Reference Manual 00809-0100-4102, Rev AA May 2013 Rosemount 2051 Wireless Pressure Transmitters Pressure, Level, and Flow Solutions with WirelessHART™ Protocol
Reference Manual 00809-0100-4102, Rev AA Rosemount 2051 Wireless Pressure, Flow, and Level Solutions Read this manual before working with the product. For personal and system safety, and for optimum product performance, make sure you thoroughly understand the contents before installing, using, or maintaining this product. For technical assistance, contacts are listed below: Customer Central Technical support, quoting, and order-related questions.
Reference Manual 00809-0100-4102, Rev AA Explosions could result in death or serious injury: Installation of this transmitter in an explosive environment must be in accordance with the appropriate local, national, and international standards, codes, and practices. Please review the approvals section of the 2051 reference manual for any restrictions associated with a safe installation.
Reference Manual 00809-0100-4102, Rev AA Shipping considerations for wireless products (Lithium Batteries: Green Power Module, model number 701PGNKF): The unit was shipped to you without the Power Module installed. Please remove the Power Module from the unit prior to shipping. Each power module contains one “D” size primary lithium-thionyl chloride battery. Primary lithium batteries are regulated in transportation by the U.S.
Reference Manual 00809-0100-4102, Rev AA iv
Reference Manual Table of Contents 00809-0100-4102, Rev AA May 2013 Contents 1Section 1: Introduction 1.1 Using this manual. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 1.2 Models covered . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 1.2.1 Rosemount 2051C Coplanar™ Pressure Transmitter . . . . . . . . . . . . . . . . . . . 1 1.2.
Reference Manual Table of Contents 00809-0100-4102, Rev AA May 2013 2.6.2 Re-Mapping device variables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18 2.6.3 Set range points . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19 2.7 Review configuration data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20 2.7.1 Review pressure information . . . . . . . . . . . . . . . . . . . . . . . .
Reference Manual Table of Contents 00809-0100-4102, Rev AA May 2013 3.5.1 Rosemount 305 Integral Manifold installation procedure . . . . . . . . . . . . .48 3.5.2 Rosemount 306 Integral Manifold installation procedure . . . . . . . . . . . . .49 3.5.3 Rosemount 304 Conventional Manifold installation procedure . . . . . . . .50 3.5.4 Manifold operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .50 4Section 4: Commissioning 4.1 Overview . . . . . . . . . .
Reference Manual Table of Contents 00809-0100-4102, Rev AA May 2013 AAppendix A: Specifications and Reference Data A.1 Performance Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .89 A.1.1 Conformance to specification (±3s (Sigma)) . . . . . . . . . . . . . . . . . . . . . . . . .89 A.1.2 Digital output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .89 A.2 Functional Specifications . . . . . . .
Reference Manual Table of Contents 00809-0100-4102, Rev AA May 2013 CAppendix C: Field Communicator Menu Trees and Fast Keys C.1 Field Communicator menu trees. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 135 DAppendix D: Network design best practices D.1 Effective range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Table of Contents May 2013 vi Reference Manual 00809-0100-4102, Rev AA Table of Contents
Reference Manual Section 1: Introduction 00809-0100-4102, Rev AA Section 1 May 2013 Introduction Using this manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 1 Models covered . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 1 Service support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Reference Manual Section 1: Introduction 00809-0100-4102, Rev AA May 2013 1.2.3 Rosemount 2051L Level Transmitter 1.2.4 Rosemount 2051CF Flowmeters 2 Measures level and specific gravity up to 300 psi (20,7 bar) Measures flow in line sizes from 1/2 in. (15 mm) to 96 in.
Reference Manual Section 1: Introduction 00809-0100-4102, Rev AA 1.3 May 2013 WirelessHART installation flowchart Figure 1-1.
Reference Manual Section 1: Introduction 00809-0100-4102, Rev AA May 2013 1.4 Transmitter overview The Rosemount 2051C Coplanar design is offered for Differential Pressure (DP), Gage Pressure (GP) and Absolute Pressure (AP) measurements. The Rosemount 2051C utilizes capacitance sensor technology for DP and GP measurements. The Rosemount 2051T and 2051CA utilize piezo-resistive sensor technology for AP and GP measurements.
Reference Manual Section 1: Introduction 00809-0100-4102, Rev AA May 2013 Figure 1-3. Block diagram of operation A B C Signal Processing Microprocessor Temp. Sensor Sensor Module Memory Sensor linearization Rerange Diagnostics Engineering units Communication Local HART Handheld Communicator WirelessHART Communication Memory Configuration D A. Sensor Module B. Electronics Board C. WirelessHART Signal to Control System D. Field Communicator 1.
Section 1: Introduction Reference Manual 00809-0100-4102, Rev AA May 2013 Network design best practices When mounting the device, recommended practices should be considered to achieve the best wireless performance. See Appendix D: Network design best practices for more information on recommended practices. Field communicator connections The Power Module needs to be installed in the device for the Field Communicator to interface with the Rosemount 2051.
Reference Manual Section 1: Introduction 00809-0100-4102, Rev AA May 2013 701PGNKF). Each battery contains approximately 5 grams of lithium. Under normal conditions, the battery materials are self-contained and are not reactive as long as the battery and the Power Module are maintained. Care should be taken to prevent thermal, electrical, or mechanical damage. Contacts should be protected to prevent premature discharge.
Section 1: Introduction Reference Manual 00809-0100-4102, Rev AA May 2013 Shipping considerations for wireless products (Lithium Batteries: Green Power Module, model number 701PGNKF): The unit was shipped to you without the Power Module installed. Please remove the Power Module from the unit prior to shipping. Each power module contains a primary lithium-thionyl chloride battery. Primary lithium batteries are regulated in transportation by the U.S.
Section 2: Configuration Reference Manual May 2013 00809-0100-4102, Rev AA Section 2 Configuration Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 9 Safety messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 9 Required bench top configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Reference Manual Section 2: Configuration 00809-0100-4102, Rev AA May 2013 Warnings ( ) Failure to follow these installation guidelines could result in death or serious injury. Make sure only qualified personnel perform the installation. Explosions could result in death or serious injury: Installation of this transmitter in an explosive environment must be in accordance with the appropriate local, national, and international standards, codes, and practices.
Reference Manual Section 2: Configuration 00809-0100-4102, Rev AA 2.3.1 May 2013 Connection diagrams Bench hook-up Connect the bench equipment as shown in Figure 2-1 on page 11, and turn on the Field Communicator by pressing the ON/OFF key or log into AMS. The Field Communicator or AMS will search for a HART-compatible device and indicate when the connection is made. If the Field Communicator or AMS fail to connect, it indicates that no device was found.
