Table 27 SolaHD S5KC specifications
Unit Size, Type
10 Bay 16 Bay 12 Bay 16 Bay 10 Bay 16 Bay
No Transformer Transformer-based
No Transformer
Dual Inverter
Frame Rating, kVA/kW 15/13.5 20/18 15/13.5 20/18 15/13.5 20/18
General & Environmental
Conducted and Radiated
EMC Levels
IEC/EN/AS 62040-2 Cat 2, CISPR22 Class A, FCC Part 15 Class A
Compliant Safety Standards
IEC/EN/AS 62040-1:2008,
UL 1778 4
th
Ed and CSA 22.2 No. 107.3
UL 1778 4
th
Ed and
CSA 22.2 No. 107.3
Compliant Immunity
Standards
IEC/EN/AS 61000-4-2, 3, 4, 5, 6
Transportation Individual packaged modules meet ISTA-1A / 1B; the complete system meets ISTA-1E
Environmental WEEE and ROHS2 (6 by 6), REACH Compliant
Protection Degree
IEC60529
IP 20
Color RAL 7021
Dimensions, W x D x H, in (mm)
17x32x27
(440x800x695)
17x34x38
(440x850x970)
17x32x42
(440x800x1060)
17x34x49
(440x850x1240)
17x32x27
(440x800x695)
17x34x38
(440x850x970)
Weight, lb. (kg)
Unit Weight
(empty frame)
280 (127) 320 (145.1) 510 (231.3) 540 244.9) 280 (127) 320 (145.1)
Shipping Weight
(empty frame)
320 (145.1) 360 (163.3) 550 (249.5) 580 (263.1) 320 (145.1) 360 (163.3)
Unit Weight
(frame rating populated)
565 (256.3) 700 (317.5) 795 (360.6) 920 (417.3) 565 (256.3) 700 (317.5)
Shipping Weight
(frame rating populated)
605 (274.4) 740 (335.7) 835 (378.7) 960 (435.4) 605 (274.4) 740 (335.7)
Environmental
Operating Temperature 32 - 104°F (0 - 40°C)
Relative Humidity 0 - 95%, non-condensing
Altitude 10,000 ft. @ 77°F) (3000m @ 25°C)
Efficiency (AC-AC), % 91.8-92.0 91.6-92.0 88.5-89.9 88.6-89.7 90.4-91.0 90.0-91.0
Nominal Heat Dissipation
(maximum)
4208 BTU/Hr 5747 BTU/Hr 5528 BTU/Hr 7965 BTU/Hr 4904 BTU/Hr 6768 BTU/Hr
Acoustic Noise Level, dBA < 55dB (<
50% load), < 65dB (51-100% load) @ 1 meter
Input Data
Nominal Input Voltage,
VAC
200/208/220/230/240; Single-Phase 200/100, 220/110, 230/115,
240/120, 254/127, 208/120,
173/100, 190/110, 200/115,
220/127; Two-Phase
380/400/415; Three-Phase
Input Voltage Range The input voltage range based on the output loading, refer to Table 28
Power Factor, Cos
Single-Phase Input, >
0.99;
Three-phase Input, >
0.95
Single-Phase Input, >
0.99
Input Frequency, Nominal 50/60 Hz
Input Current
Distortion, THDi
<
5%
Input Frequency Range 40 to 70Hz auto-sensing