the O2 and T/C terminal blocks, and from the CO and CJC terminal blocks. 6. Disconnect the heater power cable from the HTR terminal blocks. 7. If moving the sensor housing to another work site, disconnect and remove the power and signal cables from the sensor housing. 8.
Instruction Manual IM-106-880, Rev 2.0 September 2009 OCX 8800 Install Sensor Housing 1. Insert and bolt the sensor housing in the stack and install insulation. 2. Connect the test gas, reference air, eductor air, and dilution air lines to the sensor housing. 3. Remove the sensor housing cover. 4. If removed, install the power and signal cables and the customer power and signal conduits and wiring at the sensor housing. 5.
Instruction Manual IM-106-880, Rev 2.0 September 2009 OCX 8800 Figure 9-5.
Instruction Manual IM-106-880, Rev 2.0 September 2009 OCX 8800 Figure 9-6.
Instruction Manual IM-106-880, Rev 2.0 September 2009 OCX 8800 Install Remote Electronics Housing 1. Mount remote electronics housing on wall or pipe within distance of signal and heater cables in use. 2. Remove the electronics housing cover. 3. If removed, install the power and signal cables and the customer power and signal conduits and wiring at the electronics housing. 4. Connect the signal cable leads to the O2 cell and thermocouple connector (J4), and to the COe and CJC connector (J5), Figure 9-6.
Instruction Manual IM-106-880, Rev 2.0 September 2009 OCX 8800 Figure 9-7. Removal of O2 Cell and Heater Strut Assembly Screw Locking Clip Cover O-ring Marking Plate Terminal Insulator Reference Air Tube Sensor Housing Heater Strut Assembly Gasket Screw Heater Clamp Heater Rod 3 7 4 9 5 6 11 10 12 8 13 2 1 37390067 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. Remove O2 Cell and Heater Strut Assembly 1. Remove reference air tube (7, Figure 9-7) from sensor housing (8). 2. See Figure 9-8.
Instruction Manual IM-106-880, Rev 2.0 September 2009 OCX 8800 Remove Sample Block Heater Rods 1. Disconnect sample block heater rod wires from terminal block. Refer to Figure 9-8. 2. Loosen screws (11, Figure 9-7) and rotate heater clamps (12) to release heater rods (13). One heater clamp secures each heater rod. 3. Slide sample block heater rods (13) out of housing (8).
Instruction Manual IM-106-880, Rev 2.0 September 2009 OCX 8800 Remove COe Sensor Assembly 1. Disconnect COe heater, thermocouple, and sensor wires from terminal blocks. Refer to Figure 9-9. 2. Remove insulator (1, Figure 9-10). NOTE For easier access, you may remove two screws from base of terminal block mounting (13) and move terminal block assembly out of the way. 3. Remove tubes (2, 3, and 4) from COe sensor assembly (5), eductor fittings (12 and 15), and sensor housing (7). 4.
Instruction Manual IM-106-880, Rev 2.0 September 2009 OCX 8800 Figure 9-10. Removal of COe Sensor Assembly 4 3 5 8 1 11 9 2 15 10 6 12 13 16 14 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. 15. 16.
Instruction Manual IM-106-880, Rev 2.0 September 2009 OCX 8800 6. See Figure 9-11. Using straightedge on the sensor holder flat, as shown, matchmark upper flange of sensor housing to show correct alignment of sensor holder. 7. With one wrench holding eductor elbow (12, Figure 9-10), and one wrench on flats of sensor holder (11), unthread and remove COe sensor assembly (5). Do not allow eductor elbow to turn. 8. Slide band heater (10) and heater insulator (9) from sensor holder (11). Figure 9-11.
Instruction Manual IM-106-880, Rev 2.0 September 2009 OCX 8800 Figure 9-12. Eductor Alignment Matchmarks Eductor Flat Straightedge 37390036 Matchmark Remove Eductor The O2 cell and heater strut assembly (9, Figure 9-7) and the COe sensor assembly (5, Figure 9-10) must be removed before you start this procedure. 1. Use straightedge to matchmark alignment of eductor flat and elbow, as shown in Figure 9-12. 2. Unscrew terminal block mounting (13, Figure 9-10).
Instruction Manual IM-106-880, Rev 2.0 September 2009 OCX 8800 Figure 9-13. Removal of Sample and Exhaust Tubes Remove Sample and Exhaust Tubes Use heat resistant gloves when removing the probe tube or exhaust tube. The tubes are bonded with a thread sealing compound. The compound softens at 450°F (232°C). The heated parts can cause severe burns. 1. Secure the sensor housing (1, Figure 9-13) in soft (plastic, wood, or brass) vice jaws. 2.