Reference Manual Section 2: Configuration 00809-0100-4102, Rev AA May 2013 2.4.2 Join device to network Fast Keys 2, 1, 3 In order to communicate with the Smart Wireless Gateway, and ultimately the Host System, the transmitter must be configured to communicate over the wireless network. This step is the wireless equivalent of connecting wires from a transmitter to the host system. 1. From the Home screen, select 2: Configure. 2. Select 1: Guided Setup. 3. Select 3: Join Device to Network.
Reference Manual Section 2: Configuration 00809-0100-4102, Rev AA 2.4.4 May 2013 Set process variable units Fast Keys 2, 2, 2, 3 The PV Unit command sets the process variable units to allow you to monitor your process using the appropriate units of measure. To select a unit of measure for the PV: 1. From the Home screen, select 2: Configure. 2. Select 2: Manual Setup. 3. Select 2: Pressure. 4. Select 3: Unit to select from the following engineering units: 2.4.
Reference Manual Section 2: Configuration 00809-0100-4102, Rev AA May 2013 Table 2-1. Variable Mapping Classic Mapping Scaled Variable Mapping PV Pressure Scaled Variable SV Sensor Temperature Pressure TV Electronics Temperature Sensor Temperature QV Supply Voltage Supply Voltage Note The variable assigned to the primary variable drives the output. This value can be selected as Pressure or Scaled Variable.
Reference Manual Section 2: Configuration 00809-0100-4102, Rev AA 2.5.3 May 2013 Set transmitter percent of range (transfer function) The Rosemount 2051 Wireless transmitter has two transfer functions for pressure applications: Linear and Square Root. As shown in Figure 2-2 on page 15, activating the square root options the transmitter analog output proportional to flow. However, for DP Flow and DP Level applications it is recommended to use Scaled Variable.
Reference Manual Section 2: Configuration 00809-0100-4102, Rev AA May 2013 2.6 Configure for Level and Flow 2.6.1 Configuring scaled variable The Scaled Variable configuration allows the user to create a relationship/conversion between the pressure units and user-defined/custom units. There are two use cases for Scaled Variable. The first use case is to allow custom units to be displayed on the transmitter's LCD Display.
Reference Manual Section 2: Configuration 00809-0100-4102, Rev AA May 2013 a. When configuring for level applications, select Linear under Select Scaled data options. b. When configuring for flow applications, select Square Root under Select Scaled data options. DP Level Example Figure 2-3. Example tank A D B H L C A. 230 in. B. 200 in. C. 12 in. D. 0.94 sg A differential transmitter is used in a level application.
Reference Manual Section 2: Configuration 00809-0100-4102, Rev AA May 2013 recommended to use the low flow cutoff function in order to have a stable output and avoid problems due to process noise at a low flow or no flow condition. A low flow cutoff value that is practical for the flow element in the application should be entered. In this particular example, the low flow cutoff value is 1000 gallons of water per hour.
Reference Manual Section 2: Configuration 00809-0100-4102, Rev AA 1. May 2013 Select Manual Setup and click on the HART tab. 2. Assign Primary, secondary, tertiary and quaternary variables under Variable Mapping. 3. Click Send. 4. Carefully read the warning and click Yes if it is safe to apply the changes. 2.6.
Reference Manual Section 2: Configuration 00809-0100-4102, Rev AA May 2013 2.7 Review configuration data The following is a list of factory default configurations that can be viewed by using the Field Communicator or AMS. Follow the steps below to review the transmitter configuration information.
Reference Manual Section 2: Configuration 00809-0100-4102, Rev AA 2.7.3 May 2013 Review radio information Fast Keys 1, 7, 3 To view radio information: 1. From the Home screen, select 1: Overview. 2. Select 7: Device Information. 3. Select 3: Radio. 4. Select from the corresponding number to view each field: 1 2 3 4 5 6 7 2.7.
Reference Manual Section 2: Configuration 00809-0100-4102, Rev AA May 2013 2.8 Configuring the LCD display The LCD Display configuration command allows customization of the LCD to suit application requirements. The LCD will alternate between the selected items. Pressure Units Sensor Temperature % of Range Supply Voltage Scaled Variable In the following instructions, the LCD can also be configured to display configuration information during the device startup.
Reference Manual Section 2: Configuration 00809-0100-4102, Rev AA May 2013 2.9 Detailed transmitter setup 2.9.1 Configure process alerts Fast Keys 2, 1, 6 Process alerts allow the transmitter to indicate when the configured data point is exceeded. Process alerts can be set for pressure, temperature, or both. An alert will be displayed on a Field Communicator, AMS Device Manager status screen or in the error section of the LCD Display. The alert will reset once the value returns within range.
Reference Manual Section 2: Configuration 00809-0100-4102, Rev AA May 2013 2051 Wireless pressure transmitter, damping only takes effect when the device is placed in high power refresh mode and during calibration. In normal power mode, the effective damping is 0. Note that when the device is in high power refresh mode, battery power will be depleted rapidly.
Reference Manual Section 2: Configuration 00809-0100-4102, Rev AA 2.10.1 May 2013 Device reset The master reset function will reset the device electronics. To perform a device reset: Performing master reset using a Field Communicator From the HOME screen, enter the fast key sequence Device Dashboard Fast Keys 3, 5, 5 Performing master reset using AMS Device Manager 2.10.2 1. From the Home screen, select 3: Service Tools. 2. Select 5: Maintenance 3.
Reference Manual Section 2: Configuration 00809-0100-4102, Rev AA May 2013 2.10.3 Number of available neighbors Viewing number of available neighbors using a Field Communicator From the HOME screen, enter the fast key sequence Device Dashboard Fast Keys 3, 4, 3 Viewing number of available neighbors using AMS Device Manager In a self-organizing network, the more neighbors a device has, the more robust the network will be.
Reference Manual Section 2: Configuration 00809-0100-4102, Rev AA May 2013 2.11 Advanced Functions for HART Protocol 2.11.1 Saving, Recalling, and Cloning Configuration Data Fast Keys left arrow, 1, 2 Use the cloning feature of the Field Communicator or the AMS “User Configuration” feature to configure several 2051 Wireless transmitters similarly. Cloning involves configuring a transmitter, saving the configuration data, then sending a copy of the data to a separate transmitter.
Reference Manual Section 2: Configuration 00809-0100-4102, Rev AA May 2013 When finished, the Field Communicator informs you of the status. Repeat Steps 3 through 13 to configure another transmitter. Note The transmitter receiving cloned data must have the same software version (or later) as the original transmitter. AMS creating a Reusable Copy To create a reusable copy of a configuration perform the following procedure: 1. Completely configure the first transmitter. 2.
