5. Failure Messages in ESM-1510 Temperature Controller
Probe defect in analogue inputs. Sensor connection is wrong or
there is no sensor connection.
SV
P
ESM-1510
SET
°C
Temperature Controller
27
6. Specifications
Device Type : Temperature Controller
Housing&Mounting : 86mm x 35mm x 59mm plastic housing for Rail Mounting.
Protection Class : IP20.
Weight : Approximately 0.14 Kg.
Environmental Ratings : Standard, indoor at an altitude of less than 2000 meters
with none condensing humidity.
oooo
Storage / Operating Temperature: -40 C to +85 C / 0 C to +50 C
Storage / Operating Humidity : 90 % max. (None condensing)
Installation : DIN Rail Mounting
Overvoltage Category : II.
Pollution Degree : II, office or workplace, none conductive pollution
Operating Conditions : Continuous
Supply Voltage and Power : 230 V V (± 15%) 50/60 Hz. 1.5 VA
115 V V (± 15%) 50/60 Hz. 1.5 VA
24 V V (± 15%) 50/60 Hz. 1.5 VA
24 V W (- 15%, + 10%) 50/60 Hz. 1.5 VA
10...30 V Z 1.5 W
Temperature Sensor Inputs : NTC, PTC, TC, RTD
NTC Input Type : NTC (10 kW @.25 °C )
PTC Input Type : PTC (1000 W @.25 °C )
Thermocouple Input Types : J, K (IEC584.1)(ITS90)
Thermoresistance Input Type : PT-100, PT-1000 (IEC751)(ITS90)
Accuracy : ±1% of full scale for thermocouple and thermoresistance
Cold Junction Compensation : Automatically ± 0.1°C/1°C.
Sensor Break Protection : Upscale
Sampling Cycle : 3 samples per second
Control Form : ON / OFF
Relay Output : Resistive Load 5 A@250 V V
(Electrical Life : 100.000 operation (Full Load)
Optional SSR Output : Maximum 28 mA, Maximum 15 V Z
Display : 9 mm Red 3 digits LED Display
Leds : SV (Green) , OUT (Red) , P(Red) 3 mm
Approvals : ,