User manual
2.2PanelCut-Out
2.GeneralDescription
2.1FrontViewandDimensionsofESM-3710-NTemperatureController
MountingClamp
PanelSurface
(maximumthickness15mm/0.59inch)
FrontPanel
IP65protection
NEMA 4X
ESM-3710-N77x35 DINSize TemperatureController
InstructionManual.ENGESM-3710-N01V0407/14
-4DigitsDisplay
-NTCInputor
PTCInputor
(Mustbedeterminedinorder.)
- Adjustabletemperatureoffset
-Operationselectionofcompressoroperatescontinuously,
stopsoroperatesperiodicallyincaseofsensordefect
-Compressorprotectiondelays
- Adjustableinternalbuzzeraccordingtosensordefectstatus.
-Passwordprotectionforprogrammingsection
-InstallingparametersusingProkey
-Remoteaccess,datacollectingandcontrollingwithModbusRTU
-HavingCEmarkaccordingtoEuropeanNorms
-
JTypethermocoupleInputor,
KTypethermocoupleInputor,
2-WirePT-100Inputor,
2-WirePT-1000Input
ON/OFFtemperaturecontrol
Selectableheatingorcoolingfunction
-Selectionofoperationwithhysteresis
- Adjustabletemperatureoffset
-
-Setvaluelowlimitandsetvaluehighlimitboundaries
ESM- 77x35DINSize3710-N
Digital,ON/OFFTemperature
Controller
OperatingTemperature:
Max.OperatingHumidity :
Altitude :
0to50°C
90%Rh(non-condensing)
Upto2000m.
Forbidden Conditions:
Corrosive atmosphere
Explosive atmosphere
Home applications (The unit is only for industrial applications)
c
1.2GeneralSpecifications
1.Preface
ESM-3710Nseriestemperaturecontrollersaredesignedformeasuringandcontrolling
temperature. TheycanbeusedinmanyapplicationswiththeirOn/Offcontrolform,heating
andcoolingcontrolformandeasy-useproperties.Someapplicationfieldswhichtheyare
usedarebelow:
ApplicationFields Applications
Glass Heating
Food BakingOvens
Plastic Incubators
Petro-Chemistry Storages
Textile, Automative AirConditioning
MachineProductionIndustriesEtc... Etc...
2
1.1EnvironmentalRatings
3 41615
13 14
A visual inspection of this product for possible damage occurred during shipment is
recommended before installation. It is your responsibility to ensure that qualified mechanical
and electrical technicians install this product.
If there is danger of serious accident resulting from a failure or defect in this unit, power off the
system and separate the electrical connection of the device from the system.
The unit is normally supplied without a power supply switch or a fuse. Use power switch and fuse
as required.
Be sure to use the rated power supply voltage to protect the unit against damage and to prevent
failure.
Keep the power off until all of the wiring is completed so that electric shock and trouble with the
unit can be prevented.
Never attempt to disassemble, modify or repair this unit. Tampering with the unit may results in
malfunction, electric shock or fire.
Do not use the unit in combustible or explosive gaseous atmospheres.
During putting equipment in hole on the metal panel while mechanical installation some metal
burrs can cause injury on hands, you must be careful.
Montage of the product on a system must be done with it’s fixing clamps. Do not do the montage
of the device with inappropriate fixing clamp. Be sure that device will not fall while doing the
montage.
It is your responsibility if this equipment is used in a manner not specified in this instruction
manual.
EMKO Elektronik warrants that the equipment delivered is free from defects in material and
workmanship. This warranty is provided for a period of two years. The warranty period starts
from the delivery date. This warranty is in force if duty and responsibilities which are determined
in warranty document and instruction manual performs by the customer completely.
Repairs should only be performed by trained and specialized personnel. Cut power to the
device before accessing internal parts.
Do not clean the case with hydrocarbon-based solvents (Petrol, Trichlorethylene etc.). Use of
these solvents can reduce the mechanical reliability of the device. Use a cloth dampened in
ethyl alcohol or water to clean the external plastic case.
1.3Installation
1.4Warranty
1.5Maintenance
1.6ManufacturerCompany
ManufacturerInformation:
Repairandmaintenanceserviceinformation:
EmkoElektronikSanayive Ticaret A.Þ.
DemirtaþOrganizeSanayiBölgesiKaranfilSk.No:616369BURSA/TURKEY
Phone:+902242611900
Fax:+902242611912
EmkoElektronikSanayive Ticaret A.Þ.
DemirtaþOrganizeSanayiBölgesiKaranfilSk.No:616369BURSA /TURKEY
Phone:+902242611900
Fax:+902242611912
DeviceType
Housing&Mounting
ProtectionClass
Weight
EnvironmentalRatings
Storage/OperatingTemperature
Storage/OperatingHumidity
Installation
OvervoltageCategory
PollutionDegree
OperatingConditions
SupplyVoltageandPower
TemperatureSensorInput
NTCinputtype
PTCinputtype
Thermocoupleinputtype
Thermoresistanceinputtype
Accuracy
ColdJunctionCompensation
SensorBreakProtection
SamplingCycle
ControlForm
RelayOutput
OptionalSSRDriveOutput
Display
LED
InternalBuzzer
: TemperatureController
:76mmx34.5mmx71mmplastichousingforpanel
Mounting.Panelcut-outis71x29mm.
:NEMA 4X(Ip65atfront,Ip20atrear).
: Approximately0.20Kg.