Instruction Manual IM-106-880, Rev 2.0 September 2009 OCX 8800 Figure 9-14. O2 Cell, Heater, and Thermocouple, Exploded View Do not remove the O2 cell unless you are certain it needs to be replaced. Removal may damage the cell and platinum pad. Remove the O2 cell for cell replacement only. Disassemble O2 Cell and Heater Strut Assembly Do not attempt to replace the O2 cell until all other possibilities for poor performance have been considered.
Instruction Manual IM-106-880, Rev 2.0 September 2009 OCX 8800 Disassemble COe Sensor Assembly 1. Carefully remove screws (1, Figure 9-15), lockwashers (2), and COe sensor (3) from sensor holder (4). Remove and discard gasket (5). 2. If damaged, use the following procedure to remove thermocouple adaptor (6) from sensor holder (4): a. Use a propane torch to heat the thermocouple adaptor to 450°F (232°C), minimum. b. While heating, use a flat-head screwdriver to apply removal torque.
Instruction Manual IM-106-880, Rev 2.0 September 2009 OCX 8800 Always remove the stainless steel balls (approximately 200) from sensor holder before removing or installing pre-heater. Turning pre-heater in the sensor holder with the stainless steel balls in place will cause permanent damage to the pre-heater. 3. If pre-heater (7) is to be removed, clamp flats of sensor holder (4) in vise jaws with plug (8) pointing up. Remove plug.
Instruction Manual IM-106-880, Rev 2.0 September 2009 OCX 8800 Figure 9-16. COe Sensor and Pre-Heater Alignment COe SENSOR ASSEMBLY TOP VIEW THERMOCOUPLE Sensor Holder Sensor Holder Flat Pre-Heater Flat Sensor Holder Flat 37390034 2 to 2-1/4 in. (51 to 57 mm) COe Sensor Flat 7. Install COe sensor (3), lockwashers (2), and screws (1). Rotate flat of COe sensor (3) to center of sensor holder (4). 8. Align COe sensor flat parallel to sensor holder flat, as shown in Figure 9-16.
Instruction Manual IM-106-880, Rev 2.0 September 2009 OCX 8800 Install Eductor If installed, the O2 cell and heater strut assembly (9, Figure 9-7) must be removed from sensor housing (8), before you install the eductor. 1. Apply pipe thread sealant (Loctite #567) to the external pipe threads of eductor (6, Figure 9-17). Do not apply sealant to the first turn of the pipe threads. Figure 9-17. Installation of Eductor and COe Sensor 4 3 5 8 1 11 9 2 15 10 6 12 13 16 14 1. 2. 3. 4. 5. 6. 7. 8. 9.
Instruction Manual IM-106-880, Rev 2.0 September 2009 OCX 8800 2. Install and tighten eductor (6) in eductor holder (14). 3. Install and tighten elbow (12) on eductor (6). Male port of elbow must point up and be in line with long axis of eductor. 4. Apply anti-seize compound to the external pipe threads of eductor holder (14). 5. Install and tighten eductor holder (14) in sensor housing (7). Align eductor with matchmarks, as shown in Figure 9-18. Figure 9-18.
Instruction Manual IM-106-880, Rev 2.0 September 2009 OCX 8800 Install COe Sensor Assembly Figure 9-19. Band Heater Height COe Sensor 1. Apply pipe thread sealant (Loctite #567) to the exposed pipe threads of eductor elbow (12, Figure 9-17). Do not apply sealant to the first turn of the pipe threads. 2. Screw sensor holder (11) onto eductor elbow (12). 0.37 in. (9,4 mm) 3. With wrenches on eductor elbow (12) and on flats of sensor holder (11), tighten sensor holder. Do not allow eductor elbow to turn.
Instruction Manual IM-106-880, Rev 2.0 September 2009 OCX 8800 8. Install and fasten thermocouple (8, Figure 9-17). 9. Position band heater as shown in Figure 9-19 and Figure 9-20 and tighten band heater clamp screw. The heater insulator (9) end joint must line up with the band gap of the COe band heater (10). 10. Reconnect the COe sensor, thermocouple, and heater wires at the sensor housing terminal blocks. Refer to Figure 9-21. 11.
Instruction Manual IM-106-880, Rev 2.0 September 2009 OCX 8800 Figure 9-22. Installation of O2 Cell and Heater Strut Assembly 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13.
Instruction Manual IM-106-880, Rev 2.0 September 2009 OCX 8800 Install Sample Block Heater Rods 1. Before installing sample block heater rods (13, Figure 9-22), evenly coat the heater rods with Watlube heater release agent. 2. Install the heater rods (13), heater clamps (12), and screws (11). 3. Reconnect the heater rod leads at the sensor housing terminal blocks, (Figure 9-23). Figure 9-23.
