INSTALLATION, OPERATION AND MAINTENANCE MANUAL EMI AMERICA SERIES MULTI-ZONE LIMITED RANGE HEAT PUMP CONDENSING UNITS S2HA HEAT PUMPS Nominal Circuit Capacities: 9,000 & 12,000 Btuh units. S2HA Multi-Zone Enviromaster International LLC 5780 Success Dr. Rome, NY 13440 www.enviromaster.com An ISO 9001-2000 Certified Company P/N# 240006458 Rev. 1.
EMI AMERICA SERIES MULTI-ZONE HEAT PUMP CONDENSING UNITS INSTALLATION, OPERATION AND MAINTENANCE MANUAL P/N 240006458, Rev. 1.0 [01/07] This manual is intended as an aid to a qualified service personnel for proper installation, operation, and maintenance of these EMI America Series multi-zone heat pump condensing units. Read the instructions thoroughly and carefully before attempting installation or operation.
EMI AMERICA SERIES MULTI-ZONE HEAT PUMP CONDENSING UNITS DESCRIPTION INSTALLER SUPPLIED ITEMS EMI offers the finest dual zone heat pump outdoor units in the ductless split market, the S2HA Condensing Unit. The S2HA allows the installation of two circuits from a single outside location when space or aesthetic requirements limit the use of the number of cabinets outdoors. Each zone is independent so no mixing of refrigerant occurs.
INSTALLATION INSTRUCTIONS UNIT MOUNTING SECTION Side discharge unit allows for permanent mounting through the feet. This is highly recommended due to the vertical design of the unit. Accumulator Compressor Capacitor 1. Loosen the screws on left and right sides of the front panel. (Do not remove these screws.) Filter Driers Lag Bolts 5. Insert lag bolts through the holes in the bottom of the unit and tighten to secure. 2. Remove the screws on the front of the panel. 3. To remove front panel: 6.
ELECTRICAL WIRING INSTALLATION SECTION ! DANGER ! The EMI America Series condensing unit must: • Be connected to a properly grounded electrical supply with the proper voltage as stated on the rating plate. 3. Use only HACR type breakers or time delay fuses. Select the wire size according to the ampacity rating. 4. To access electrical connections and wiring diagram: a) Remove the screws on the side panel adjacent to the back panel.
ELECTRICAL WIRING INSTALLATION SECTION Inside electrical access panel. Note: Refer to the units’ wiring diagram for all wiring. Wire Diagram 8. Check wiring diagram for the required number of low voltage wires to be run between indoor and outdoor sections. Low Volt High Volt Plastic Edge Guards 9. Connect the 24 Volt wiring matching color to color. Refer to the wiring diagram on the inside panel of the condenser, and also refer to the wiring diagram on the indoor unit.
REFRIGERANT PIPING INSTALLATION SECTION INTERCONNECTING TUBING SPECIFICATIONS Model 9900 2200 9200 • Be certain no burrs remain on the fittings. MAX. Max. Liquid Suction Length Lift Line O.D. Line O.D. 100’ 35’ 1/4" 1/2" 100’ 35’ 1/4" 1/2" 100’ 35’ 1/4" 1/2" • Use only clean refrigeration tubing. • Use tube benders to guard against kinking. • Avoid piping on wet and rainy days and insulate suction line. Be certain that plastic end caps remain in place when inserting through wall openings.
REFRIGERANT PIPING INSTALLATION SECTION 1. Clean the ends of tubing and insert into fittings. 4. Braze tubing into fittings. S1C Shown 2. Protect the valves by wrapping with a wet rag "heat sink" before brazing. 5. Verify that the correct piston for the system match is in place, refer to the air handler Installation Instructions. 6. Refer to the indoor air handler Installation Instructions for any specific details regarding the connection of tubing. Connect and braze tubing into the indoor air handler. 7.
REFRIGERANT PIPING INSTALLATION SECTION S1CA Shown Refer to Refrigerant Charge Table for specified line charge. S2CA Shown nt igera Refr Note: Charging should be done with a dial-a-charge or weighed in with a scale. 9. Once certain of a good evacuation and leak free joints, back-seat the valves (counter-clockwise) to open and allow factory charge to fill lines and indoor unit. 10. Charge to proper weight, charge based on feet of interconnect (table on next page) S1CA Shown 11.
