Operating Instructions
Table Of Contents
- Table of contents
- 1 Document information
- 2 Basic safety instructions
- 3 Product description
- 4 Incoming acceptance and product identification
- 5 Mounting
- 5.1 General instructions
- 5.2 Mounting requirements
- 5.3 Mounting the measuring device
- 5.3.1 Encapsulated antenna, PVDF40 mm (1.5 in)
- 5.3.2 Drip-off antenna PTFE 50 mm (2 in)
- 5.3.3 Integrated antenna, PEEK 20 mm (0.75 in)
- 5.3.4 Integrated antenna, PEEK 40 mm (1.5 in)
- 5.3.5 Turning the housing
- 5.3.6 Turning the display module
- 5.3.7 Changing the installation position of the display module
- 5.3.8 Closing the housing covers
- 5.4 Post-mounting check
- 6 Electrical connection
- 7 Operation options
- 8 System integration
- 9 Commissioning
- 10 Operation
- 11 Diagnostics and troubleshooting
- 11.1 General troubleshooting
- 11.2 Error - SmartBlue operation
- 11.3 Diagnostic information on local display
- 11.4 Diagnostic event in the operating tool
- 11.5 Adapting the diagnostic information
- 11.6 Queued diagnostic messages
- 11.7 Diagnostic list
- 11.8 List of diagnostic events
- 11.9 Event logbook
- 11.10 Resetting the device
- 11.11 Device information
- 11.12 Firmware history
- 12 Maintenance
- 13 Repair
- 14 Accessories
- 14.1 Weather protection cover 316L
- 14.2 Plastic weather protection cover
- 14.3 Mounting bracket, adjustable
- 14.4 M12 socket
- 14.5 Remote display FHX50B
- 14.6 Gas-tight feedthrough
- 14.7 Commubox FXA195 HART
- 14.8 HART Loop Converter HMX50
- 14.9 FieldPort SWA50
- 14.10 Wireless HART adapter SWA70
- 14.11 Fieldgate FXA42
- 14.12 Field Xpert SMT70
- 14.13 DeviceCare SFE100
- 14.14 FieldCare SFE500
- 14.15 Memograph M
- 14.16 RN42
- 15 Technical data
- Index
Electrical connection Micropilot FMR60B HART
24 Endress+Hauser
10.5
11.0
12.5
13.5
14.5
15.5
16.5
17.5
18.5
I
LOOP
U
3.6 3.8 4 4.2 4.4 4.6 4.8 5 5.2 5.4
A
B
C
A0047056
A Display lighting switched on, Bluetooth can be switched on optionally
B Display lighting switched off, Bluetooth can be switched on optionally
C Display lighting switched off and Bluetooth not active
6.2.2 Cable specification
Rated cross-section
• Supply voltage
0.5 to 2.5 mm
2
(20 to 13 AWG)
• Protective earth or grounding of the cable shield
> 1 mm
2
(17 AWG)
• External ground terminal
0.5 to 4 mm
2
(20 to 12 AWG)
Cable outer diameter
The cable outer diameter depends on the cable gland used
• Coupling, plastic:
⌀5 to 10 mm (0.2 to 0.38 in)
• Coupling, nickel-plated brass:
⌀7 to 10.5 mm (0.28 to 0.41 in)
• Coupling, stainless steel:
⌀7 to 12 mm (0.28 to 0.47 in)
6.2.3 4 to 20 mA HART
2
3
4
Y
+ +
- -
I
1
mA
A0028908
3 Block diagram of HART connection
1 Device with HART communication
2 HART communication resistor
3 Power supply
4 Multimeter or ammeter
The HART communication resistor of 250 Ω in the signal line is always necessary in
the case of a low-impedance power supply.
Take the voltage drop into consideration:
Maximum 6 V for a 250 Ω communication resistor