6.2 Modbus Adresses of Device Status Parameters (Read Input Register)
10
Buzzer is active during this time
When this parameter is 1, if decrement button is pressed, is observed. In this
condition buzzer is active till buzzer silence button is pressed.
( Default = ) MODBUS ADDRESS:40016
If buzzer function selection parameter value =0, this parameter can not be
observed. Buzzer stays active during this time. It can be adjusted from 1 to 99 minutes
Programming Section Accessing Password
.
( Default = 0 ) MODBUS ADDRESS:40019
It is used for accessing to the programming section. It can be adjusted from 0 to 9999. If it is
selected 0, password will not be asked
PROKEY communication selected.
Communication Mode Selection Parameter ( Default = 0 ) MODBUS ADDRESS:40017
Rs485 communication selected.
Slave ID Parameter ( Default = 1 ) MODBUS ADDRESS=40018
Device communication address parameter (1 to 247).
, , , , and Parameters are observed if Operation type
is selected “Cooling”. If operation type is selected “Heating ,skip to the parameter
i
Compressor Start-Start Delay Parameter ( Default = 0) MODBUS ADRES:40011
This time delay must be expired between two activation of the compressor. It can be
adjusted from 0 to 20 minutes.
Sensor Defect Parameter ( Default = 0 ) MODBUS ADRES:40012
Compressor is active during this time period in case of probe defect (Default = 0)
MODBUS ADRES:40013
If probe defect parameter is 2, then this parameter is observed. It can be adjusted
from 0 to 99 minutes.
Compressor is OFF in case of sensor defect.
Compressor is ON in case of sensor defect.
Compressor operates periodically according to and Time periods in
case of sensor defect.
Compressor is inactive during this time period in case of probe defect
( Default = 0 )MODBUS ADRES:40014
If probe defect parameter is 2, then this parameter is observed. It can be adjusted
from 0 to 99 minutes.
Buzzer Function Selection Parameter ( Default = 0 ) MODBUS ADDRESS:40015
Buzzer is inactive.
Buzzer is active during sensor failures.
Compressor Stop-Start Delay Parameter ( Default = 0) MODBUS ADRES:40010
When compressor is inactive, this time delay must be expired for activation of the
compressor. It can be adjusted from 0 to 20 minutes
MODBUS ADDRESS:30001 Temperature Value
MODBUS ADDRESS:30002 Reserved
o
MODBUS ADDRESS:30003 Led Status : 0.bit C Led,
6.bit Compressor Led,
13.bit Program Led, 14.bit Set Led
MODBUS ADDRESS:30004 Device Status : 1.bit Buzzer Status
2.bit Sensor Lost Status
MODBUS ADDRESS:30005 Output Status
MODBUS ADDRESS:30006 Device Type and Device Version
A