Programmable Timer EZM-9935 96x96 DIN 1/4 EZM-9935 96 x 96 DIN 1/4 Universal Input Programmable Timer - 6 digits Process (PV) and 6 digits Set (SV) Value Display - Operation with 1 Set Value - Reset , Pause and Start Inputs - Operation with Automatic and Manual Reset - NPN/PNP Type Operation - Programmable Time Bases (Second, Minute, Hour) Introduction Manual.
ABOUT INSTRUCTION MANUAL Instruction manual of EZM-9935 Programmable Timer consists of two main sections. Explanation of these sections are below. Also, there are other sections which include order information and technical specifications of the device. All titles and page numbers in instruction manual are in “CONTENTS” section. User can reach to any title with section number.
CONTENTS 1.PREFACE..................................................................................................................Page 5 1.1 GENERAL SPECIFICATIONS 1.2 ORDERING INFORMATION 1.3 WARRANTY 1.4 MAINTENANCE 2.INSTALLATION......................................................................................................... Page 7 2.1 GENERAL DESCRIPTION 2.2 DIMENSIONS 2.3 PANEL CUT-OUT 2.4 ENVIRONMENTAL RATINGS 2.5 PANEL MOUNTING 2.6 INSTALLATION FIXING CLAMP 2.7 REMOVING FROM THE PANEL 3.
EU DECLARATION OF CONFORMITY Manufacturer Company Name : Emko Elektronik A.S. Manufacturer Company Address: DOSAB, Karanfil Sokak, No:6, 16369 Bursa, Turkiye The manufacturer hereby declares that the product conforms to the following standards and conditions.
1.Preface EZM Series Programmable Timer can be used in package machines, production and quality control rollers, and can be adapted easily to all mechanical construction and automation system. Some application fields which they are used are below: Application Field Package machines, Quality Control rollers, Filling Systems, Tool Benchs, Building Automation. Production bands 1.
1.2 Ordering Information EzM-9935 A BC D E / FG HI 00 0 1 / 00 00 / A Supply Voltage 2 3 4 5 9 24 V V (-%15;+%10) 50/60Hz 24 VZ (-%15;+%10) 24 V V (-%15;+%10) 50/60Hz 115 V V (-%15;+%10) 50/60Hz 230V V (-%15;+%10) 50/60Hz Customer (Maximum 240V V (-%15;+%10))50/60Hz E Output-1 1 / U V W Z ( 96x96 1/4 DIN) Relay Output (5A @ 250 V V) Rezistive Load 0 0 0 0 All order information of EZM-9935 Programmable Timer are given on the table at left.
2.Installation c Before beginning installation of this product, please read the instruction manual and warnings below carefully. In package , - One piece unit - Two pieces mounting clamps - One piece instruction manual A visual inspection of this product for possible damage occured during shipment is recommended before installation. It is your responsibility to ensure that qualified mechanical and electrical technicians install this product.
2.1 General Description Mounting Clamp EZM -9 93 5 O1 OP S1 SV P Device Label SET RES ET Time r Panel surface (maximum thickness 15 mm / 0.59 inch) Front Panel IP65 protection NEMA 4X 2.2 Dimentions Maximum 15 mm / 0.59 inch S1 SV O1 OP P SET RESET Timer 96 mm / 3.78 inch 96 mm / 3.78 inch EZM-9935 11.5 ± 1 mm / 0.45 inch 84mm / 3.
2.3 Panel Cut-out 92 mm / 3.62 inch 129 mm / 5.08 inch (min) 129 mm / 5.08 inch (min) 92 mm / 3.
2.4 Environmental Ratings Operating Conditions Operating Temperature : 0 to 50 °C Max. Operating Humidity : 90% Rh (non-condensing) Altitude c : Up to 2000m. Forbidden Conditions: Corrosive atmosphere Explosive atmosphere Home applications (The unit is only for industrial applications) 2.5 Panel Mounting 1-Before mounting the device in your panel, make sure that the cut-out is the right size. 1 2-Check front panel gasket position 3-Insert the device through the cut-out.