REFRIGERANT PIPING INSTALLATION SECTION REFRIGERANT CHARGE TABLE FOR S2HA CIRCUIT CAPACITY EVAPORATOR PAIRING LINE CHG/FT LINE LENGTH LINE ADJUST 3 OZ. 6 OZ. 13 OZ. 3 OZ. 6 OZ. 13 OZ. 9,000 Btuh WLHA09, CAHB12 WLHA12, CAHB12 .25 OZ. 10 25 50 12,000 Btuh WLHA12 CAHB12 .25 OZ. 10 25 50 FACTORY CHARGE SYSTEM TOTAL S2HA S2HA 42 45 48 55 46 49 52 59 IMPORTANT NOTES: 1.
FIELD CHARGING Cooling Cycle S2HA 9,000 Btuh circuit Cooling Cycle S2HA 12,000 Btuh circuit with EMI’s-WLHA09 or CAHA12 (���������� ��� ��������������� ��������������������� ��� �������������������� �������������������� ��� with EMI’s-WLHA09 or CAHB12 (���������� ��� ��� ��� ��� ��� ��� �� �� �� �� ����� ����� ����� �� �� �� �� ����� ����� ����� �� �� �� �� �� ��� ���� ��� ��� ��� ���� ������������������ ��� ������������������������� ������������������������� ��� ��� ������������
FIELD CHARGING Heat Cycle S2HA 9,000 Btuh circuit Heat Cycle S2HA 12,000 Btuh circuit with EMI WLHA09 or CAHB12 (���������� �������������������� ��������������� ��� ��� ��� ������������������� ��� ��� ��� ��� ��� ����� ����� ����� �� �� �� �� ����� ����� ����� �� �� �� �� ���������������������� �� ���������������������� ��� ��� �� ��������������� ��� ������������������� �������������������� ��� with EMI WLHA12 or CAHB12 (���������� �� �� �� � ���� ��� ��� ��� ��� �� ��������������
REFRIGERANT PIPING INSTALLATION SECTION FIELD CHARGING NOTE: If operating superheat is more than 5°F above the chart value, add refrigerant. If below the chart value remove refrigerant. If below the limit line, remove refrigerant. Example (Using the 12,000 Btuh cooling chart): 1. Suction pressure is 65 psi. which equals 38° F on The R-22 Scale of the LowSide Gauge. 2. Suction line temperature taken at the unit is 70° F. 70° F minus 38° F equals 32° F superheat. 3.
START-UP AND TROUBLESHOOTING TEST PROCEDURE The Test Unit Performance Data sheet below is provided for use by a qualified service professional. In order for our Technical Service Department to better serve you, please complete and have this information ready when calling. Make sure to include the Model Number, Serial Number, Date of Installation. Call our Technical Support Department @ 1-800-228-9364.
MULTI-ZONE CONDENSER SEQUENCE OF OPERATION EMI America Series multi-zone heat pump condensers are designed to operate with EMI America Series indoor air handlers. Both the condenser (outdoor unit) and evaporator (indoor unit) have a high Volt service connection. Each is to be independently connected to the electrical service panel. (See the unit name plate for the correct breaker type and size). The outdoor and indoor units are also connected to each other through a low Volt interconnect wiring.
MULTI-ZONE CONDENSER SEQUENCE OF OPERATION When the outdoor temperature falls below 35°F, compressor operation will cease. At that point the unit will switch on the indoor units electric heater to assume the heating demand, (second stage of heat). Note: For full operation the indoor unit must have an electric heater. S2HA LOW VOLT INTERCONNECT DIAGRAMS WL HA Wall unit Heat P ump A pplic ations I.D. UNIT O.D.
S2HA DIMENSIONS AND SPECIFICATIONS NOTE: All EMI products are subject to ongoing development programs so design and specifications may change without notice. 15” 38” Easy access interconnects on back of unit 44” 1/2” Diameter Lag Holes Front of unit 3.00” Electrical connections 12.44” 28.74” 4.63” 4.63” S2HA ELECTRICAL SPECIFICATIONS MODEL VOLTS/HZ/PHASE (1) FAN COMPRESSOR 1 COMPRESSOR 2 TOTAL AMPS MIN. CIR. HACR AMPS BRKR (2) RLA HP RLA LRA RLA LRA 9900 208-230/60/1 1.8 0.33 3.
S2HA SYSTEM PERFORMANCE WLHA WLHA S2HA S2HA / WLHA SYSTEM PERFORMANCE MODEL COOLING HEATING S2HA (Outdoor) Indoor Units Btuh SEER SHR EER Btuh C.O.P. 9900 WLHA09 + WLHA09 18,600 13.0 .80 12.2 16,000 3.3 2200 WLHA12 + WLHA12 22,600 13.0 .72 11.9 20,400 3.3 9200 WLHA09 + WLHA12 20,600 13.0 .76 12.0 18,200 3.