Instruction Manual IM-106-880, Rev 2.0 September 2009 OCX 8800 Install O2 Cell and Heater Strut Assembly 1. Rub a small amount of anti-seize compound on both sides of new gasket (10, Figure 9-22). 2. Apply anti-seize compound to threads of O2 cell and heater strut assembly (9) and sensor housing (8). Stripped threads on the O2 cell and heater strut assembly can allow gas leakage. Gas leakage can affect the O2 measurements and calibration. Avoid over-tightening the O2 cell and heater strut assembly. 3.
Instruction Manual IM-106-880, Rev 2.0 September 2009 OCX 8800 REPAIR ELECTRONICS HOUSING Use the following procedures to remove damaged components from the OCX 8800 electronics housing and to install new replacement parts. Disassemble the unit only as needed to replace damaged components. Use the assembly procedures that apply to install replacement parts and reassemble the unit. Electronics Housing Disassembly Remove Cover 1. See Figure 9-24.
Instruction Manual IM-106-880, Rev 2.0 September 2009 OCX 8800 Figure 9-24. Removal/Installation of Electronics Housing Components Ana lyti cal 8 11 7 12 10 3 9 13 6 14 5 15 4 16 Screw Locking Clip Cover O-ring Electronics Stack Flash PROM Screw LOI Module LOI Board LOI Connector Screw Lockwasher Screw Lockwasher Solenoid Valve (3 way) Solenoid Valve 2 1 37390037 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. 15. 16. Remove Electronics Stack 1.
Instruction Manual IM-106-880, Rev 2.0 September 2009 OCX 8800 Remove Solenoid Valves 1. Disconnect solenoid leads from mating terminal connector. 2. Remove top nut of solenoid valve (15 or 16, Figure 9-24). 3. Remove the solenoid coil assembly and washer. 4. Unthread and remove solenoid valve base. Remove EMI Filter and Terminal Block 1. Disconnect EMI filter wiring (Figure 9-25) at terminal block (3). 2. Disconnect EMI filter wiring at AC power input terminal block on electronic stack. 3.
Instruction Manual IM-106-880, Rev 2.0 September 2009 OCX 8800 Install Solenoid Valves 1. Disassemble replacement solenoid valve (15 or 16, Figure 9-24). 2. Install new solenoid valve base. Be careful not to overtighten. 3. Install new washer and solenoid coil assembly and secure with nut. 4. Connect the solenoid leads to the proper terminations on the solenoid power terminal block (Figure 9-27). Install Electronics Stack 1.
Instruction Manual IM-106-880, Rev 2.0 September 2009 OCX 8800 Figure 9-26.
Instruction Manual IM-106-880, Rev 2.0 September 2009 OCX 8800 Figure 9-27. Solenoid Power Terminals SOL 2 SOL 3 SOL 4 SOL 1 TOP VIEW SOL 4 CO Test Gas SOL 3 SOL 2 High O2 Test Gas Low O2 Test Gas SOL 1 Instrument Air #1 37390033 #1 Install Cover 1. If removed, install cover gasket (4, Figure 9-24). Screw cover (3) onto electronics housing. Tighten cover firmly. Align locking clip (2) with gap between cover ribs. 2.
Instruction Manual IM-106-880, Rev 2.0 September 2009 REPLACE TUBE FITTINGS OCX 8800 The OCX transmitter housings have special tube fittings that, if clogged or damaged, must be replaced with the same type of fitting. The special tube fittings have alpha or numeric codes etched on the fitting. Unetched tube fittings are standard 1/4 inch, stainless steel fittings. ‘E’ Type Fitting The ‘E’ type fitting is an eductor drive air fitting for the OCX 8800 general purpose sensor housing.
Instruction Manual IM-106-880, Rev 2.0 September 2009 OCX 8800 Figure 9-28. Removal of Tube Fittings 5 3 4 1. 2. 3. 4. 5. Sensor Housing Electronics Housing Tube Fitting Tube Fitting (Type R) Tube Fitting (Type E) 1 3 3 Install Tube Fittings 37390070 3 2 1. Verify that the replacement tube fitting is identical to the item removed. Special fittings are etched with code markings. 2. Apply pipe thread sealant (Loctite #567) to the mating threads of the tube fitting.
Instruction Manual IM-106-880, Rev 2.0 October 2009 Section 10 OCX 8800 Replacement Parts Sensor Housing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 10-2 Electronics Housing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 10-6 O2 Cell and Heater Strut Assembly . . . . . . . . . . . . . . . . . page 10-9 http://www..raihome.
