GAS SUPPLY
Thegaspipelinecanbebroughtinthroughtherightorleftsideof
the appliance. The insert has a Flexline with shutoff valve located on
the left side when facing the unit. See Figures 16 and 17. Consult
the current National Fuel Gas Code, ANSI Z223.1 CAN/CGA-B149
(.1 or .2) installation code.

Pipe Length Schedule 40 Pipe



Nat. L.P. Nat. L.P.
0-10ft
0-3m
1/2"
12.7mm
3/8"
9.5mm
1/2"
12.7mm
3/8"
9.5mm
11-40ft
4-12m
1/2"
12.7mm
1/2"
12.7mm
5/8"
15.9mm
1/2"
12.7mm
41-100ft
13-30m
1/2"
12.7mm
1/2"
12.7mm
3/4"
19mm
1/2"
12.7mm
101-150ft
31-46m
3/4"
19mm
1/2"
12.7mm
7/8"
22.2mm
3/4"
1.9 mm
Caution:Neveruseplasticpipe.Checktoconrmwhetheryour
localcodesallowcoppertubingorgalvanized.
Notice: Since some municipalities have additional local codes, it
isalwaysbesttoconsultyourlocalauthorityandinstallationcode.
The use of the following gas connectors is recommended:
— ANSZ21.24ApplianceConnectorsofCorrugatedMetalTubing
and Fittings.
— ANSZ21.45AssembledFlexibleApplianceConnectorsofOther
Than All-Metal Construction
Theaboveconnectorsmaybeusedifacceptablebytheauthority
having jurisdiction. The state of Massachusetts requires that a
exibleapplianceconnectorcannotexceedthreefeetinlength.
Figure 16

Eachapplianceshouldhaveitsownmanualgascock.
Amanualmaingascockshouldbelocatedinthevicinityoftheunit
andcanbe easilyaccessedafterassembly. Wherenoneexists,
or where its size or location is not adequate, contact your local
authorized installer for installation or relocation.
Compoundsusedonthreadedjointsofgaspipingshallberesistant
totheactionofliqueedpetroleumgases.Thegaslinesmustbe
checkedforleaksbytheinstaller.Thisshouldbedonewithasoap
solutionwatchingforbubblesonallexposedconnections,andif
unexposed,apressuretestshouldbemade.




Notice: Themillivoltgascontrolsareequippedwithacapturedscrew
type pressure test point, therefore it is not necessary to provide a
1/8"testpointupstreamofthecontrol.
Whenusingcopperorexconnectoruseonlyapprovedttings.
Theapplianceandit’sindividualshutoffvalvemustbedisconnected
from supply piping system during any pressure testing of that system
attestpressuresinexcessof1/2psig(3.5kPa).
Theappliancemustbeisolatedfromthegassupplypipingsystem
byclosingitsindividualmanualshutoffvalveduringanypressure
testingofthegassupplypipingsystemattestpressuresequalto
orlessthan1/2psig(3.5kPa).
Attention! If one of the procedures results in pressures in excess of
1/2psig(14"w.c.)(3.5kPa)onthereplacegasvalve,itwillresult
in a hazardous condition.
Figure 17
Shutoffvalvemustbeaccessibleafterinstallation.

MILLIVOLT VALVES (VFL(L,Z)48SP30)
Natural gaswillhaveamanifoldpressureofapproximately3.5"w.c.
formaximuminputor1.6"w.c.forminimuminputatthepressure
regulator outlet with the inlet pressure to the pressure regulator
fromaminimumof4.5"w.c.forthepurposeofinputadjustmentto
amaximumof10.5"w.c.
Propane gas willhaveamanifoldpressureapproximately10.0"w.c.
(2.49kPa)formaximuminputor6.3"w.c.forminimuminputatthe
pressure regulator outlet with the inlet pressure to the pressure
regulator from a minimum of 11.0"w.c. for the purpose of input
adjustmenttoamaximumof13.0"w.c.
INTERMITTENT PILOT VALVES (VFL(L,Z)48SP90)
Natural gaswillhaveamanifoldpressureofapproximately3.5"
w.c. at the pressure regulator outlet with the inlet pressure to the
pressureregulatorfromaminimumof7.0"w.c.forthepurposeof
inputadjustmenttoamaximumof10.5"w.c.
Propane gas willhaveamanifoldpressureapproximately10.0"w.c.
at the pressure regulator outlet with the inlet pressure to the pressure
regulator from a minimum of 11.0"w.c. for the purpose of input
adjustmenttoamaximumof13.0"w.c.
A test gage connection is located downstream of the gas appliance
pressure regulator for measuring gas pressure. The connection is
a 1/8 inch N.P.T. plugged tapping.
Millivolt Control Valve
Thevalveregulatorcontrolstheburnerpressurewhichshouldbe
checkedatthepressuretestpoint.Turncapturedscrewcounter
clockwise2or3turnsandthenplacetubingtopressuregaugeover
testpoint(Usetestpoint“A”closesttocontrolknob).See Figure
41.After taking pressure reading,     
     Do not over torque. Check
forgasleaks.