Operating Instructions
Table Of Contents
- Table of contents
- 1 Document information
- 2 Basic safety instructions
- 3 Product description
- 4 Incoming acceptance and product identification
- 5 Mounting
- 5.1 General instructions
- 5.2 Mounting requirements
- 5.3 Mounting the measuring device
- 5.3.1 Encapsulated antenna, PVDF40 mm (1.5 in)
- 5.3.2 Drip-off antenna PTFE 50 mm (2 in)
- 5.3.3 Integrated antenna, PEEK 20 mm (0.75 in)
- 5.3.4 Integrated antenna, PEEK 40 mm (1.5 in)
- 5.3.5 Turning the housing
- 5.3.6 Turning the display module
- 5.3.7 Changing the installation position of the display module
- 5.3.8 Closing the housing covers
- 5.4 Post-mounting check
- 6 Electrical connection
- 7 Operation options
- 8 System integration
- 9 Commissioning
- 10 Operation
- 11 Diagnostics and troubleshooting
- 11.1 General troubleshooting
- 11.2 Error - SmartBlue operation
- 11.3 Diagnostic information on local display
- 11.4 Diagnostic event in the operating tool
- 11.5 Adapting the diagnostic information
- 11.6 Queued diagnostic messages
- 11.7 Diagnostic list
- 11.8 List of diagnostic events
- 11.9 Event logbook
- 11.10 Resetting the device
- 11.11 Device information
- 11.12 Firmware history
- 12 Maintenance
- 13 Repair
- 14 Accessories
- 14.1 Weather protection cover 316L
- 14.2 Plastic weather protection cover
- 14.3 Mounting bracket, adjustable
- 14.4 M12 socket
- 14.5 Remote display FHX50B
- 14.6 Gas-tight feedthrough
- 14.7 Commubox FXA195 HART
- 14.8 HART Loop Converter HMX50
- 14.9 FieldPort SWA50
- 14.10 Wireless HART adapter SWA70
- 14.11 Fieldgate FXA42
- 14.12 Field Xpert SMT70
- 14.13 DeviceCare SFE100
- 14.14 FieldCare SFE500
- 14.15 Memograph M
- 14.16 RN42
- 15 Technical data
- Index
Micropilot FMR60B HART Mounting
Endress+Hauser 21
7 → 8
Display
1.
2.
A0048406 A0046928
‣
Plug in the connection for the
display module in the
connection compartment.
‣
Fit the display module in the
desired position until it clicks
into place.
‣
Screw the display cover firmly
back onto the housing. If fitted:
tighten the screw of the cover
lock using the Allen key
0.7 Nm (0.52 lbf ft).
5.3.8 Closing the housing covers
NOTICE
Thread and housing damaged from dirt!
‣
Remove dirt (e.g. sand) on the cover and housing thread.
‣
If you encounter resistance when closing the cover, check the thread for dirt and clean
it.
Housing thread
The thread of the electronics and connection compartment is coated with lubricant
varnish.
Avoid additional lubrication.
5.4 Post-mounting check
Is the device free from damage (visual inspection)?
Are the measuring point identification and labeling correct (visual inspection)?
Is the measuring device protected against precipitation and sunlight?
Are the securing screws and cover lock tightened securely?
Does the measuring device comply with the measuring point specifications?
For example:
• Process temperature
• Process pressure
• Ambient temperature
• Measuring range