Instruction Manual IM-106-880, Rev 2.0 October 2009 OCX 8800 SENSOR HOUSING Figure 10-1.
Instruction Manual IM-106-880, Rev 2.0 October 2009 OCX 8800 Index No. Part Number 1 5R10190G02 5R10190G03 6P00177H01 4851B46G03 1A99786H01 6P00163H01 1A99746H02 1A99749H01 1A99747H01 5R10200H01 6A00123G01 6P00155H02 1A98765H02 1A99520H01 2 3 4 5 6 7 8 9 10 11 12 13 Description O2 Cell and Heater Assembly, Standard Cell O2 Cell and Heater Assembly, High Sulfur Cell Heater Insulator, Mica Combustibles Sensor Replacement Kit Heater Leads Insulator, 14.
Instruction Manual OCX 8800 Figure 10-2. Sensor Housing Components (Sheet 2 of 2) 10-4 IM-106-880, Rev 2.
Instruction Manual IM-106-880, Rev 2.0 October 2009 OCX 8800 Index No. Part Number Description 1 2 3 1A99089H02 5R10246H06 1A98448H02 Cover Gasket (O-ring) Blowback Filter, 5 Micron, Stainless Steel O-ring 4 5R10247H01 Fitting 5 5R10183H02 Tube, Sample, 18 in. (457 mm) 316 Stainless steel 5R10183H06 Tube, Sample, 18 in. (457 mm) Inconel 600 5R10227G01 Tube, Sample, 18 in. (457 mm) Ceramic 5R10183H03 Tube, Sample, 3 ft. (0.91 m) 316 Stainless steel 5R10183H07 Tube, Sample, 3 ft. (0.
Instruction Manual IM-106-880, Rev 2.0 October 2009 OCX 8800 ELECTRONICS HOUSING Figure 10-3.
Instruction Manual IM-106-880, Rev 2.0 October 2009 OCX 8800 Index No.
Instruction Manual IM-106-880, Rev 2.0 October 2009 OCX 8800 Figure 10-4. EMI Filter and Terminal Block Blue Brown Blue Green Brown Green Green 1 37390083 2 3 10-8 Index No.
Instruction Manual IM-106-880, Rev 2.0 October 2009 OCX 8800 O2 CELL AND HEATER STRUT ASSEMBLY Figure 10-5. O2 Cell and Heater Strut Assembly 1 2 3 4 37390055 7 5 6 Index No.
Instruction Manual OCX 8800 10-10 IM-106-880, Rev 2.
Instruction Manual IM-106-880, Rev 2.0 September 2009 Appendix A OCX 8800 Safety Data Safety Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page A-2 Safety Data Sheet for Ceramic Fiber Products . . . . . . . . page A-24 High Pressure Gas Cylinders . . . . . . . . . . . . . . . . . . . . . . page A-30 http://www..raihome.
Instruction Manual IM-106-880, Rev 2.0 September 2009 OCX 8800 SAFETY INSTRUCTIONS IMPORTANT SAFETY INSTRUCTIONS FOR THE WIRING AND INSTALLATION OF THIS APPARATUS The following safety instructions apply specifically to all EU member states. They should be strictly adhered to in order to assure compliance with the Low Voltage Directive. Non-EU states should also comply with the following unless superseded by local or National Standards. 1.
Instruction Manual IM-106-880, Rev 2.0 September 2009 OCX 8800 DŮLEŽITÉ Bezpečnostní pokyny pro zapojení a instalaci zařízení Následující bezpečnostní pokyny se speciálně vztahují na všechny členské státy EU. Pokyny by měly být přísně dodržovány, aby se zajistilo splnění Směrnice o nízkém napětí. Pokud nejsou pokyny nahrazeny místními či národními normami, měly by je dodržovat i nečlenské státy EU. 1. U všech zemnicích bodů, interních a externích, by mělo být vytvořeno odpovídající uzemnění. 2.
Instruction Manual IM-106-880, Rev 2.0 September 2009 OCX 8800 VIGTIGT Sikkerhedsinstruktion for tilslutning og installering af dette udstyr. Følgende sikkerhedsinstruktioner gælder specifikt i alle EU-medlemslande. Instruktionerne skal nøje følges for overholdelse af Lavsspændingsdirektivet og bør også følges i ikke EU-lande medmindre andet er specificeret af lokale eller nationale standarder. 1. Passende jordforbindelser skal tilsluttes alle jordklemmer, interne og eksterne, hvor disse forefindes. 2.
