Owner`s manual
28040-3-0511Page 18
8”
MINIMUM CLEARANCE
TO PERPENDICULAR
COMBUSTIBLE SIDE-WALL
Figure 11
Propane gas will have a manifold pressure approximately 10.0"w.c.
at the pressure regulator outlet with the inlet pressure to the pressure
regulator from a minimum of 11.0"w.c. for the purpose of input
adjustment to a maximum of 13.0"w.c.
A test gage connection is located downstream of the gas appliance
pressure regulator for measuring gas pressure. The connection is
a 1/8 inch N.P.T. plugged tapping.
Millivolt Control Valve
The valve regulator controls the burner pressure which should be
checked at the pressure test point. Turn captured screw counter
clockwise 2 or 3 turns and then place tubing to pressure gauge over
testpoint(Usetestpoint“A”closesttocontrolknob).Aftertaking
pressure reading,
Do not over torque. Check for gas leaks.
MILLIVOLT VALVES
Natural gas will have a manifold pressure of approximately 3.5" w.c.
for maximum input or 1.7" w.c. for minimum input at the pressure
regulator outlet with the inlet pressure to the pressure regulator
from a minimum of 4.5" w.c. for the purpose of input adjustment to
a maximum of 10.5" w.c.
Propane gas will have a manifold pressure approximately 10.0"w.c.
(2.49kPa)formaximuminputor4.9"w.c.forminimuminputatthe
pressure regulator outlet with the inlet pressure to the pressure
regulator from a minimum of 11.0"w.c. for the purpose of input
adjustment to a maximum of 13.0"w.c.
INTERMITTENT PILOT VALVES
Natural gas will have a manifold pressure of approximately 3.5"
w.c. at the pressure regulator outlet with the inlet pressure to the
pressure regulator from a minimum of 7.0" w.c. for the purpose of
input adjustment to a maximum of 10.5" w.c.
GAS SUPPLY (continued)
CLEARANCES