10 - When power is on ; not starting the normal operation and blinking
the bottom display as shown on the left;
It appears when two analogue input modules ( EMI-410, EMI-430,
EMI-440, EMI-450 ) are plugged in Module-1 and Module-2 socket at
the same time.
For starting normal operation power off and pull out one of the
analogue input modules.
11 - When power is on ; not starting the normal operation and blinking
the bottom display as shown on the left;
It appears when two EMI-420 CT input modules are plugged in
Module-1 and Module-2 socket
For starting normal operation power off and pull out one of the EMI-420
CT input modules.
V
V
°C
°F
V
O1
O2
O3
SV
REMOTE RAMP MAN AUTO
AT
SET
°C
°F
V
O1
O2
O3
SV
REMOTE RAMP MAN AUTO
AT
SET
10.Specifications
DeviceType
Housing&Mounting
ProtectionClass
Weight
EnvironmentalRatings
Storage/OperatingTemperature
Storage/OperatingHumidity
Installation
OvervoltageCategory
PollutionDegree
OperatingConditions
SupplyVoltageandPower
ProcessInputs
ThermocoupleInputTypes
ThermoresistanceInputTypes
VoltageInputTypes
CurrentInputTypes
Accuracy
ColdJunctionCompensation
LineCompensation
SensorBreakProtection
:ProcessController
:48mmx48mmx116mm1/16DIN43700plastichousingforpanel
mounting.Panelcut-outis46x46mm.
Type-1EnclosureMounting.
:NEMA 4X(IP65atfront,IP20atrear).
: Approximately0.21Kg.
:Standard,indooratanaltitudeoflessthan2000meters
withnonecondensinghumidity.
:-40 Cto+85 C/0 Cto+50 C
:90%max.(Nonecondensing)
:Fixedinstallation
:II
:II,officeorworkplace,noneconductivepollution
:Continuous
:100-240V (-15%/+10%)50/60Hz6VA
24V (-15%/+10%)50/60Hz6VA
24V (-15%/+10%)6W
:Universalinput TC,RTD, Voltage/Current
:Selectablebyparameters
L (DIN43710),
J,K,R,S,T ,B,E,N(IEC584.1)(ITS90),C(ITS90)
:PT 100(IEC751)(ITS90)
:Selectablebyparameters0...50mV ,0...5V ,
0...10V
:Selectablebyparameters0...20mA ,4...20mA
:±0,25%offullscaleforthermocouple,thermoresistance
andvoltage,
±0,70%offullscaleforcurrent.
: Automatically±0.1°C/1°C.
:Maximum10 .
:Upscale
o o o o
V
V
Z
Z