Instruction Manual IM-106-880, Rev 2.0 September 2009 OCX 8800 BELANGRIJK Veiligheidsvoorschriften voor de aansluiting en installatie van dit toestel. De hierna volgende veiligheidsvoorschriften zijn vooral bedoeld voor de EU lidstaten. Hier moet aan gehouden worden om de onderworpenheid aan de Laag Spannings Richtlijn (Low Voltage Directive) te verzekeren. Niet EU staten zouden deze richtlijnen moeten volgen tenzij zij reeds achterhaald zouden zijn door plaatselijke of nationale voorschriften. 1.
Instruction Manual IM-106-880, Rev 2.0 September 2009 OCX 8800 BELANGRIJK Veiligheidsinstructies voor de bedrading en installatie van dit apparaat. Voor alle EU lidstaten zijn de volgende veiligheidsinstructies van toepassing. Om aan de geldende richtlijnen voor laagspanning te voldoen dient men zich hieraan strikt te houden. Ook niet EU lidstaten dienen zich aan het volgende te houden, tenzij de lokale wetgeving anders voorschrijft. 1.
Instruction Manual IM-106-880, Rev 2.0 September 2009 OCX 8800 WICHTIG Sicherheitshinweise für den Anschluß und die Installation dieser Geräte. Die folgenden Sicherheitshinweise sind in allen Mitgliederstaaten der europäischen Gemeinschaft gültig. Sie müssen strickt eingehalten werden, um der Niederspannungsrichtlinie zu genügen. Nichtmitgliedsstaaten der europäischen Gemeinschaft sollten die national gültigen Normen und Richtlinien einhalten. 1.
Instruction Manual IM-106-880, Rev 2.0 September 2009 OCX 8800 ΣΗΜΑΝΤΙΚΟ Οδηγιεσ ασφαλειασ για την καλωδιωση και εγκατασταση τησ συσκευησ Οι ακόλουθες οδηγίες ασφαλείας εφαρµόζονται ειδικά για όλες τις χώρες µέλη της Ευρωπαϊκής Κοινότητας. Θα πρέπει να ακολουθούνται αυστηρά ώστε να εξασφαλιστεί η συµβατότητα µε τις οδηγίες για τη Χαµηλή Τάση. Χώρες που δεν είναι µέλη της Ευρωπαϊκής Κοινότητας θα πρέπει επίσης να ακολουθούν τις οδηγίες, εκτός εάν αυτές αντικαθίστανται από τα Τοπικά ή Εθνικά πρότυπα. 1.
Instruction Manual IM-106-880, Rev 2.0 September 2009 OCX 8800 OLULINE TEAVE Juhtmestiku ja seadme paigaldamisega seotud ohutusjuhised Alljärgnevad ohutusjuhised rakenduvad eriti kõigi Euroopa Liidu liikmesriikide suhtes. Antud juhiseid tuleb täpselt järgida, et kindlustada vastavus madalpinge direktiiviga. Euroopa Liitu mittekuuluvad riigid peavad samuti alljärgnevaid juhiseid järgima, va juhul, kui on olemas vastavad kohalikud riiklikud standardid. 1.
Instruction Manual IM-106-880, Rev 2.0 September 2009 OCX 8800 TÄRKEÄÄ Turvallisuusohje, jota on noudatettava tämän laitteen asentamisessa ja kaapeloinnissa. Seuraavat ohjeet pätevät erityisesti EU:n jäsenvaltioissa. Niitä täytyy ehdottomasti noudattaa jotta täytettäisiin EU:n matalajännitedirektiivin (Low Voltage Directive) yhteensopivuus. Myös EU:hun kuulumattomien valtioiden tulee nou-dattaa tätä ohjetta, elleivät kansalliset standardit estä sitä. 1.
Instruction Manual IM-106-880, Rev 2.0 September 2009 OCX 8800 IMPORTANT Consignes de sécurité concernant le raccordement et l'installation de cet appareil. Les consignes de sécurité ci-dessous s'adressent particulièrement à tous les états membres de la communauté européenne. Elles doivent être strictement appliquées afin de satisfaire aux directives concernant la basse tension.
Instruction Manual IM-106-880, Rev 2.0 September 2009 OCX 8800 FONTOS Biztonsági előírások a készülék vezetékeléséhez és üzembeállításához A következő biztonsági előírások kifejezetten vonatkoznak az összes EU-tagállamra. Ezeket szigorúan be kell tartani a Kisfeszültségű irányelvnek való megfelelés biztosításához. A nem EU-tagállamok szintén tartsák be a következőket, kivéve ha a helyi és nemzeti szabványok azt másként nem írják elő. 1.
