4.3 Program Parameters
i
, , , , and parameters are observed if
Operating type is selected “ Cooling ”. If operating type is selected “ Heating ”
beginning of the parameters list is shown.
Hysteresis Parameter for Output ( Default = 1 )
1 to 100 °C for TC Type Devices,
1 to 100 °C for PT-100 (-50°C , 400°C) and PT-1000 (-50°C , 400°C),
0.1 to 10.0 °C for PT-100 (-19.9°C, 99.9°C) and PT-1000 (-19.9°C, 99.9°C),
1 to 20 °C for PTC (-50°C, 150°C) and NTC (-50°C, 100°C),
0.1 to 10.0 °C for PTC (-19.9°C, 99.9°C) and NTC (-19.9°C, 99.9°C)
Minimum Set Value Parameter ( Default =Minimum value of device scale )
Set value can not be lower than this value. This parameter value can be adjusted
from minimum value of device scale to maximum set value parameter
Maximum Set Value Parameter ( Default = Maximum value of device scale )
Set value can not be greater than this value. This parameter value can be adjusted
from minimum set value to maximum value of the device scale
Process Offset Parameter ( Default = 0 )
-100 to 100 °C for TC Type Devices,
-100 to 100 °C for PT-100 (-50°C , 400°C) and PT-1000 (-50°C , 400°C),
-10.0 to 10.0 °C for PT-100 (-19.9°C, 99.9°C) and PT-1000 (-19.9°C, 99.9°C),
-20 to 20 °C for PTC (-50°C, 150°C) and NTC (-50°C, 100°C),
-10.0 to 10.0 °C for PTC (-19.9°C, 99.9°C) and NTC (-19.9°C, 99.9°C)
Switch On Delay After Power On Parameter ( Default = 0 )
When power is first applied to the device, this time delay must be expired for
activation of the compressor. It can be adjusted from 0 to 20 minutes
Compressor Stop/Start Time Delay Parameter ( Default =0 )
When compressor is inactive, this time delay must be expired for activation of the
compressor. It can be adjusted from 0 to 20 minutes.
Probe Defect Parameter ( Default = 0 )
Compressor is active during this time period in case of probe defect
( Default = 0 ) If Probe Defect Parameter is , then this parameter
can be observed. It can be adjusted from 0 to 99.
Compressor is OFF in case of probe defect
Compressor is ON in case of probe defect
Compressor operates periodically according to and time
periods in case of probe defect.
Compressor Start/Start Time Delay Parameter ( Default =0 )
This time delay must be expired between two activation of the compressor.
It can be adjusted from 0 to 20 minutes.
Operating Type Parameter ( Default = 0 )
Heating
Cooling
Compressor is inactive during this time period in case of probe defect
( Default = 0 ) If Probe Defect Parameter is , then this parameter
can be observed. It can be adjusted from 0 to 99.
Programming Mode Accessing Password ( Default =0 )
It is used for accessing to the programming mode. It can be adjusted from 0 to 999.
If it is selected 0, password is not entered for accessing to the parameters.