Section 3: Installation Reference Manual May 2013 00809-0100-4102, Rev AA Section 3 Installation Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 29 Safety messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 29 Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Reference Manual Section 3: Installation 00809-0100-4102, Rev AA May 2013 3.2.1 Warnings ( ) Failure to follow these installation guidelines could result in death or serious injury. Make sure only qualified personnel perform the installation. Explosions could result in death or serious injury: Installation of this transmitter in an explosive environment must be in accordance with the appropriate local, national, and international standards, codes, and practices.
Reference Manual Section 3: Installation 00809-0100-4102, Rev AA May 2013 Electrical shock can result in death or serious injury. Avoid contact with the leads and terminals. Process leaks could result in death or serious injury. Install and tighten all four flange bolts before applying pressure. Do not attempt to loosen or remove flange bolts while the transmitter is in service.
Section 3: Installation Reference Manual 00809-0100-4102, Rev AA May 2013 Internal antenna position The internal antenna is designed for multiple mounting orientations. The transmitter should be mounted according to measurement best practices for your pressure measurement application. The antenna should be approximately 3 ft (1 m) from any large structure or building to allow clear communication to other devices.
Reference Manual Section 3: Installation 00809-0100-4102, Rev AA May 2013 Figure 3-2.
Reference Manual Section 3: Installation 00809-0100-4102, Rev AA May 2013 Tilting of the transmitter may cause a zero shift in the transmitter output, but can be eliminated by performing a trim procedure. Figure 3-3. Draft range installation example A A. Isolators Reducing process noise Rosemount 2051CD0 draft transmitters are sensitive to small pressure changes. Increasing the damping will decrease output noise, but will further reduce response time.
Reference Manual Section 3: Installation 00809-0100-4102, Rev AA 3.4 May 2013 Installation procedures For dimensional drawing information refer to Appendix A: Specifications and Reference Data on page 89. Process flange orientation Mount the process flanges with sufficient clearance for process connections. For safety reasons, place the drain/vent valves so the process fluid is directed away from possible human contact when the vents are used.
Reference Manual Section 3: Installation 00809-0100-4102, Rev AA May 2013 Environmental seal for housing Always ensure a proper seal by installing the electronics housing cover(s) so that polymer contacts polymer (i.e. no o-ring visible). Use Rosemount O-rings. 3.4.1 Mount the transmitter Mounting brackets Rosemount 2051 transmitters may be panel-mounted or pipe-mounted via an optional mounting bracket.
Reference Manual Section 3: Installation 00809-0100-4102, Rev AA May 2013 Figure 3-5. Mounting bracket option code B4 A. D. C. B. A. 5/16 x 11/2 Bolts for Panel Mounting (Not Supplied) B. 3.4 (85) C. 3/8-16 x 11/4 Bolts for Mounting to Transmitter D. 2.8 (71) Note: Dimensions are in inches (millimeters). Flange bolts The Rosemount 2051 can be shipped with a Coplanar flange or a Traditional flange installed with four 1.75-inch flange bolts.
Reference Manual Section 3: Installation 00809-0100-4102, Rev AA May 2013 Bolt installation Only use bolts supplied with the Rosemount 2051 or sold by Emerson Process Management as spare parts. When installing the transmitter to one of the optional mounting brackets, torque the bolts to 125 in-lb. (0,9 N-m). Use the following bolt installation procedure: 1. Finger-tighten the bolts. 2. Torque the bolts to the initial torque value using a crossing pattern. 3.
Reference Manual Section 3: Installation 00809-0100-4102, Rev AA May 2013 Figure 3-7. Mounting bolts and bolt configurations for coplanar flange A B Description Qty Size in. (mm) Differential Pressure Flange Bolts 4 1.75 (44) Flange/Adapter Bolts 4 2.88 (73) Flange Bolts 4 1.75 (44) Flange/Adapter Bolts 2 2.88 (73) Gage/Absolute Pressure (1) C D (1) Rosemount 2051T transmitters are direct mount and do not require bolts for process connection. A. Transmitter with flange bolts B.
Reference Manual Section 3: Installation 00809-0100-4102, Rev AA May 2013 Figure 3-9. Panel mounting bracket option codes B2 and B8 A B C B C A D E D A. 3.75 (95) B. 1.63 (41) C. 4.09 (104) D. 2.81 (71) E. 4.5 (114) A. 1.40 (36) B. Mounting Holes 0.375 Diameter (10) C. 1.405 (35,7) D. 1.405 (35,7) Figure 3-10. Flat mounting bracket option codes B3 and BC B A D C A. 1.625 (41) B. 2.125 (54) C. 2.81 (71) D. 8.00 (203) Note: Dimensions are in inches (millimeters).
Reference Manual Section 3: Installation 00809-0100-4102, Rev AA 3.4.2 May 2013 Impulse piping Best practices The piping between the process and the transmitter must accurately transfer the pressure to obtain accurate measurements. There are five possible sources of error: leaks, friction loss (particularly if purging is used), trapped gas in a liquid line, liquid in a gas line, and density variations between the legs.
Reference Manual Section 3: Installation 00809-0100-4102, Rev AA May 2013 Mounting Requirements Refer to Figure 3-11 on page 43 for examples of the following mounting configurations: Liquid Flow Measurement Place taps to the side of the line to prevent sediment deposits on the process isolators. Mount the transmitter beside or below the taps so gases vent into the process line. Mount drain/vent valve upward to allow gases to vent.
Reference Manual Section 3: Installation 00809-0100-4102, Rev AA May 2013 Figure 3-11. Installation examples Liquid Service Gas Service Steam Service A A A A. Drain/vent valves 3.4.3 Process connections Coplanar or traditional process connection Install and tighten all four flange bolts before applying pressure to avoid leakage. When properly installed, the flange bolts will protrude through the top of the sensor module housing.
Reference Manual Section 3: Installation 00809-0100-4102, Rev AA May 2013 1. Remove the flange bolts. 2. Leaving the flange in place, move the adapters into position with the O-ring installed. 3. Clamp the adapters and the Coplanar flange to the transmitter module using the longer of the bolts supplied. 4. Tighten the bolts. Refer to “Flange bolts” on page 37 for torque specifications.
Reference Manual Section 3: Installation 00809-0100-4102, Rev AA May 2013 Figure 3-12. Inline gage low side pressure port A A. Low side pressure port (atmospheric reference) a Do not apply torque directly to the sensor module. Rotation between the sensor module and the process connection can damage the electronics. To avoid damage, apply torque only to the hex-shaped process connection. Sensor Module Process Connection 3.4.5 Power Module installation Figure 3-13. Power Module A A.