Instruction Manual IM-106-880, Rev 2.0 September 2009 OCX 8800 IMPORTANTE Norme di sicurezza per il cablaggio e l'installazione dello strumento. Le seguenti norme di sicurezza si applicano specificatamente agli stati membri dell'Unione Europea, la cui stretta osservanza è richiesta per garantire conformità alla Direttiva del Basso Voltaggio. Esse si applicano anche agli stati non appartenenti all'Unione Europea, salvo quanto disposto dalle vigenti normative locali o nazionali. 1.
Instruction Manual IM-106-880, Rev 2.0 September 2009 OCX 8800 SVARBU šio prietaiso laidų prijungimo ir instaliacijos saugos instrukcijos Toliau išvardinti saugumo reikalavimai taikomi konkrečiai visoms ES šalims narėms. Jų turi būti griežtai paisoma, kad būtų užtikrintai laikomasi Žemos įtampos direktyvos. Ne ES narės taip pat turi laikytis toliau pateikiamų reikalavimų nebent juos pakeičia vietiniai ar Nacionaliniai standartai. 1.
Instruction Manual IM-106-880, Rev 2.0 September 2009 OCX 8800 SVARĪGI Droš ības norādījumi š īs iekārtas pievienoš anai un uzstādīš anai Turpmākie drošības norādījumi attiecas uz visām ES dalībvalstīm. Tie ir stingri jāievēro, lai nodrošinātu atbilstību Zemsprieguma direktīvai. Turpmāk norādītais jāievēro arī valstīs, kas nav ES dalībvalstis, ja vien šos norādījumus neaizstāj vietējie vai valsts standarti. 1. Visi pieejamie iekšējie un ārējie zemējuma punkti ir atbilstoši jāiezemē. 2.
Instruction Manual IM-106-880, Rev 2.0 September 2009 OCX 8800 IMPORTANTI STRUZZJONIJIET TAS-SIGURTÀ GĦALL-WIRING U L-INSTALLAZZJONI TAT-TAGĦMIR L-istruzzjonijiet tas-sigurtà japplikaw speċifikament għall-Istati Membri ta' l-UE. Dawn għandhom jiġu osservati b'mod strett biex tkun żgurata lkonformità mad-Direttiva dwar il-Vultaġġ Baxx. Stati li mhumiex membri ta' l-UE għandhom ukoll ikunu konformi ma' dan li ġej ħlief jekk dawn ikunu sostituti mill-Istandards lokali jew Nazzjonali. A-16 1.
Instruction Manual IM-106-880, Rev 2.0 September 2009 OCX 8800 VIKTIG Sikkerhetsinstruks for tilkobling og installasjon av dette utstyret. Følgende sikkerhetsinstruksjoner gjelder spesifikt alle EU medlemsland og land med i EØS-avtalen. Instruksjonene skal følges nøye slik at installasjonen blir i henhold til lavspenningsdirektivet. Den bør også følges i andre land, med mindre annet er spesifisert av lokale- eller nasjonale standarder. 1.
Instruction Manual IM-106-880, Rev 2.0 September 2009 OCX 8800 WAŻNE! Zalecenia dotyczące bezpieczeństwa w zakresie podłączania i instalacji tego urządzenia Następujące zalecenia dotyczą zwłaszcza stosowania urządzenia we wszystkich krajach Unii Europejskiej. Należy się ściśle do nich stosować w celu zapewnienia zgodności z dyrektywą niskonapięciową.
Instruction Manual IM-106-880, Rev 2.0 September 2009 OCX 8800 IMPORTANTE Instruções de segurança para ligação e instalação deste aparelho. As seguintes instruções de segurança aplicam-se especificamente a todos os estados membros da UE. Devem ser observadas rigidamente por forma a garantir o cumprimento da Directiva sobre Baixa Tensão. Relativamente aos estados que não pertençam à UE, deverão cumprir igualmente a referida directiva, exceptuando os casos em que a legislação local a tiver substituído. 1.
Instruction Manual IM-106-880, Rev 2.0 September 2009 OCX 8800 DÔLEŽITÉ Bezpečnostné pokyny pre zapojenie káblov a inš taláciu tohto prístroja Nasledovné bezpečnostné pokyny sa vzt’ahujú konkrétne na všetky členské štáty EÚ. Musia byt’ striktne dodržané, aby sa zaistila zhoda so Smernicou o nízkom napätí. Štáty, ktoré nie sú členskými štátmi EÚ by mali nasledovné pokyny taktiež dodržiavat’, pokiaľ nie sú nahradené miestnymi alebo národnými normami. 1.
Instruction Manual IM-106-880, Rev 2.0 September 2009 OCX 8800 POMEMBNO Varnostna navodila za povezavo in vgradnjo naprave Naslednja varnostna navodila veljajo za vse države članice EU. Zaradi zagotovitve skladnosti z nizkonapetostno direktivo morate navodila strogo upoštevati. V državah, ki niso članice EU, je treba upoštevati tudi naslednje smernice, razen če jih ne zamenjujejo lokalni ali nacionalnimi standardi. 1.
