Specifications
10 EMPYRE PRO SERIES INSTALLATION AND OPERATION MANUAL
INSTALLATION
Trench for Underground Pipes
1. The water lines
must be prop-
erly insulated
to minimize
heat loss. Ask
your dealer for
the right under-
ground water
line insulation.
2. Dig a trench,
minimum 24 in
(61 cm) deep* and 12 in (30 cm) wide, and make
as level as possible to avoid damage to the tubing.
* Trench should be at least 36 inches (91 cm) deep under
driveways.
3. The water lines should be a minimum of 1” (2.54
cm) inside dimensions*, rated and approved for
use with high temperature water.
* Size of water lines depends on distance; consult with
a qualied heating professional to determine the line
size necessary to meet the demands of your specic
application.
4. Identify each water line clearly in order to
correctly locate the supply and return lines.
5. Lay down 14-2 underground wire approved for
underground installation. Obtain the required
electrical permit and conrm local electrical
code requirements prior to installation.
Foundation Dimensions
Thespecicationsbelowprovideastableconcrete
pad for the Empyre Pro Series furnace. The open
area indicated by ‘E’ in the drawing provides a
channel for plumbing and electrical conduit.
NOTE: Furnace can also be installed on concrete
patio blocks.
Pro Series 200 Pro Series 400
in cm in cm
A 4 10 5 13
B 48 122 49 124
C 67 170 76 193
D 4 10 4 10
E 10 25 10 25
F 25 64 25 64
House
Shop
Insulated Lines
Typical Installation
Water Lines