THERMOSTAT LOCATION (SG MODELS)
CAUTION Do not run wire behind flanges of Header Plate
or in any location where it might be damaged.
Millivolt wall thermostats are specially designed for use on self-
generating systems. They should never be used on line or low
voltage A.C. circuits.
Interior Wall The thermostat should be installed on an inside
wall away from the furnace but in the same room.
Note: Use 16 gauge wire to prevent excessive loss of milli-
volts.
Proper operation depends on a good pilot flame. The flame must
cover the top of the thermopile. Cleaning of the pilot orifice and
burner may be required due to spiders.
System Check (Figure 7)
A millivolt meter is required to check the system. Millivolt
readings should be:
Across the thermopile terminals, 400-450 millivolts with
thermostat OFF.
Across the thermopile terminals, 150-250 millivolts with
thermostat ON.
Across the thermostat wires at the valve, less than 30 millivolts
with thermostat ON.
Across the thermostat wires at the thermostat, less than 5
millivolts with thermostat ON. (Dirty pilot or low pressure
will reduce readings.)
Connect thermostat wires to gas valve as shown in Figure 7.