Reference Manual Section 3: Installation 00809-0100-4102, Rev AA May 2013 To make connections, perform the following procedure: 3.4.6 1. Remove the housing cover on the Power Module compartment side. The Power Module supplies all power to the transmitter. 2. Connect Power Module 701PGNKF. 3. Replace the Power Module cover and tighten to safety specification (polymer to polymer). Installing the LCD display Transmitters ordered with the LCD display will be shipped with the display installed.
Reference Manual 00809-0100-4102, Rev AA Section 3: Installation May 2013 Figure 3-14. Optional LCD Display 3.5 Rosemount 304, 305 and 306 integral manifolds The Rosemount 305 Integral Manifold mounts directly to the transmitter and is available in two designs: Traditional and Coplanar. The traditional 305 Integral Manifold can be mounted to most primary elements with mounting adapters in the market today.
Reference Manual Section 3: Installation 00809-0100-4102, Rev AA May 2013 Figure 3-15. Integral Manifold Designs A C B D A. 2051C and 304 Conventional B. 2051C and 305 Integral Coplanar C. 2051C and 305 Integral Traditional D. 2051T and 306 In-Line 3.5.1 Rosemount 305 Integral Manifold installation procedure To install a 305 Integral Manifold to a 2051 Wireless transmitter: 1. Inspect the PTFE sensor module O-rings. If the O-rings are undamaged, reusing them is recommended.
Reference Manual Section 3: Installation 00809-0100-4102, Rev AA May 2013 Figure 3-16. Bolt tightening pattern 3. If the PTFE sensor module O-rings have been replaced, the flange bolts should be re-tightened after installation to compensate for cold flow of the O-rings. 4. If applicable, install flange adapters on the process end of the manifold using the 1.75-in. flange bolts supplied with the transmitter.
Reference Manual Section 3: Installation 00809-0100-4102, Rev AA May 2013 Note If using thread tape, be sure the thread tape does not strip when the manifold assembly is started. 3.5.3 5. Wrench tighten manifold into process connection. (Note: Minimum toque value is 425 in-lbs) 6. Count how many threads are still showing. (Note: Minimum engagement is 3 revolutions) 7. Subtract the number of threads showing (after tightening) from the total threads to calculate the revolutions engaged.
Reference Manual Section 3: Installation 00809-0100-4102, Rev AA May 2013 In normal operation the two block valves between the process and instrument ports will be open and the equalizing valve will be closed. L H Drain/ Vent Valve Drain/ Vent Valve Equalize (closed) Isolate (open) Isolate (open) Process 1. To zero the 2051, close the block valve to the low pressure (downstream) side of the transmitter first.
Reference Manual Section 3: Installation 00809-0100-4102, Rev AA May 2013 Five-valve Natural Gas configurations shown: In normal operation, the two block valves between the process and instrument ports will be open, and the equalizing valves will be closed. L H Test (Plugged) Test (Plugged) Equalize (closed) Equalize (closed) Isolate (open) Isolate (open) Process 1. To zero the 2051, first close the block valve on the low pressure (downstream) side of the transmitter.
Reference Manual Section 3: Installation 00809-0100-4102, Rev AA May 2013 3. Open the equalize valve on the low pressure (downstream) side of the transmitter. The manifold is now in the proper configuration for zeroing the transmitter. L H Test (Plugged) Test (Plugged) Equalize (open) Isolate (open) Isolate (closed) Process 4. After zeroing the transmitter, close the equalize valve on the low pressure (downstream) side of the transmitter.
Section 3: Installation May 2013 54 Reference Manual 00809-0100-4102, Rev AA Installation
Section 4: Commissioning Reference Manual May 2013 00809-0100-4102, Rev AA Section 4 Commissioning Safety messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 55 Viewing network status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 57 Verifying operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Section 4: Commissioning 4.2.1 Reference Manual 00809-0100-4102, Rev AA May 2013 Warnings ( ) Failure to follow these installation guidelines could result in death or serious injury. Make sure only qualified personnel perform the installation. Explosions could result in death or serious injury: Installation of this transmitter in an explosive environment must be in accordance with the appropriate local, national, and international standards, codes, and practices.
Reference Manual 00809-0100-4102, Rev AA 4.3 Section 4: Commissioning May 2013 Viewing network status If the Rosemount 2051 Wireless was configured with the Network ID and Join Key and sufficient time for network polling has passed, the transmitter should be connected to the network. To verify connectivity, open the Smart Wireless Gateway’s integral web interface and navigate to the Explorer page. This page will display the transmitter’s HART tag, PV, SV, TV, QV, and Update Rate.
Reference Manual Section 4: Commissioning 00809-0100-4102, Rev AA May 2013 Figure 4-1. Diagnostic Screen Sequence Tag Device ID Network ID Abcde id - 12 netwk Network Join Status Device Status fgh 345678 netwk Suply OK volts 3. 6 0 13 0 5 ID Figure 4-2.
Reference Manual 00809-0100-4102, Rev AA Section 4: Commissioning May 2013 Figure 4-3. Smart Wireless Gateway Explorer page. AMS Suite Wireless Configurator When the device has joined the network, it will appear in the Device Manager as illustrated in Figure 4-4. For HART Wireless transmitter communication, a Rosemount 2051 Wireless DD is required. To obtain the latest DD, visit the Emerson Process Management Easy Upgrade site at: http://www2.emersonprocess.com/en-US/documentation/deviceinstallkits.
Reference Manual Section 4: Commissioning 00809-0100-4102, Rev AA May 2013 Function Key Sequence Menu Items Join Device to Network 2, 1, 3 Network ID, Set Join Key Figure 4-5. Smart Wireless Gateway Network Settings 4.4.1 Using the Field Communicator Note In order to communicate with a Field Communicator, power the Rosemount 2051 Wireless Transmitter by connecting the Power Module.
Reference Manual Section 4: Commissioning 00809-0100-4102, Rev AA May 2013 Table 4-1.
Reference Manual Section 4: Commissioning 00809-0100-4102, Rev AA May 2013 Configuring HART Lock using Field Communicator From the HOME screen, enter the fast key sequence Device Dashboard Fast Keys 2, 2, 7, 2 Configuring HART Lock using AMS Device Manager 1. Right click on the device and select Configure. 2. Under Manual Setup select the Security tab. 3. Click Lock/Unlock button under HART Lock (Software) and follow the screen prompts.