:Standard,indooratanaltitudeoflessthan2000meters
withnonecondensinghumidity.
:-40 Cto+80 C/-30 Cto+80 C
:90%max.(Nonecondensing)
:Fixedinstallation
:II.
:II,officeorworkplace,noneconductivepollution
:Continuous
:
:115
:24
:24
:10-30
:NTC,PTC, TC,RTD
:NTC(10k @25°C)
:PTC(1000 @25°C)
:J,K(IEC584.1)(ITS90)
:PT-100,PT-1000(IEC751)(ITS90)
:±1%offullscaleforthermoresistance
: Automatically±0.1°C/±1°C
:Upscale
:3samplespersecond
:ON/OFF
: A@250V forResistiveload( Output)
(Electricallife:100.000switchingatfullload)
:Maximum20mA,Maximum17V
:14mmRed4digitsLEDDisplay
:S(Green),P (Green), C(Yellow), F(Yellow),
CompressorOutput(Red),HeatingOutput(Red)
: 83dB
:
o o o o
o o
W
W
³
16(8) V
Approvals
230V ( %15)50/60Hz-1.5VA
V ( %15)50/60Hz-1.5VA
V ( %15)50/60Hz-1.5VA
V ( %15)50/60Hz-1.5VA
V 1.5WZ
Z
V
V
V
W
±
±
±
±
Compressor
7.Specifications
All order information of ESM-3710-N Temperature Controller are given on the table at above. User
may form appropriate device configuration from information and codes that at the table and convert it to
the ordering codes.Firstly, supply voltage then other specifications must be determined. Please fill the
order code blanks according to your needs.
Please contact us, if your needs are out of the standards.
V
Z
Vac,
Vdc
Vdc or Vac
can be applied
Þ
Þ
ÞW
c
8.OrderingInformation
Note-1:If input type is selected PTC or NTC (BC= 12, 18), Temperature sensor is given with the
device.For this reason, if input type is selected as PTC,sensor type (V = 0,1 or 2) or if input type is
selected as NTC, sensor type (V = 0,3 or 4) must be declared in ordering information.
ESM-3710-N
PowerSupply
Input
TemperatureSensor
Input
76mm/3inch
O
F
O
C
S
P
6mm/0.24inch
34,5mm/1.36inch
65mm/2.56inch
Maximum15mm/0.59inch
110mm/4.33inch(min)
71mm/2.79inch
29mm/1.14inch
50mm/1.97inch(min)
230V ( %15)50/60HzV ±
OptionalSupplyVoltage
-30V Z
115V ( %15)50/60Hz,
24V ( %15)50/60Hz,
24V ( %15)50/60Hz,
10
±
±
±
V
V
W
Standard
A BC D E FG HI /
/
U
V W Z/
/
0 1 0 0
1
RelayOutput(16(8) A@250V ,atresistiveLoad,1NO)V
CompressorOutput
E
SupplyVoltageA
InputType
BC
Scale(°C)
ESM-3710-N
4
-50°C/-58°F; 150°C/302°F
12
PTC(Not-1)
Temp.Sensorwhichisgivenwith ESM-3710-N
V
0
None
3
NTC-M5L20.K1.5(NTCSensor,thermoplasticmouldedwith1.5mcable
forcoolingapplication)
4
NTC-M6L50.K1.5(NTCSensor,stainlesssteelhousingwith1.5mcable
forcoolingapplication)
9
Customer
115V ( %15)50/60Hz-1.5VAV ±
5
230V ( %15)50/60Hz-1.5VAV ±
00 00
8
10-30V Z
-50°C/-58°F; 100°C/212°F
18
NTC(Not-1)
1
PTC-M6L40.K1.5(PTC AirProbe1.5mtSiliconCable)
2
PTCS-M6L30.K1.5.1/8”(PTCLiquidProbe1.5mtSiliconCable)
(77x35DINSizes)
YourTechnologyPartner
www.emkoelektronik.com.tr
Thankyouverymuchforyourpreferenceto
useEmkoElektronikproducts,pleasevisitour
webpagetodownloaddetailedusermanual.
9.Optional Accessories
RS-485CommunicationInterface
1.RS-485Module
2.PROKEY ProgrammingModule
Thedeviceisprogrammed(Uploador
Download)byusingtheparameters.
ü
ESM3710-N
SET
P
0°C/32°F; 800°C/1472°F
05
J,FeCuNiIEC584.1(ITS90)
0°C/32°F; 999°C/1830°F
10
K,NiCrNiIEC584.1(ITS90)
-50°C/-58°F; 400°C/752°F
11
PT 100,IEC751(ITS90)
-19.9°C/-4°F; 99.9°C/212°F
09
PT 100,IEC751(ITS90
-50°C/-58°F; 400°C/752°F
14
PT 1000,IEC751(ITS90)
-19.9°C/-4°F; 99.9°C/212°F
13
PT 1000,IEC751(ITS90
3
24V ( %15)50/60Hz-1.5VAV ±
NTC,PTC,
JorKTypeTC
2-WirePT-100
PT-10002-Wire
Output-1
ControlOutput
AlarmOutput
Output-1
Standard
Optional
(RelayOutput)
(SSRDriveOutput)
HeatingorCooling
Function
ON/OFFOperation
ControlOutput
AlarmOutput
2
SSRDriver Maximum20m,Maximum17VOutput( )Z
2
24V ( %15)50/60Hz-1.5VAW ±
,