Endress+Hauser V. 10, Rev. 3, 1-10-2019 19
Input values Analog Output:
Analog value from PLC (for sensor block external pressure to compensate gas phase
effects)
Analog value from PLC to be indicated on the display
Digital Output:
Extended diagnostic block
Level limiter
Sensor block measurement on
Sensor block save history on
Status output
Supported functions Identification & Maintenance
Einfachste Geräteidentifizierung seitens des Leitsystems und des Typenschildes
Automatic Ident Number Adoption
GSD compatibility mode with respect to the preceding product Micropilot M FMR2xx
Physical Layer Diagnostics
Installation check of the PRFIBUS segment and the Micropilot FMR5x via the terminal
voltage and telegram surveillance.
PROFIBUS Up-/Download
Up to 10 times faster writing and reading of parameters via PROFIBUS up-/download
Condensed Status
Simple and self-explanatory diagnostic information by categorization of occurring
diagnostic messages.
FOUNDATION Fieldbus
Manufacturer ID 0x452B48
Device type 0x1028
Device Revision 0x01
DD Revision Information and files can be found:
www.endress.com
www.fieldcommgroup.org
CFF Revision
Device Tester Version (ITK Version) 6.0.1
ITK Test Campaign Number IT085300
Link Master (LAS) capable yes
Link Master / Basic Device selectable yes; default: Basic Device
Node address Default: 247 (0xF7)
Features supported Following methods are supported:
Restart
ENP Restart
Setup
Linearization
Self Check
Virtual Communication Relationships (VCRs)
Number of VCRs 44
Number of Link Objects in VFD 50
Permanent entries 1
Client VCRs 0
Server VCRs 10
Source VCRs 43
Sink VCRs 0
Subscriber VCRs 43
Publisher VCRs 43
Device Link Capabilities
Slot time 4