Instruction Manual IM-106-880, Rev 2.0 September 2009 OCX 8800 IMPORTANTE Instrucciones de seguridad para el montaje y cableado de este aparato. Las siguientes instrucciones de seguridad, son de aplicacion especifica a todos los miembros de la UE y se adjuntaran para cumplir la normativa europea de baja tension. 1. Se deben preveer conexiones a tierra del equipo, tanto externa como internamente, en aquellos terminales previstos al efecto. 2.
Instruction Manual IM-106-880, Rev 2.0 September 2009 OCX 8800 VIKTIGT Säkerhetsföreskrifter för kablage och installation av denna apparat. Följande säkerhetsföreskrifter är tillämpliga för samtliga EU-medlemsländer. De skall följas i varje avseende för att överensstämma med Lågspännings direktivet. Icke EU medlemsländer skall också följa nedanstående punkter, såvida de inte övergrips av lokala eller nationella föreskrifter. 1.
Instruction Manual IM-106-880, Rev 2.0 September 2009 OCX 8800 SAFETY DATA SHEET FOR CERAMIC FIBER PRODUCTS JULY 1, 1996 SECTION I. IDENTIFICATION PRODUCT NAME Ceramic Fiber Heaters, Molded Insulation Modules and Ceramic Fiber Radiant Heater Panels. CHEMICAL FAMILY Vitreous Aluminosilicate Fibers with Silicon Dioxide. CHEMICAL NAME N.A. CHEMICAL FORMULA N.A. MANUFACTURER'S NAME AND ADDRESS Watlow Columbia 2101 Pennsylvania Drive Columbia, MO 65202 573-814-1300, ext.
Instruction Manual IM-106-880, Rev 2.0 September 2009 OCX 8800 SECTION IV. FIRE AND EXPLOSION DATA FLASH POINT: None FLAMMABILITY LIMITS: N.A. EXTINGUISHING MEDIA Use extinguishing agent suitable for type of surrounding fire. UNUSUAL FIRE AND EXPLOSION HAZARDS / SPECIAL FIRE FIGHTING PROCEDURES N.A. SECTION V. HEALTH HAZARD DATA THRESHOLD LIMIT VALUE (See Section III) EFFECTS OF OVER EXPOSURE • EYE - Avoid contact with eyes. Slightly to moderately irritating.
Instruction Manual IM-106-880, Rev 2.0 September 2009 OCX 8800 3. A statistical "trend" was observed in the exposed population between the duration of exposure to RCF and a decrease in some measures of pulmonary function. These observations are clinically insignificant. In other words, if these observations were made on an individual employee, the results would be interpreted as being within the normal range. 4.
Instruction Manual IM-106-880, Rev 2.0 September 2009 OCX 8800 SECTION VI. REACTIVITY DATA STABILITY/CONDITIONS TO AVOID Stable under normal conditions of use. HAZARDOUS POLYMERIZATION/CONDITIONS TO AVOID N.A. INCOMPATIBILITY/MATERIALS TO AVOID Incompatible with hydrofluoric acid and concentrated alkali. HAZARDOUS DECOMPOSITION PRODUCTS N.A. SECTION VII.
Instruction Manual IM-106-880, Rev 2.0 September 2009 OCX 8800 SECTION IX. SPECIAL PRECAUTIONS PRECAUTIONS TO BE TAKEN IN HANDLING AND STORING General cleanliness should be followed. The Toxicology data indicate that ceramic fiber should be handled with caution. The handling practices described in this MSDS must be strictly followed.
Instruction Manual IM-106-880, Rev 2.0 September 2009 OCX 8800 If airborne fiber or cristobalite concentrations are not known, as minimum protection, use NIOSH/MSHA approved half face, air purifying respirator with HEPA filter cartridges. Insulation surface should be lightly sprayed with water before removal to suppress airborne dust. As water evaporates during removal, additional water should be sprayed on surfaces as needed.
Instruction Manual OCX 8800 HIGH PRESSURE GAS CYLINDERS IM-106-880, Rev 2.0 September 2009 GENERAL PRECAUTIONS FOR HANDLING AND STORING HIGH PRESSURE GAS CYLINDERS • Edited from selected paragraphs of the Compressed Gas Association's "Handbook of Compressed Gases" published in 1981 Compressed Gas Association 1235 Jefferson Davis Highway Arlington, Virginia 22202 Used by Permission 1. Never drop cylinders or permit them to strike each other violently. 2.
