8 System integration
8.1 Overview of device description files
Manufacturer ID: 17 (0x0011)
Device type ID: 0x11C1
HART specification: 7.6
DD files, information and files can be found at:
www.endress.com
www.fieldcommgroup.org
8.2 Measured variables via HART protocol
The following measured values are assigned to the device variables at the factory:
Device variable Measured value
Primary variable (PV) Level linearized
Secondary variable (SV) Distance
Tertiary variable (TV) Absolute echo amplitude
Quaternary variable (QV) Relative echo amplitude
The assignment of the measured values to the device variables can be changed in the
following submenu:
Application → HART output → HART output
In a HART Multidrop loop, only one device may use the analog current value for signal
transmission. For all other devices in the "Loop current mode" parameter, select the
Disable option.