User's Manual

Installation
27 SOLA HD
®
S5KC
2. Connect the cables to the corresponding terminal of the power input and output terminals.
3. Tighten the screws to 4.52Nm (40 in-lb) with a 13mm (1/2") torque wrench.
4. Respectively, secure the conduit of the input/output cables through the cable bridges on the rear
panel of the UPS (see Figure 31).
The connection methods in the single-phase input mode and the 3-phase input mode are shown in
Figures 32 and 33, respectively. Installation of the factory-provided copper bar is essential in the
single-phase input mode. The copper busbar is in the accessory bag included with the UPS.
Figure 32 Connection in single-phase input
Figure 33 Connection in 3-phase input
PE 2 1 PE 4 3 2 1
OUTPUT INPUT
200V/208V/220V/230V/240V
200V/208V/220V/230V/240V
PE 2 1 PE 4 3 2 1
OUTPUT INPUT
200V/208V/220V/230V/240V
380V/400V/415V