User's Manual

EMS Wireless Operator’s Manual
EkoLink Plus Fiber Optic DAS
39
Modem dialing
MEMNUMBER.
BOTH = Remote unit will
use both methods to report
alarm.
PEAK 20 - 39 SET PEAK 36 Allows the user to set a
LOWER peak output power
than the factory setting.
ALARM # ON or OFF SET ALARM 2
OFF
If alarm is turned off, unit
will not check for specific
alarm condition.
DESIG # 0 – 3 SET DESIG 2 3 Change the designation of
alarm #. Determines the
specific alarm’s value:
0 = Non-reporting
1 = Minor
1 = Major
2 = Critical
PWD # 8
alphanumerics
SET PWD 1
1Passwrd
CASE SENSITIVE and can
only be used by User ID1
and 2.
UID # 8
alphanumerics
SET UID 1
1UserNam
CASE SENSITIVE and can
only be used by User ID1
and 2.
DT xx/xx/xx SET DT
12/31/02
Date in month/day/year
format.
TM xx:xx:xx SET TM
16:33:00
Time in 24 hour format.
ID Up to 19
alphanumerics
SET ID
unit1location
User defined name or
location of repeater; seen
at MUM also.
Note: The SET UL and DL ATTN commands override the auto setup feature and
allows the repeater to be set up outside of the RF detected power range of the
repeater. Peak power limit will still function properly at the lowest usable level of
detection, 18 dBm typical. User may wish to disable down link power detect alarm
which will be on constantly due to no RF detected.