Reference Manual Section 5: Operation and Maintenance 00809-0100-4102, Rev AA May 2013 Section 5 Operation and maintenance Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 63 Calibration overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 63 LCD Screen Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Reference Manual Section 5: Operation and Maintenance 00809-0100-4102, Rev AA May 2013 Absolute pressure transmitters (2051CA and 2051TA) are calibrated at the factory. Trimming adjusts the position of the factory characterization curve. It is possible to degrade performance of the transmitter if any trim is done improperly or with inaccurate equipment. Table 5-1. Recommended Calibration Tasks Transmitter 2051CD 2051CG 2051L 2051TG, Range 1-4 Bench Calibration Tasks 1.
Reference Manual Section 5: Operation and Maintenance 00809-0100-4102, Rev AA May 2013 For transmitters that are field installed, the manifolds discussed in “Rosemount 304, 305 and 306 integral manifolds” on page 47 allow the differential transmitter to be zeroed using the zero trim function. Both 3-valve and 5-valve manifolds are discussed. This field calibration will eliminate any pressure offsets caused by mounting effects (head effect of the oil fill) and static pressure effects of the process.
Reference Manual Section 5: Operation and Maintenance 00809-0100-4102, Rev AA May 2013 Sample calculation for 2051 (0.04% accuracy & 5-year stability) Step 1: Determine the performance required for your application. Required Performance: 0.20% of span Step 2: Determine the operating conditions.
Reference Manual Section 5: Operation and Maintenance 00809-0100-4102, Rev AA May 2013 Example A range 4 differential pressure HART transmitter (2051CD4...) will be used in an application with a static line pressure of 1200 psi (83 bar). The transmitter output is ranged with the Lower Range Value at 500 inH20 (1, 2 bar) and the Upper Range Value at 1500 inH20 (3, 7 bar).
Reference Manual Section 5: Operation and Maintenance 00809-0100-4102, Rev AA May 2013 position. Since this correction maintains the slope of the characterization curve, it should not be used in place of a sensor trim over the full sensor range. When performing a zero trim, ensure that the equalizing valve is open and all wet legs are filled to the correct levels. Line pressure should be applied to the transmitter during a zero trim to eliminate line pressure errors.
Reference Manual Section 5: Operation and Maintenance 00809-0100-4102, Rev AA May 2013 Note Use a pressure input source that is at least four times more accurate than the transmitter, and allow the input pressure to stabilize for ten seconds before entering any values. Performing a Sensor Trim with a Field Communicator From the Home screen, enter the fast key sequence and follow the steps within the Field Communicator to complete the Sensor Trim.
Reference Manual Section 5: Operation and Maintenance 00809-0100-4102, Rev AA May 2013 5.4.3 Recall Factory Trim—Sensor Trim The Recall Factory Trim—Sensor Trim command allows the restoration of the as-shipped factory settings of the Sensor Trim. This command can be useful for recovering from an inadvertent zero trim of an absolute pressure unit or inaccurate pressure source.
Reference Manual Section 5: Operation and Maintenance 00809-0100-4102, Rev AA May 2013 Zero Effect: ± 0.1% of the upper range limit per 1000 psi (69 bar) for line pressures from 0 to 2000 psi (0 to 138 bar) For line pressures above 2000 psi (138 bar), the zero effect error is ± 0.2% of the upper range limit plus an additional ± 0.2% of upper range limit error for each 1000 psi (69 bar) of line pressure above 2000 psi (138 bar). Example: Line pressure is 3000 psi (3 kpsi).
Reference Manual Section 5: Operation and Maintenance 00809-0100-4102, Rev AA May 2013 To calculate the low trim (LT) value: LT = 500 + (0.01/1000)(500)(1200) LT = 506 inH2O (1.26 bar) To calculate the high trim (HT) value: HT = 1500 + (0.01/1000)(1500)(1200) HT = 1518 inH2O (3.78 bar) Complete a 2051 Wireless sensor trim and enter the corrected values for low trim (LT) and high trim (HT), refer to “Sensor Trim” on page 68.
Reference Manual Section 5: Operation and Maintenance 00809-0100-4102, Rev AA May 2013 5.5 LCD Screen Messages 5.5.1 Startup Screen Sequence The following screens will display when the Power Module is first connected to the Rosemount 2051 Wireless. XXXXX XXXXxxx xxxxxx 2051 All Segments On: used to visually determine if there are any bad segments on the LCD Device Identification: used to determine Device Type. WIrels Abcde fgh PRESS 5 8.
Section 5: Operation and Maintenance Reference Manual 00809-0100-4102, Rev AA May 2013 SNSR 2 5. 0 0 SV Screen - sensor temperature value deg c DEV 2 5. 2 5 TV Screen - device temperature value deg c Suply 3. 6 0 QV Screen - voltage reading at the power supply terminals volts PRCNT 7.
Reference Manual Section 5: Operation and Maintenance 00809-0100-4102, Rev AA 5.5.2 May 2013 Diagnostic Button Screen Sequence The following five screens will display when the device is operating properly and the Diagnostic Button has been pressed.
Reference Manual Section 5: Operation and Maintenance 00809-0100-4102, Rev AA May 2013 Suply 3. 6 0 Diagnostic Button Screen 5: voltage reading at the power supply terminals volts 5.5.3 Network Diagnostic Status Screens These screens display the network status of the device. Only one will be shown during the startup sequence or diagnostic sequence. netwk Diagnostic Button Screen 4.1: the device is attempting to start the radio unknwn netwk Diagnostic Button Screen 4.
Reference Manual Section 5: Operation and Maintenance 00809-0100-4102, Rev AA May 2013 netwk Diagnostic Button Screen 4.4: the device is in a disconnected state and requires a “Force Join” command to join the network DISCNT NETwK Diagnostic Button Screen 4.5: the device is searching for the Network SRCHNG netwk Diagnostic Button Screen 4.6: the device is attempting to join a network NEGOT netwk Diagnostic Button Screen 4.
Section 5: Operation and Maintenance Reference Manual 00809-0100-4102, Rev AA May 2013 netwk Diagnostic Button Screen 4.
Reference Manual Section 5: Operation and Maintenance 00809-0100-4102, Rev AA 5.5.4 May 2013 Device Diagnostic Screens The following screens will show the device diagnostics depending on the state of the device. DEV fAilur PRESS 5 8. 0 Device Information - Status: there is a critical error which may prevent the device from operating correctly. Check additional status screens for more information. PV Screen - process pressure value PSI SNSR 2 5.
Section 5: Operation and Maintenance Reference Manual 00809-0100-4102, Rev AA May 2013 Suply 3. 6 0 QV Screen - voltage reading at the power supply terminals volts PRCNT 7.