2.6 Installation Fixing Clamp 1 2 The unit is designed for panel mounting. 1-Insert the unit in the panel cut-out from the front side. EZM -9935 O1 OP 2- Insert the mounting clamps to the holes that located top and bottom sides of device and screw up the fixing screws until the unit completely immobile within the panel S1 SV P SET RES ET Time r c Montage of the unit to a system must be done with it’s own fixing clamps. Do not do the montage of the device with inappropriate fixing clamps.
3.Electrical Wirings c c c c You must ensure that the device is correctly configured for your application. Incorrect configuration could result in damage to the process being controlled, and/or personal injury. It is your responsibility, as the installer, to ensure that the configuration is correct. Parameters of the device has factory default values. These parameters must be set according to the system’s needs. Only qualified personnel and technicians should work on this equipment.
3.2 Electrical Wiring Diagram c Electrical wiring of the device must be the same as ‘Electrical Wiring Diagram’ below to prevent damage to the process being controlled and personnel injury. P/N : EZM-9935 cY 5A@250VV C NO NC 11 12 13 14 15 a PAUSE START RESET 0VZ 12 V Z Max 50mA NOTE-1 1 2 3 4 5 Relay Output Sensor Supply Voltage Inputs Supply Voltage Input 230V V (-%15;+%10) 50/60Hz - 2.3VA 115V V (-%15;+%10) 50/60Hz - 2.3VA 24 V V (-%15;+%10) 50/60Hz - 2.
3.3 View of Device Label c aY 1 2 3 4 Pause Start 5A@250VV Reset 0VZ 230 VV ± 15% 50/60 Hz - 2.3VA 12 V Z Max.
3.
3.5 Input Connection 3.5.1 Proximity Connection 2 0VZ PROX. PNP PNP 3 RESET 1 12 V Z Max. 50mA PNP PROX. 4 5 PAUSE PROX. PNP type operation START = NOTE-1 = PROX. PROX. PROX. 1 2 3 4 5 RESET START PAUSE NPN 0VZ NPN 12 V Z Max.
3.5.2 Switch Connection 5 PAUSE 4 START 12 V Z Max. 50mA Switch 3 RESET 2 0VZ 1 Switch PNP type operation Switch = NOTE-1 3 4 5 RESET START PAUSE Switch 2 0VZ 12 V Z Max.
3.6 Relay Output Wiring Diagram L N 5A V T Fuse C 11 NC 13 Last Control Element (Contactor) 12 NO c Fuse Load c Fuses must be selected according to the applications. 3.7 Galvanic Isolation Test Results of EZM-9935 EZM-9930 Programmable Timer Counter 500V V ( for EZM-9935.3 ) 2000V V ( for EZM-9935.
4.Definition of Front Panel and Accessing to the Set Parameters 4.1 Definition of Front Panel EZM-9935 Led indication of output is active Displays Actual Value and Name of Program Parameter Displays SET and Parameter Value S1 SV O1 OP P SET RESET Led indication of SV:SET value Timer PROG Button is Used for accessing to the Program Parameters SHIFTING Button is used for Changing the cursor position in Programming mode and entering the SET Value.
4.2 Power On Observation of EZM - 9935 Programmable Timer and Software Revision on the Display When power is applied to the device, software revision number of the controller is momentarily illuminated on actual value display. Then operation screen is observed.
4.3 Adjustment of SET Value Changing SET Value SET Screen Operation Screen SET P S1 SV O1 OP S1 SV O1 OP RESET SET P RESET Press Shift button again. When shift button is pressed, 6th digit of SET value starts to flash. SET Screen S1 SV O1 OP S1 SV O1 OP SET P SET Screen RESET SET P 5th digit of SET value starts to flash. RESET Press Shift button again. Increase the flashing value with increment button.
4.4 Resetting the Count Value Operation Screen P S1 SV O1 OP S1 SV O1 OP Operation Screen SET RESET P SET RESET When RESET button is pressed, Actual Value becomes the 0 Value. i RESET operation can be realized by Reset button or applying signal to the RESET input. These two operations are named MANUAL RESET in parameters section. At the end of MANUAL RESET; if then Count value becomes 0 value. If then Count value becomes SET value.
