Data Sheet

ELECTRICAL CHARACTERISTICS
230V AC +%10-%20, 50/60Hz ; 12V AC/DC ± %10 ; 24V AC/DC ±%10 or 10-30VDC / 8-24VAC ±%10 SMPS
Max. 3VA
2.5mm² screw-terminal connections
EN 61326-1: 2013 (Performance criteria B h a s bee n satisfied for EN 61000-4-3 standard)
EEPROM (Min. 10 years)
±1% - 1sec.
Max. 100ohm
EN 61010-1: 2010 (Pollution degree 2, overvoltage category II ).
Suitable for flush-panel mounting according to DIN 43 700.
W77xH35xD61 mm
Approx. 215g (after packing)
Self extinguishing plastics
Single set-poin t and al a rm control
12-bit accuracy, 100ms sam p ling time
Adjustable between 0.1 and 15.0 °C/F
Max.2000m
KEEP AWAY device from exposed to corrosive, volatile and flammable gas es or
liquids and DO NOT USE the device in similar hazardous locations.
80% Relative humidity for temperatures up to 31°C, decreasing linearly to 50% at 40°C.
0 ... +50°C/-25 ... +70°C (with no icing)
According to EN 60529 ; Front Panel : IP65, Rear Panel : Ip20
Avoid any liquid contact when the device is switched on.
DO NOT clean the device with solvent (thinner, gasoline, acid etc.) and / or abrasive cleaning agents.
Scale Range
Accuracy
EN 60751
- ... 0 °C -76.0...302.0°F60.0 15 .0
± 1% (Full scale) ±
1 digit
Supply
Power Consumption
Wiring
Line Resistance
Data Protection
Time Accuracy
EMC
Safety Requirements
HOUSING
Housing Type
Dimensions
Weight
Enclosure Ma terial
CONTROL
Control type
Kontrol yöntemi
A/D converter
Hysteres is
ENVIRONMENTAL CONDITIONS
INPUT
Height
Ambient / Storage Temper a ture
Relative Humidity
Protection Class
Input Type
NTC Resistive Sensor
3.5 digit, 7-segmen t 19mm red LED
Scale
8A : NO and NC 250V AC, 8A (resistive load), Control output.
20A : NO 250V AC, 20A (resistive load), Control ou tput.
8A : Mechanical 30.000.000; Electrical 300.000 operation. 250V AC, 8A (resistive load).
20A : Mechanical 30.000.000; Electrical 100.000 operation. 250V AC, 20A (resistive l o a d ).
OUTPUT
Life expectancy for relay
C1 Output
Holding screw
0.4-0.5Nm
Equipment is protected throughout
by DOUBLE INSULATION.
ENDA EDT3 11 COOLING / DEFROST CONTROLLER4
77x35mm sized.
Single NT C probe input.
Offset value can be entered for NT C input .
Cooling or heating control sel ection.
Defrost duration and interval time settin gs.
Delay time and minimum operating time settings for compressor protection.
Compressor or door alarm control via digital input.
In case of probe failure, output status can be set to ON, OFF or periodic.
Upper and Lower setpoint value limits can be adjusted.
Temperature unit can be selected °C or °F.
Upper/Lowe r limits and delay t i me ass i gnments for Alarm.
RS485 communication features with Modbus RTU protocol. (Specify at Order).
Parameter transferr i ng feature via ENDAKEY-RF. (Specify at Order).
CE Marked according to European standards.
71,5mm
8 68 040 7 7 26 1 72
C1
1 2 3 4 5 6
7 8 9
10
ENDA INDUSTRIALELECTRONICS
SN: XXXXXXXXX
EDT3411-230-08
DIGITAL THERMOSTAT
11
12
250V AC 8A
RESISTIVE LOAD
MADE IN TURKEY
2
B
A
TECHNICIAL SPECIFICATIONS
2
3
4
3
1
Read this document carefully before using this device. The guarantee will be expired by device
if you don't attend to the directions in the user manual. Also we don't accept any
compensationsforpersonalinjury,material damage or capitaldisadvantages.
damages
Thank you for choosing ENDA EDT3411 temperature controllers.
CONNECTION DIAGRAM
ENDA EDT3411 is intended for installation i n control panels. Make sure that the device is used
only for intended purpose. The electrical connections must be carried out by a qualified staff
and must be according to the relevant locally applicable regulations. During an installation, all of the
cablesthat are connected to the device must be free of electricalpower. The device must be protected
against inadmissible humidity, vibrations, severe soiling and make sure that the operation
temperatureisnot exceeded.The cablesshould notbe close to the power cablesor components.
SUPPLY:
NOTE:
184-253V AC
50/60Hz 4VA
Line
Neutral
230V AC
Supply
Switch
Cable size: 1,5mm²
Fuse
F 100 mA
250V AC
Fuse should
be connected
11
12
Note:
1)
2)
Mains supply cords shall meet the requirements of
IEC 60227 or IEC 60245.
In accordance with the safety regulations, the power
supply switch shall bring the identification of the
relevant instrument and it should be easily
accessible by the operator.
EDT3411- -EN 29092021
Removal of the device from t he front
Panel cut-out
1) Panel thickness
shou l d be maximum
7mm.
2) If there is no 60mm
free spa ce at the back
side of the device, it
would b e difficult to
remove it from the
panel.
1
To mounting device ;
- Push the device in
direction .
Note :
A
2
B - Push the clamps in the direction .
Remove the device from the panel by
pulling i n direction .
A - Remove the side covers by lifting
them wi th a flat screwdriver in direction
To removing the device from panel :
2
3
4
Order Code : EDT3411 - - -
1 2 3
1- Su pply Voltage
230... ..230V AC
24........24V AC
...
0 /DC
012........12V AC/DC
SM.........10-30VDC / 8- 24VAC
2- Output Selection
Relay out put
.... Relay output
08.....8A
20 .20A
3- ModBus
Blank.....N/A
RS.........Modbus
(Specify at Order)
8 6804 07 726882
C1
1 2 3 4 5 6
7 8 9
10
ENDA INDUSTRIALELECTRONICS
SN: XXXXXXXXX
EDT3411-230-20-RS
DIGITAL THERMOSTAT
11
12
250V AC 20A
RESISTIVE LOAD
MADE IN TURKEY
+
-
A
B
RS485
SURAN Industrieelektronik
Dettinger Str. 9
D-72160 Ho rb a.N.
Tel.: +49 (0)7451 / 625 6 17 E-mail : info@suran-elektronik.de
Fax: +49 (0)7451 / 625 0650 Internet : www.suran-elektronik.de