Reference Manual Section 5: Operation and Maintenance 00809-0100-4102, Rev AA May 2013 suply failur suply low radio failur confg failur Operation and maintenance Diagnostic Button Screen 7.1: the terminal voltage has dropped below level of operating limit. Replace the Power Module (Part Number: 701PGNKF) Diagnostic Button Screen 7.
Reference Manual Section 5: Operation and Maintenance 00809-0100-4102, Rev AA May 2013 confg warn snsr failur snsr warn Diagnostic Button Screen 9.2: configuration of the transmitter is invalid such that non-critical operation of the device may be affected - check the extended configuration status to identify which configuration item(s) need to be corrected Diagnostic Button Screen 10.
Section 6: Troubleshooting Reference Manual May 2013 00809-0100-4102, Rev AA Section 6 Troubleshooting Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 83 Safety messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 83 Removing from service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Reference Manual Section 6: Troubleshooting 00809-0100-4102, Rev AA May 2013 6.2.1 Warnings ( ) Explosions could result in death or serious injury: Installation of this transmitter in an explosive environment must be in accordance with the appropriate local, national, and international standards, codes, and practices. Please review the approvals section of the 2051 reference manual for any restrictions associated with a safe installation.
Reference Manual Section 5: Troubleshooting 00809-0100-4102, Rev AA May 2013 Device Status Description Pressure has Exceeded Limits The sensor has exceeded the maximum measurement range. Electronics Temperature has Exceeded Limits The electronics temperature has exceeded the transmitter's maximum range. Recommended Action 1. Check process for possible saturation condition 2. Verify that the appropriate sensor was chosen for the application 3. Reconfirm sensor configuration 4.
Reference Manual Section 6: Troubleshooting 00809-0100-4102, Rev AA May 2013 Device Status Description LO Alarm The primary variable has surpassed the user defined limit. LO LO Alarm Button Stuck Simulation Active 86 The primary variable has surpassed the user defined limit. A buttons on the Electronics Board is detected as stuck in the active position. The device is in simulation mode and may not be reporting actual information. Recommended Action 1.
Reference Manual Section 5: Troubleshooting 00809-0100-4102, Rev AA May 2013 Table 6-2.
Section 6: Troubleshooting 6.3 Reference Manual 00809-0100-4102, Rev AA May 2013 Removing from service Follow these steps: 1. Follow all plant safety rules and procedures. 2. Isolate and vent the process from the transmitter before removing the transmitter from service. 3. Remove the transmitter from the process connection. a. The Rosemount 2051C Wireless transmitter is attached to the process connection by four bolts and two cap screws.
Appendix A: Reference Data Reference Manual May 2013 00809-0100-4102, Rev AA Appendix A Specifications and Reference Data Performance Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 89 Functional Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 92 Physical specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Reference Manual Appendix A: Reference Data 00809-0100-4102, Rev AA May 2013 Reference Accuracy(1) Models(1) Standard 2051CD, 2051CG Range 0 (CD) ±0.10% of span For spans less than 2:1, accuracy = ±0.05% of URL Range 1 High Accuracy Option ±0.10% of span For spans less than 15:1, accuracy = URL 0.025 + 0.005 --------------- % of Span Span Ranges 2-5 ±0.065% of span For spans less than 10:1, accuracy = URL 0.015 + 0.005 --------------- % of Span Span 2051T Ranges 1-4 ±0.
Appendix A: Reference Data Reference Manual May 2013 00809-0100-4102, Rev AA Long Term Stability Models Long Term Stability 2051C Ranges 2-5 2051CD Low/Draft Range Ranges 0-1 2051T Ranges 1-4 ±0.125% of URL for 5 years ±50 °F (28 °C) temperature changes, and up to 1000 psi (6,9 MPa) line pressure. ±0.2% of URL for 1 year ±0.125% of URL for 5 years ±50 °F (28 °C) temperature changes, and up to 1000 psi (6,9 MPa) line pressure.
Reference Manual Appendix A: Reference Data 00809-0100-4102, Rev AA May 2013 Ambient Temperature Effect per 50°F (28°C) Models 2051CD/CG 2051T Ambient Temperature Effect Range 0 ±(0.25% URL + 0.05% span) Range 1 ±(0.1% URL + 0.25% span) Ranges 2-5 ±(0.0125% URL + 0.0625% span) from 1:1 to 5:1 ±(0.025% URL + 0.125% span) from 5:1 to 100:1 Range 1 ±(0.025% URL + 0.125% span) from 1:1 to 10:1 ±(0.05% URL + 0.125% span) from 10:1 to 100:1 Range 2-4 Range 5 2051CA All Ranges ±(0.025% URL + 0.
Appendix A: Reference Data Reference Manual May 2013 00809-0100-4102, Rev AA A.2.2 Range and Sensor Limits Table A-1. 2051CD, 2051CG, 2051L, and 2051H Range and Sensor Limits Range Minimum Span 0 1 2 3 4 5 Range and Sensor Limits Lower (LRL) 2051CD(1), CG, L, H Upper (URL) 2051C Differential 2051C/ Gage 2051L Differential 2051L Gage 2051H Differential 0.1 inH2O (0,25 mbar) 0.5 inH2O (1,2 mbar) 2.5 inH2O (6,2 mbar) 10 inH2O (24,9 mbar) 3 psi (0,20 bar) 20 psi (1,38 bar) 3.
Reference Manual Appendix A: Reference Data 00809-0100-4102, Rev AA May 2013 Update rate User selectable, 1 second to 60 minutes. Wireless sensor module for in-line transmitters The 2051 wireless transmitter requires the engineered polymer housing to be selected. The standard sensor module will come with aluminum material. If stainless steel is required, the option WSM must be selected. Wireless power module Field replaceable, keyed connection eliminates the risk of incorrect installation.
Appendix A: Reference Data Reference Manual May 2013 00809-0100-4102, Rev AA Rosemount 2051L Limit is flange rating or sensor rating, whichever is lower (see the table below). Standard Type CS Rating SST Rating ANSI/ASME ANSI/ASME ANSI/ASME Class 150 285 psig 275 psig Class 300 740 psig 720 psig Class 600 1480 psig 1440 psig At 100 °F (38 °C), the rating decreases with increasing temperature, per ANSI/ASME B16.5.
Reference Manual Appendix A: Reference Data 00809-0100-4102, Rev AA May 2013 Process Temperature Limits At atmospheric pressures and above.
Appendix A: Reference Data Reference Manual May 2013 00809-0100-4102, Rev AA A.4 Physical specifications A.4.1 Electrical connections HART interface connections fixed to the Power Module. A.4.2 Process connections Rosemount 2051C /4–18 NPT on 21/8-in. centers 1 /2–14 NPT on 2-in. (50.8 mm), 21/8-in. (54.0 mm), or 21/4-in. (57.2 mm) centers 1 Rosemount 2051T /2–14 NPT female, G1/2 A DIN 16288 Male (available in SST for Range 1–4 transmitters only) 1 Rosemount 2051L High pressure side: 2-in.
