Surge Protective Devices STV100K Series Instruction Manual
Contents 1.0 Installation.................................................................................................... 4 1.1 Environment............................................................................................................ 4 1.2 Mounting................................................................................................................. 4 1.3 Proper Connection of SPDs....................................................................................
1.0 Installation The SolaHD STV100K Series Surge Protective Device is a high-quality, highenergy surge current diversion system designed to protect sensitive equipment from damaging transient voltage surges resulting from load switching, lightning strikes, and other sources. The installer should perform the following steps to ensure a quality installation. Please read all instructions before starting the installation of this product. These instructions do not replace national or local electrical codes.
1.4 Mechanical Dimensions Figure 1: Mechanical Dimensions (in.) Unit shown is a three-phase wye 1.5 Voltage Protection Ratings (VPRs) To maintain the voltage protection ratings marked on these products, as obtained by Underwriters Laboratories, Inc. in accordance with ANSI/UL 1449, 3rd edition, the Standard for Safety, Surge Protective Devices (SPDs), #12 AWG wire must be utilized to connect the STV100K Series to your facility’s power grid.
1.8 Wiring Connections Before making connections to the unit, verify that the unit model number and nameplate voltage rating are appropriate for connection to the intended power source. See Table 1 for voltage rating applications with typical power source configurations. 1. Connect the black phase wires to the corresponding phase on the service panel. For delta high leg units, ensure the high leg is connected to Phase B of the SPD. 2.
Table 1: Voltage Ratings & Power Source Configurations Model: STV100K-10N Nominal Voltage: 120 V Single-phase, 2W + G Model: STV100K-24L Nominal Voltage: 240 V Single-phase, 2W + G Model: STV100K-10S Nominal Voltage: 120/208–240 V Single-phase, 3W + G Model: STV100K-10Y Nominal Voltage: 120/208 V Three-phase wye, 4W + G Model: STV100K-23Y Nominal Voltage: 230/400 V Model: STV100K-27Y Nominal Voltage: 277/480 V Model: STV100K-10X* Nominal Voltage: 120/208 V Three-phase wye, 3W + G Model: STV100K-
Table 1: Voltage Ratings & Power Source Configurations Model: STV100K-20D* Nominal Voltage: 208 V Three-phase delta, 3W + G Model: STV100K-24D Nominal Voltage: 240 V Model: STV 100K-48D Nominal Voltage: 480 V *Not UL Listed. Contact SolaHD Technical Support for details. Model: STV 100K-10D4 Nominal Voltage: 120/240 V Three-phase delta high leg, 4W + G Model: STV 100K-24D4 Nominal Voltage: 240/480 V 2.0 Troubleshooting If any of the diagnostic indicators indicate a problem (e.g.
4.0 Specifications Table 2: Technical Specifications Model Parameters STV100K10N STV100K24L STV100K10S STV100K10Y STV100K23Y Nominal Input Voltage 120 V 240 V 120/208–240 V 120/208 V 230/400 V System Configuration 1-phase 2W + G 1-phase 2W + G 1-phase 3W + G 3-phase wye 4W + G 3-phase wye 4W + G Maximum Continuous Operating Voltage (MCOV) 125% of the nominal level for 120 V; 115% for all other voltages Line Frequency 47–63 Hz Response Time <0.
Table 2: Technical Specifications Model Parameters STV100K27Y STV100K24D STV100K48D STV100K10D4 STV100K24D4 Nominal Input Voltage 277/480 V 240 V 480 V 120/240 V 240/480 V System Configuration Maximum Continuous Operating Voltage (MCOV) 3-phase wye 4W + G 3-phase delta 3-phase delta 3-phase delta 3-phase delta high leg high leg 3W + G 3W + G 4W + G 4W + G 125% of the nominal level for 120 V; 115% for all other voltages Line Frequency 47–63 Hz Response Time <0.