Micropilot FMR10
Endress+Hauser 19
Free-field measurement with flooding protection tube
The flooding protection tube guarantees a definitive analysis of the maximum level even in the event
that the sensor is completely flooded.
In free-field installations and / or in applications where there is a risk of flooding, the flooding
protection tube must be used.
1
2
3
4
A0030394
12 Function of flooding protection tube
1 Air pocket
2 O-ring (EPDM) seal
3 Blocking distance
4 Max. Level
Flooding protection tube 40 mm (1.5 in) Antenna, metallized PBT-PC:
For use with devices in product structure, feature 100 "Process connection front", option WFE
"Thread ISO228 G1-1/2".
The flooding protection tube can be ordered with the device. Product structure, feature 620
"Accessory enclosed", option R7 "Flooding protection tube, metallized PBT-PC suitable for
40 mm (1.5 in) antenna with G1-1/2 process connection on front, extended measuring range
8 m (26.25 ft) liquid".
Alternatively available as an accessory; order number 71325090.
Installation with mounting bracket, adjustable
A0028893
13 Installation with mounting bracket, adjustable
• Wall or ceiling installation is possible.
• Using the mounting bracket, position the antenna so that it is perpendicular to the product
surface.