Installer Information
On two transformer systems, the transformers MUST be in phase. Measure
the voltage across RC and RH. If more than 12 Volts AC is present between
RC and RH, then the transformers are NOT in phase. To correct this condition,
reverse the secondary low voltage connections at either the Heating or
Cooling transformer.
Thermostat installation and all components of the control system shall
conform to Class II circuits per the NEC code. Do not use on circuits
exceeding specified voltage.
Do not use on circuits exceeding specified voltage. Higher voltage will
damage control and could cause shock or fire hazard.
To prevent electrical shock and/or equipment damage, disconnect
electric power to system at maincircuit breaker box until installation
is complete.If “Call For Service” is displayed on your Sensi thermostat,
and E4 or E5 appears where the room temperature should be displayed
or the backlight is flashing, please call our support team immediately
at 888.605.7131.