4.5 Accessing to the Program Parameters In this section Accessing to the Program parameters process is shown. For details on parameters refer to PROGRAM PARAMETERS section.
The most significant digit of the parameter (1st digit for this parameter) flashes. Output Functions S1 SV O1 OP SET P Press PROG button to exit from programming section without doing any changes. RESET You can change the parameter with INCREMENT button, save it to the memory and pass to the next parameter with ENTER button. Press Enter Button The most significant digit of the parameter (1st digit for this parameter) flashes.
The most significant digit of the parameter (1st digit for this parameter) flashes. Data Record SET P Press PROG button to exit from programming section without doing any changes. The most significant digit of the parameter (1st digit for this parameter) flashes. S1 SV O1 OP RESET You can change the parameter with INCREMENT button, save it to the memory and pass to the next parameter with ENTER button.
P S1 SV O1 OP S1 SV O1 OP SET RESET Operation Screen P SET RESET Time Unit and Scale Selection Continue to press ENTER button for scanning all parameters.
8. Program PARAMETRELER 5. Parameters Time Unit and Scale Selection Hour/Minute It can be adjusted from to Minute/Second It can be adjusted from to Second/Milisecond It can be adjusted from to Hour/Minute It can be adjusted from to Hour It can be adjusted from to Minute It can be adjusted from to Second It can be adjusted from to Filter Time of Reset, Pause and Start Inputs It is used to protect against the electrical contact debounce or the signal that is less than the determined pulse time.
Output Functions Manual Reset-1. Device continues to count till manual reset is applied. (Output PulseTime is not considered) Count direction : 0 --> P (Upcounting) = Start Reset Set 0 Output = = Or When count value reaches the Set Value, Output Position is changed. Counting process continues over the SET value. Output Pulse Time is not considered. Process counts, until manual reset happens. Counting is continues, while Start input is active. When Start input is passive, count value becomes “0”.
Manual Reset-2. Device continues to count till manual reset is applied. (Output pulse Time is not considered) Counting direction : 0 --> P (Upcounting) = Start Reset Set 0 Output = = Or When count value reaches the Set Value, Output Position is changed. Counting process is not continue over the SET value. Output Pulse Time is not considered. Process counts, until manual reset happens. When Manual Reset happens, count value becomes 0 value. Counting is continues, while Start input is active.
Manual Reset-3. Device continues to count till manual reset is applied. (Output Pulse Time is considered.) Counting direction : 0 --> P (Upcounting) = Start Reset Set 0 Output = Output = When count value reaches the Set Value, Output Position is changed. If Output Pulse time is not 0, then Output = Position is changed at the end of the Pulse time. If then Output Position has not change, until Manual Reset happens. Counting process continues over the SET value.
Automatic Reset-1 Counting direction : 0 --> P (Upcounting) = Start Reset Set 0 Output = Output = When count value reaches the Set Value, Output Position is changed. Actual value is reset automatically. While Start input is active, then counting starts upcounting from 0 value. If Output Pulse time is not 0, then Output Position is changed at the end of the Pulse time. If , then Output Position has not changed until = Manuel Reset happens. When Manual Reset happens, count value becomes 0 value.
Automatic Reset-2 Counting direction : 0 --> P (Upcounting) = Start Reset Set 0 = Output Start Reset Set 0 Output = When count value reaches the Set Value, Output Position is changed. If Output Pulse time is not 0, then Output Position is changed at the end of the Pulse time and Actual value is reset and if the Start input is active, then counting starts from 0 value. If output pulse time is “0”, then output position has not change until Manual Reset happens.
Counting direction : P --> 0 (Downcounting) = Start Reset Set 0 Output = Start Reset Set 0 Output = When count value reaches the 0 Value, Output Position is changed. If Output Pulse time is not 0, then Output Position is changed at the end of the Pulse time and Actual value is reset. If the Start input is active, then counting starts from Set value. If output pulse time is 0, then output position has not change until Manual Reset happens. Actual counting value stops at 0 value.
