NOTE: When installing this vent system in a chase, it is always
good building practice to insulate the chase as you would the
outside walls of your home. This is especially important for cold
climate installations. Upon completion of building your chase
framing, install the vent system by following the instructions in
this manual. Remember to build the chase large enough so that
minimum clearance of combustible materials (including insulation)
to the vent system are maintained.


    
vertical vent rise is between 10 feet and 40 feet. To maintain the
        
VIB6A for use with 6 5/8" diameter vent systems, or the VIB7A
for use with 7" diameter vent systems. These are available from
your Empire Comfort Systems, Inc. distributor or dealer.


the air inlet pipe. A decrease in the height or the appearance of the



vertical top.

Kit for proper installation.
Reassembly and Resealing Vent Pipe System

the vertical or horizontal position, replace horizontal and vertical
pipe lengths, elbows and horizontal or vertical termination kit.
All rigid pipe vent system components lock into place by sliding the
concentric pipe section with four (4) equally spaced interior beads
onto the appliance collar or previously installed component end with
four (4) equally spaced indented sections. When the internal beads
of each starting outer pipe line up, rotate pipe section clockwise 90°
(approximately 3 inches). The vent pipe is now locked together.


and locked into the preceding component in the vent system.
Vertical Through the Roof Applications (Figure 62)
Your Gas Fireplace has been approved for:
a) Vertical installations up to 40 feet in height.
b) Two sets of 45 degree elbow offsets within these vertical
installations. From 0 to a maximum of 8 ft. a vent pipe can be
used between elbows.
c) Wall straps must be used to support offset pipe every 4'.

and use the appropriate venting components.
Figure 62
VERTICAL TERMINATION (continued)
TYPICAL ROOF
SUPPORT
TYPICAL JOIST
SUPPORT
40’
(12.19M)
MAXIMUM
FLEX VENT
35’
(10.67M)
MAXIMUM
8’ (2.44M)
MAXIMUM
8’ (2.44M)
MAXIMUM
45°
45°