Installation Instructions
Table Of Contents
- Table of contents
- Important document information
- Terms and abbreviations
- Registered trademarks
- Product life cycle
- Measuring principle
- Input
- Output
- Electrical connection
- Performance characteristics
- Installation
- Environment
- Process
- Mechanical construction
- Operability
- Certificates and approvals
- CE mark
- RoHS
- EAC conformity
- RCM-Tick marking
- Ex approval
- Explosion-protected smartphones and tablets
- Pressure equipment with allowable pressure ≤ 200 bar (2
- EN 302729-1/2 radio standard
- FCC / Industry Canada
- Japanese Radio Law and Japanese Telecommunications Business Law Compliance
- Other standards and guidelines
- Ordering information
- Accessories
- Supplementary documentation
Micropilot FMR20
Endress+Hauser 15
Response time
The response time can be configured. The following step response times (as per DIN EN 61298-2)
1)
apply if the damping is switched off:
Tank height Sampling rate Response time
<20 m (66 ft) 1 s
-1
<3 s
Influence of ambient
temperature
The measurements are carried out in accordance with EN 61298-3.
• Digital (HART, Bluetooth® wireless technology):
Standard version: average T
K
= ±3 mm (±0.12 in)/10 K
• Analog (current output):
– Zero point (4 mA): average T
K
= 0.02 %/10 K
– Span (20 mA): average T
K
= 0.05 %/10 K
1) According to DIN EN 61298-2 the step response time is the time which passes after a sudden change of the input signal until the output signal
assumes 90% of the steady-state value for the first time.