Automatic Reset-3 Counting direction : 0 --> P (Upcounting) = Start Reset Set 0 = Output Start Reset Set 0 = Output When count value reaches the Set Value, Output Position is changed. If Output Pulse time is not 0, then Output Position is changed at the end of the Pulse time and Real counting value is shown on Actual = value screen. If output pulse time then, output position has not change until Manual Reset happens.
Counting direction : P --> 0 (Downcounting) = Start Reset Set 0 Output = Start Reset Set 0 Output = When count value reaches the 0 Value, Output Position is changed. If Output Pulse time is not 0, then Output Position is changed at the end of the Pulse time and Real counting value is shown on Actual = value screen. If output pulse time , then output position has not change until Manual Reset happens.
Automatic Reset-4 Counting direction : 0 --> P (Upcounting) = Start Reset Set 0 = Output Start Reset Set 0 Output = When count value reaches the Set Value, Output Position is changed. If Output Pulse time is not 0, then Output Position is changed at the end of the Pulse time and counting value becomes 0 and output becomes inactive position. If output pulse time ,then = output position has not change until Manual Reset happens.
Counting direction : P --> 0 (Downcounting) = Start Reset Set 0 Output = Start Reset Set 0 Output = When count value reaches the 0 Value, Output Position is changed. If Output Pulse time is not 0, then Output Position is changed at the end of the Pulse time and counting value becomes Set value and = output becomes inactive position. If output pulse time , then output position has not change until Manual Reset happens. When counting value reach 0 value, output position becomes active position.
Automatic Reset-5 is not considered. Counting direction : 0 --> P (Upcounting) = Start Reset Set 0 Output = = Or If the Start input is active, then Process starts counting, until count value reach SET value. When count value reach SET value, Output Position becomes active position and process is automatically reset. If the Start input is active, then process start counting from “0” value. If count value reach SET value, Output Position becomes passive position.
Output Run Type Output Normally non-energised Output Normally energised Output Pulse Time It determines how long Output will be active. It can be adjusted from 00.00.00 to 99.59.99 (99 minutes; 59.99 seconds). For details, refer to the section where output functions are defined Direction of Counting Upcount. ( 0 --> Preset ) Downcount. ( Preset --> 0 ) Data Record Count value is saved to memory when power is disconnected and restored on power up.
Program Password It is used for accessing to the program parameters. It can be adjusted from to . If it is , there is no password protection while accessing to the parameters. When programming button is pressed, will appear on the display. If program password is not “0” while accessing to the program parameters ; 1- If user does not enter the value correctly ; operation screen will appear without entering to operator parameters.
6. Failure Messages in EZM-9935 Programmable Timer 1-If the password is not 0, user can access to the parameters without entering the password and by pressing ENTER button. User can see all parameters except for programming password parameter but user can not do any changes in parameters. If password is entered for accessing to the parameters correctly, most significant digit of the parameter flashes. But if the password is not entered, flashing of the most significant digit is not realised.
S1 SV O1 OP SET P RESET Operation Screen SET P P SET RESET Time Unit and Scale Selection RESET 3-If Actual Value is flashing and counting is stopped ; It appears if any of the count value is lower than the minimum count value. To remove this warning and reset the count value press RESET button. S1 SV O1 OP P 2-If Actual Value is flashing and counting is stopped ; It appears if any of the count value is greater than the maximum count value.
7. Specifications Device Type Housing & Mounting : Programmable Timer : 96mm x 96mm x 87.5 1/4 DIN 43700 plastic housing for panel mounting. Panel cut-out is 92x92mm Protection Class : NEMA 4X (IP65 at front, IP20 at rear). Weight : Approximately 0.34 Kg. Environmental Ratings : Standard, indoor at an altitude of less than 2000 meters with none condensing humidity Storage / Operating Temperature: -40 oC to +85 oC / 0 oC to +50 oC Storage / Operating Humidity : 90 % max.