Reference Manual Appendix A: Reference Data 00809-0100-4102, Rev AA May 2013 Process flanges and adapters Plated carbon steel SST: CF-8M (Cast 316 SST) per ASTM A743 Cast C-276: CW-12MW per ASTM A494 Cast Alloy 400: M-30C per ASTM A494 Wetted O-rings Glass-filled PTFE (Graphite-filled PTFE with Isolating Diaphragm code 6) A.4.
Reference Manual 00809-0100-4102, Rev AA Appendix A: Reference Data May 2013 Bolts Plated carbon steel per ASTM A449, Type 1 Austenitic 316 SST per ASTM F593 ASTM A453, Class D, Grade 660 SST ASTM A193, Grade B7M alloy steel ASTM A193, Class 2, Grade B8M SST Alloy K-500 Sensor Module Fill Fluid Silicone Process Fill Fluid (Liquid Level Only) 2051L: Syltherm XLT, D.C. Silicone 704, D.C. Silicone 200, inert, glycerin and water, Neobee M-20, propylene glycol and water.
Reference Manual Appendix A: Reference Data 00809-0100-4102, Rev AA May 2013 A.4.6 Shipping Weights for 2051 Wireless Pressure Transmitter Table A-2. Transmitter weights without options Complete Transmitter(1) Weight In lb (kg) 2051C with engineered polymer housing 2051T with engineered polymer housing 3.90 (1,8) 1.9 (0,86) (1) Transmitter weights include the sensor module and housing only. Table A-3. 2051L weights without options Flange Flush lb. (kg) 2-in. Ext. lb (kg) 4-in. Ext.
Reference Manual Appendix A: Reference Data 00809-0100-4102, Rev AA A.5 May 2013 Dimensional Drawings Dimensions are in inches (millimeters). Process adapters (option D2) and Rosemount 305 integral manifolds must be ordered with the transmitter.
Reference Manual Appendix A: Reference Data 00809-0100-4102, Rev AA May 2013 Table A-5. 2051L Dimensional Specifications Except where indicated, dimensions are in inches (millimeters). Class ASME B16.5 (ANSI) 150 Pipe Size Flange Thickness A Extension O.D. Bolt Hole Diameter(1) Gasket Surface E Diameter D 4.75 (121) 6.0 (152) 7.5 (191) 5.0 (127) 6.62 (168) 7.88 (200) 5.0 (127) 6.62 (168) 125 mm 160 mm 190 mm 180 mm 0.75 (19) 0.75 (19) 0.75 (19) 0.75 (19) 0.88 (22) 0.88 (22) 0.75 (19) 0.
Appendix A: Reference Data Reference Manual May 2013 00809-0100-4102, Rev AA A.6 Ordering Information Table A-6. 2051C Coplanar Pressure Transmitters Ordering Information ★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery. __The Expanded offering is subject to additional delivery lead time.
Reference Manual Appendix A: Reference Data 00809-0100-4102, Rev AA May 2013 Table A-6. 2051C Coplanar Pressure Transmitters Ordering Information ★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery. __The Expanded offering is subject to additional delivery lead time.
Reference Manual Appendix A: Reference Data 00809-0100-4102, Rev AA May 2013 Table A-6. 2051C Coplanar Pressure Transmitters Ordering Information ★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery. __The Expanded offering is subject to additional delivery lead time.
Appendix A: Reference Data Reference Manual 00809-0100-4102, Rev AA May 2013 Table A-6. 2051C Coplanar Pressure Transmitters Ordering Information ★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery. __The Expanded offering is subject to additional delivery lead time.
Reference Manual Appendix A: Reference Data 00809-0100-4102, Rev AA May 2013 Table A-6. 2051C Coplanar Pressure Transmitters Ordering Information ★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery. __The Expanded offering is subject to additional delivery lead time.
Reference Manual Appendix A: Reference Data 00809-0100-4102, Rev AA May 2013 Table A-7. 2051T In-Line Pressure Transmitter Ordering Information ★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery. __The Expanded offering is subject to additional delivery lead time.
Reference Manual Appendix A: Reference Data 00809-0100-4102, Rev AA May 2013 Table A-7. 2051T In-Line Pressure Transmitter Ordering Information ★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery. __The Expanded offering is subject to additional delivery lead time. Mounting Bracket Standard B4 Bracket for 2-in.
Appendix A: Reference Data Reference Manual 00809-0100-4102, Rev AA May 2013 Table A-7. 2051T In-Line Pressure Transmitter Ordering Information ★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery. __The Expanded offering is subject to additional delivery lead time.
Appendix A: Reference Data Reference Manual May 2013 00809-0100-4102, Rev AA Table A-8. Rosemount 2051L Liquid Level Transmitter Ordering Information ★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery. __The Expanded offering is subject to additional delivery lead time.
Reference Manual Appendix A: Reference Data 00809-0100-4102, Rev AA May 2013 Table A-8. Rosemount 2051L Liquid Level Transmitter Ordering Information ★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery. __The Expanded offering is subject to additional delivery lead time. ★ ★ ★ ★ ★ ★ ★ ★ ★ ★ ★ ★ ★ ★ ★ ★ ★ ★ ★ P E X(1) F(1) G(1) Y(1) H(1) J(1) Z(1) L(1) Q R S V K(1) T(1) U(1) W(1) 7(1) Expanded 2-in. 3-in. 2-in. 3-in. 4-in. 2-in.
Appendix A: Reference Data Reference Manual May 2013 00809-0100-4102, Rev AA Table A-8. Rosemount 2051L Liquid Level Transmitter Ordering Information ★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery. __The Expanded offering is subject to additional delivery lead time.
Reference Manual Appendix A: Reference Data 00809-0100-4102, Rev AA May 2013 Table A-8. Rosemount 2051L Liquid Level Transmitter Ordering Information ★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery. __The Expanded offering is subject to additional delivery lead time.
Reference Manual Appendix A: Reference Data 00809-0100-4102, Rev AA May 2013 Table A-9. Rosemount 2051CFA Annubar Flowmeter Ordering Information ★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery. __The Expanded offering is subject to additional delivery lead time. Model Product Description 2051CFA Annubar Flowmeter Measurement Type Standard D Differential Pressure Standard ★ Liquid Gas Steam Standard ★ ★ ★ 2-in.