Instruction Manual IM-106-880, Rev 2.0 September 2009 Appendix B OCX 8800 SPA with HART Alarm Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page B-1 Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page B-1 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page B-2 Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Instruction Manual IM-106-880, Rev 2.0 September 2009 OCX 8800 Figure B-2. OCX 8800 and SPA Interface Connections INSTALLATION Refer to Figure B-2 for the typical interface connections for the OCX 8800 and the SPA with HART alarm. Refer to the Moore Industries SPA user's manual for additional information concerning SPA installation, setup, and operation.
Instruction Manual IM-106-880, Rev 2.0 September 2009 OCX 8800 Figure B-3. SPA Jumper and Dip Switch Settings NOTICE REMOVE THIS PANEL FOR SERVICE ACCESS. STATIC SENSITIVE. USE CAUTION WHEN CHANGING JUMPERS Access Cover SPA - Bottom View Source Current Dip Switches (shown in correct position) Figure B-4. SPA Setup for Calibration Password OFF Failsafe Dip Switches (shown in correct position) 2. Verify that the Password Jumper is set to the OFF position.
Instruction Manual IM-106-880, Rev 2.0 September 2009 OCX 8800 NOTE The O2 signal connection is not required for SPA configuration or calibration. The OCX interface will allow you to observe the O2 signal level when the SPA configuration procedure is completed. 4. Observe the front panel of the SPA, Figure B-5: a. A process value display in the SPA display window indicates that the SPA is operational. Four pushbuttons are located below the display window. b.
Instruction Manual IM-106-880, Rev 2.0 September 2009 OCX 8800 5. Figure B-6 shows the SPA menu, submenus, and parameter values that must be selected to configure the SPA for use with the OCX 8800. Use the following instructions and selections shown to properly configure the SPA. a. Press the SELECT pushbutton. Observe the display window on the SPA front panel. The display window should read SET HART. b. See the SET HART command in Figure B-6.
Instruction Manual IM-106-880, Rev 2.0 September 2009 OCX 8800 Figure B-6.
Instruction Manual IM-106-880, Rev 2.0 September 2009 OCX 8800 Appendix C Return of Materials RETURNING MATERIAL If factory repair of defective equipment is required, proceed as follows: 1. Secure a return authorization number from an Emerson Process Management sales office or representative before returning the equipment. Equipment must be returned with complete identification in accordance with Emerson Process Management instructions or it will not be accepted.
Instruction Manual OCX 8800 C-2 IM-106-880, Rev 2.
Instruction Manual IM-106-880, Rev 2.0 September 2009 OCX 8800 Index A Accessories . . . . . . . . . . . . . . 1-16 AI Function Block . . . . . . . . . . 7-23 Alarm Detection . . . . . . . . 7-28 Application Information . . 7-30 Troubleshooting . . . . . . . . 7-34 Alarm Event Enumerations . . . 7-18 Alarm Events . . . . . . . . . . . . . . 7-18 Alarm Relay Events . . . . . . . . 8-11 Alerts . . . . . . . . . . . . . . . . . . . . . 7-4 Analog Input (AI) Function Block . . . . . . . . . . .
Instruction Manual IM-106-880, Rev 2.0 September 2009 OCX 8800 L P LOI Components . . . . . . . . . . . . 4-1 LOI Keypad . . . . . . . . . . . . . . . . 4-2 LOI Status Codes . . . . . . . . . . . 4-3 Personal Computer (PC) . . . . . . 1-5 PID Function Block Alarm Detection . . . . . . . . 7-43 Application Information . . 7-44 Modes . . . . . . . . . . . . . . . 7-42 Parameters . . . . . . . . . . . 7-36 Troubleshooting . . . . . . . . 7-50 PlantWeb Alerts . . . . . . . . . . . . . 7-6 Power Up . . . . .
WARRANTY Rosemount Analytical warrants that the equipment manufactured and sold by it will, upon shipment, be free of defects in workmanship or material. Should any failure to conform to this warranty become apparent during a period of one year after the date of shipment, Rosemount Analytical shall, upon prompt written notice from the purchaser, correct such nonconformity by repair or replacement, F.O.B. factory of the defective part or parts.
Instruction Manual IM-106-880, Rev 2.0 September 2009 OCX 8800 Rosemount Analytical and the Rosemount Analytical logotype are registered trademarks of Rosemount Analytical Inc. HART is a registered trademark of the HART Communications Foundation. All other marks are the property of their respective owners. WORLD HEADQUARTERS Emerson Process Management Rosemount Analytical Inc. 6565P Davis Industrial Parkway Solon, OH 44139 T 440 914 1261 T 800 433 6076 F 440 914 1262 E gas.csc@emerson.