Power supply failure
The configuration remains stored in the sensor.
Connection FMR20, 4 to 20 mA HART
Circuit diagram / Description
FMR20 connection with HART
communication, voltage source and
4 to 20 mA display
2
3
Y
+ +
- -
I
1
mA
A0028908
 3 FMR20 block diagram, HART
1 Micropilot FMR20
2 HART resistance
3 Power supply
The HART communication resistor of 250 Ω in the signal line is always necessary in the case of
a low-impedance power supply.
The voltage drop to be taken into account is:
Max. 6 V with 250 Ω communication resistor