Appendix A: Reference Data Reference Manual 00809-0100-4102, Rev AA May 2013 Table A-9. Rosemount 2051CFA Annubar Flowmeter Ordering Information ★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery. __The Expanded offering is subject to additional delivery lead time.
Appendix A: Reference Data Reference Manual May 2013 00809-0100-4102, Rev AA Table A-9. Rosemount 2051CFA Annubar Flowmeter Ordering Information ★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery. __The Expanded offering is subject to additional delivery lead time.
Appendix A: Reference Data May 2013 Reference Manual 00809-0100-4102, Rev AA Table A-9. Rosemount 2051CFA Annubar Flowmeter Ordering Information ★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery. __The Expanded offering is subject to additional delivery lead time.
Appendix A: Reference Data Reference Manual May 2013 00809-0100-4102, Rev AA Table A-9. Rosemount 2051CFA Annubar Flowmeter Ordering Information ★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery. __The Expanded offering is subject to additional delivery lead time.
Reference Manual Appendix A: Reference Data 00809-0100-4102, Rev AA May 2013 Table A-10. Rosemount 2051CFC Compact Flowmeter Ordering Information ★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery. __The Expanded offering is subject to additional delivery lead time.
Appendix A: Reference Data Reference Manual May 2013 00809-0100-4102, Rev AA Table A-10. Rosemount 2051CFC Compact Flowmeter Ordering Information ★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery. __The Expanded offering is subject to additional delivery lead time. Transmitter Housing Material Conduit Entry Size Standard P N/A Engineered Polymer Standard ★ Transmitter Performance Class Standard 1 Up to ±2.
Reference Manual Appendix A: Reference Data 00809-0100-4102, Rev AA May 2013 Table A-10. Rosemount 2051CFC Compact Flowmeter Ordering Information ★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery. __The Expanded offering is subject to additional delivery lead time.
Reference Manual Appendix A: Reference Data 00809-0100-4102, Rev AA May 2013 Table A-11. Rosemount 2051CFP Integral Orifice Flowmeter Ordering Information ★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery. __The Expanded offering is subject to additional delivery lead time.
Reference Manual Appendix A: Reference Data 00809-0100-4102, Rev AA May 2013 Table A-11. Rosemount 2051CFP Integral Orifice Flowmeter Ordering Information ★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery. __The Expanded offering is subject to additional delivery lead time. 0250 0345 0500 0630 0800 0295 0376 0512 0748 1022 1184 Expanded 0010 0014 0020 0034 ★ ★ ★ ★ ★ ★ ★ ★ ★ ★ ★ 0.250-in. (6.35 mm) for 1-in. Pipe 0.345-in. (8.
Reference Manual Appendix A: Reference Data 00809-0100-4102, Rev AA May 2013 Table A-11. Rosemount 2051CFP Integral Orifice Flowmeter Ordering Information ★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery. __The Expanded offering is subject to additional delivery lead time. Standard WP5 Internal Antenna, Compatible with Green Power Module (I.S.
Reference Manual Appendix A: Reference Data 00809-0100-4102, Rev AA May 2013 Table A-11. Rosemount 2051CFP Integral Orifice Flowmeter Ordering Information ★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery. __The Expanded offering is subject to additional delivery lead time.
Appendix A: Reference Data Reference Manual May 2013 00809-0100-4102, Rev AA A.
Reference Manual Appendix A: Reference Data 00809-0100-4102, Rev AA May 2013 Output information Output range points must be the same unit of measure.
Appendix A: Reference Data Reference Manual May 2013 00809-0100-4102, Rev AA Rosemount 2051C Traditional Flange bracket options B1 Bracket for 2-in. Pipe Mounting For use with the traditional flange option Bracket for mounting on 2-in.
Reference Manual Appendix A: Reference Data 00809-0100-4102, Rev AA May 2013 A.
Appendix B: Product Certifications Reference Manual May 2013 00809-0100-4102, Rev AA Appendix B Product Certifications Wireless Certifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 131 B.1 Wireless Certifications B.1.1 Approved manufacturing locations Rosemount Inc. — Chanhassen, Minnesota USA Fisher-Rosemount GmbH & Co.
Appendix B: Product Certifications B.1.5 Reference Manual 00809-0100-4102, Rev AA May 2013 Ordinary location certification for FM As standard, the transmitter has been examined and tested to determine that the design meets basic electrical, mechanical, and fire protection requirements by FM, a nationally recognized testing laboratory (NRTL) as accredited by the Federal Occupational Safety and Health Administration (OSHA). B.1.
Reference Manual Appendix B: Product Certifications 00809-0100-4102, Rev AA May 2013 Special Conditions for Safe Use (X) The plastic enclosure may constitute a potential electrostatic ignition risk and must not be rubbed or cleaned with a dry cloth. For use with Rosemount 701PGNKF only. I7 IECEx Intrinsic Safety Certificate No: IECEx BAS 12.
Appendix B: Product Certifications Reference Manual May 2013 00809-0100-4102, Rev AA 134 Product Certifications
Appendix C: Field Communicator Menu Trees Reference Manual May 2013 00809-0100-4102, Rev AA Appendix C Field Communicator Menu Trees and Fast Keys Field Communicator menu trees . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 135 C.1 Field Communicator menu trees Figure C-1.
Reference Manual Appendix C: Field Communicator Menu Trees 00809-0100-4102, Rev AA May 2013 Figure C-2.
Reference Manual Appendix C: Field Communicator Menu Trees 00809-0100-4102, Rev AA May 2013 Figure C-3.
Reference Manual Appendix C: Field Communicator Menu Trees 00809-0100-4102, Rev AA May 2013 Figure C-4.
Appendix D: Network design best practices Reference Manual May 2013 00809-0100-4102, Rev AA Appendix D Network design best practices Effective range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 139 All recommended practices should be followed to ensure highest data reliability. Deviation from these best practices may require device repeaters in the network to maintain 99% data reliability.
Appendix D: Network design best practices May 2013 Reference Manual 00809-0100-4102, Rev AA For examples and complete explanations, refer to the IEC62591 WirelessHART System Engineering Guide: http://www2.emersonprocess.com/siteadmincenter/PM%20Central%20Web%20Documents/EMR_WirelessHART_SysEngGuide.
Reference Manual 00809-0100-4102, Rev AA May 2013 Standard Terms and Conditions of Sale can be found at www.rosemount.com/terms_of_sale The Emerson logo is a trademark and service mark of Emerson Electric Co. Rosemount. the Rosemount logotype, and SMART FAMILY are registered trademarks of Rosemount Inc. Coplanar is a trademark of Rosemount Inc. Halocarbon is a trademark of the Halocarbon Products Corporation.o.