Datasheet

J (Fe-CuNi) Thermocouple
K (NiCr-Ni) Thermocouple
T (Cu-CuNi) Thermocouple
S (Pt/0Rh-Pt) Thermocouple
R (Pt13Rh-Pt) Thermocouple
0-20 mA
4-20 mA
EN 60584
EN 60584
EN 60584
EN 60584
EN 60584
EN 60584
EN 60584
0... 600
0...1200
0... 400
0...1600
0...1600
°C
°C
°C
°C
°C
+32... +1112
+32... +2192
+32... +752
+32... +2912
+32... +2912
°F
°F
°F
°F
°F
Pt 100 Resistance Thermometer
Pt 100 Resistance Thermometer
EN 60751
EN 60751
-200...600
-99.9...300.0
-999...4000
-999...4000
°C
°C
0,2% ( )of full scale
0,2% ( )of full scale
1 digit
1 digit
0,2% ( )of full scale 1 digit
0,2% ( )of full scale 1 digit
0,2% ( )of full scale
0,2% ( )of full scale
0,2% ( )of full scale
1 digit
1 digit
1 digit
0,2% ( )of full scale
1 digit
0,2% ( )of full scale 1 digit
-328... +1112
-99.9...+543.0
°F
°F
°C
°F
OUTPUTS
Selectable as Control or Alarm2 output.Relay : 250V AC, 2A ( for resistive load), NO/NC.
Selectable as 0-20mA, 4-20mA analog output or logic control output(max. load 400 12V/20mAÙ)
(Alarm1 output).Relay : 250V AC, 2A ( for resistive load), NO/NC selectable.
AL1
ANL/SSR
Mechanical 30.000.000 operation; Electrical 300.000 operation
Life expectancy for relay
CONT./AL2
ENDA EUC442 PID UNIVERSAL CONTROLLER
* 48 x 48mm sized.
* Selectable sensor type.
* Selectable 0-20mA or 4-20mA input.
* Soft-Start.
*
Automatic calculation of PID parameters (SELF TUNE).
* Selectable Heat/Cool control.
* Communication vi RS-485 ModBus protocol (Optional).a
* Selectable 0-20mA or 4-20mA analog control output.
* Relay output can be programmable as second alarm or control output.
* AL1 relay output for first alarm out.
* Input offset feature.
* In the case of sensor failure relay state
can be selected.
periodical running or
*
Parameter access protection on 3 levels.
* Programming by using keypad or Modbus.
* CE marked according to European Norms.
ThankyouforchoosingENDA EUC442universalcontroller.
* Selectable analog, SSR or relay control output.
Readthisdocumentcarefullybeforeusingthisdevice. Theguaranteewillbeexpiredby
damagingofthedeviceifyoudon'tattendtothedirectionsintheusermanual. Alsowedon't
acceptanycompensationsforpersonalinjury,materialdamageorcapitaldisadvantages.
Enter PID parameters of the system if they are known at the beginning.
Otherwise, Self-Tune should be activated.
TECHNICAL SPECIFICATIONS
Input type Temperature range
Accuracy
ENVIRONMENTAL CONDITIONS
Height
Max. 2000m
80 up to 31 decreasing linearly 50 at 40 .% %
Ambient/storage temperature
Max. Relative humidity
0 ... +50 /°C -25... +70°C (with no icing)
°C °C
Rated pollution degree
According to EN 60529 Front panel : IP6
Rear panel : IP20
5
Do not use the device in locations subject to corrosive and flammable gases.
ELECTRICAL CHARACTERISTICS
Supply
230V AC +10% -20%, 50/60Hz or other power supply (please see page 5, order code)
Power consumption
Max. 5VA
2.5mm² screw-terminal connections
Wiring
Line resistance
Data retention
EMC
Safety requirements
EN 61326-1: 1997, A1: 1998, A2: 2001 (Performance criterion B for standard EN 61000-4-3)
EEPROM (minimum 10 years)
EN 61010-1: 2001 (Pollution degree 2, overvoltage category II)
For thermocouple max.100 , for 3 wired Pt 100 max. 20Ù Ù
CONTROL
Control type Single set-point and alarm control
On-Off / P, PI, PD, PID (selectable)
Control algorithm
A/D converter
15 bits
Sampling time
Proportional band
Derivative time
Integral time
Control period
Hysteresis
Output power
500ms
Adjustable between 0 and 100 . If , On-Off control is selected.Pb 0=% % %
Adjustable between 0.0 and 100.0 minutes
Adjustable between 0.00 and 25.00 minutes
and 250 secondsAdjustable between 1
1 and 50Adjustable between °C/F
The ratio of power at a set point can be adjusted between 0 and 100% %
HOUSING
Housing type
Suitable for flush-panel mounting according to DIN 43 700.
Dimensions
W48xH48xD87mm
Weight
Approx. 250g (after packing)
Self extinguishing plastics.
Enclosure material
While cleaning the device, solvents (thinner, benzine, acid etc.) or must not be used.corrosive materials
uptodate:01022014,modificationreservedandcanbechangeanytimepreviousnotice!
english
RoHS
conform
1./5EUC442-E
UNIVERSAL CONTROLLER
ENDA
PV
SV
CSET
ASET
SET
EUC 442
CNT/AL2