Owner`s manual

26591-1-1209Page 22
Figure 26
MINIMUM HOLE LOCATION DIMENSIONS FOR
THROUGH THE WALL HORIZONTAL INSTALLATIONS
WITH 90 DEGREE ELBOW AND 1' VERTICAL VENT OFF
TOP OF FIREPLACE
Positioning the Fireplace
Determine the exact position of the appliance so the direct vent
termination will be centered (if possible) between two (2) studs. This
will avoid any extra framing. All vent kit pipes should be assembled

Cutting the Hole (Figures 26)

the hole through the exterior wall of the house can be cut. This hole
must be 11" (279.4 mm) high x 10" (254mm) wide with its center
line determined by the amount of vertical rise and horizontal run
of the termination. See Figure 26.
When locating the hole it must be noted that the bottom of the cap
must be 12" (305mm) above the ground level, and top of the cap
must be no less than 18" (457mm) below a combustible projection,
and no closer than 9" (229mm) to any wall running parallel to vent
termination. See Figure 27.
SEE VENT CHART
FOR PERMISSIBLE
“H” AND “V”
DIMENSIONS
1 FOOT VERTICAL
PIPE REQUIRED
(MINIMUM)
A
CENTER OF ELBOW
STRAIGHT OUT
(MINIMUM)
10”
(254mm)
C
B
V
C
B
H
11
(279mm)
MAXIMUM HORIZONTAL
RUN WITH1FOOT VERTICAL
RISE AND 90° ELBOW
MAXIMUM HORIZONTAL
RUN WITH MINIMUM
VERTICAL RISE AND
90° ELBOW
2’ MAX.
(609.6mm)
20’ (6.1m)
PIPE STRAPS
EVERY3 (91cm)
8’ (244cm)
TO BOTTOM
OF UNIT
VENT CAP
NOTE:1FOOT SECTION (MIN.)
OF VERTICAL VENT REQUIRED
WHEN USING HORIZONTAL
TERMINATION OFF TOP.
9” (229 MM)
MINIMUM
Figure 27
Figure 28
FIREPLACE
SERIES
HARD ELBOW DIMENSIONS
"A" "B" "C"
DVP36(SP,PP) 53"
(1346.2mm)
4 1/2"
(114.3mm)
6 1/2"
(165.1mm)