Corp. Heat Pump INSTALLATION, OPERATION AND MAINTENANCE MANUAL S2HA, T2HA

www.enviromaster.com
10
Multi-zone Heat Pump Condensing Units
The system will support refrigerant runs
to the inside unit of up to 100' equivalent
feet with a 35' rise included. The units
are furnished with sweat connections and
are equipped with refrigerant valves and
Schrader fittings for charging and taking
S2HA & T2HA REFRIGERANT PIPING INSTALLATION SECTION
A P-trap is recommended when the suc-
tion riser is equal to or greater than 20
feet in height.
When the condenser is installed above
the evaporator, the P-trap will help the
return of oil back to the compressor.
The placement of the P-trap should be at
the halfway mark of
the suction riser. For
example if the suc
-
tion riser is 30 feet tall
then a P-trap is recom
-
mended at the 15 foot
mark of the suction
riser
(see Figure #1).
A P-trap may be fabri
-
cated using;
(2) street elbows and
(2) regular elbows. A
prefabricated trap
may be purchased
from a Wholesaler or Distributor how
-
ever the trap should be shallow as
the:
(4) elbow configuration. Each elbow is
approximately 2 equivalent feet. One
P-trap is equal to approximately 8
equivalent feet.
P-TRAP INSTALLATION
30’
15’
Evaporator
or
Condenser
Evaporator
or
Condenser
Figure #1
pressure readings. The following precau-
tions should be made:
Be certain no burrs remain on the
fittings.
• Use only clean refrigeration tubing.
Use tube benders to guard against
kinking.
Avoid piping on wet and rainy days
and insulate suction line. Be certain
that plastic end caps remain in place
when inserting through wall openings.
Isolate tubing from transmitting vibra
-
tion to the building or unit and avoid
contact with sharp edges. Refrigera-
tion valves should be wrapped with
a wet rag "heat sink" to protect
valves while brazing.
INTERCONNECTING TUBING SPECS
S2HA, T2HA, T3HA, & T4HA models:
Nominal
Circuit
Capacity
Maximum
Length
Maximum
Lift
Liquid
Line
OD
Suction
Line
OD
9,000 100’ 35’ 1/4” 1/2”
12,000 100’ 35’ 1/4” 1/2”
18,000 100’ 35’ 3/8” 5/8”
24,000 100’ 35’ 3/8” 3/4”
NOTE: Refrigerant Piping Installation for both the S2HA & T2HA models.