Operating Instructions
Table Of Contents
- Table of contents
- 1 Document information
- 2 Basic safety instructions
- 3 Product description
- 4 Incoming acceptance and product identification
- 5 Mounting
- 5.1 General instructions
- 5.2 Mounting requirements
- 5.3 Mounting the measuring device
- 5.3.1 Encapsulated antenna, PVDF40 mm (1.5 in)
- 5.3.2 Drip-off antenna PTFE 50 mm (2 in)
- 5.3.3 Integrated antenna, PEEK 20 mm (0.75 in)
- 5.3.4 Integrated antenna, PEEK 40 mm (1.5 in)
- 5.3.5 Turning the housing
- 5.3.6 Turning the display module
- 5.3.7 Changing the installation position of the display module
- 5.3.8 Closing the housing covers
- 5.4 Post-mounting check
- 6 Electrical connection
- 7 Operation options
- 8 System integration
- 9 Commissioning
- 10 Operation
- 11 Diagnostics and troubleshooting
- 11.1 General troubleshooting
- 11.2 Error - SmartBlue operation
- 11.3 Diagnostic information on local display
- 11.4 Diagnostic event in the operating tool
- 11.5 Adapting the diagnostic information
- 11.6 Queued diagnostic messages
- 11.7 Diagnostic list
- 11.8 List of diagnostic events
- 11.9 Event logbook
- 11.10 Resetting the device
- 11.11 Device information
- 11.12 Firmware history
- 12 Maintenance
- 13 Repair
- 14 Accessories
- 14.1 Weather protection cover 316L
- 14.2 Plastic weather protection cover
- 14.3 Mounting bracket, adjustable
- 14.4 M12 socket
- 14.5 Remote display FHX50B
- 14.6 Gas-tight feedthrough
- 14.7 Commubox FXA195 HART
- 14.8 HART Loop Converter HMX50
- 14.9 FieldPort SWA50
- 14.10 Wireless HART adapter SWA70
- 14.11 Fieldgate FXA42
- 14.12 Field Xpert SMT70
- 14.13 DeviceCare SFE100
- 14.14 FieldCare SFE500
- 14.15 Memograph M
- 14.16 RN42
- 15 Technical data
- Index
Micropilot FMR60B HART Commissioning
Endress+Hauser 37
9.6 Device configuration
9.6.1 Level measurement in liquids
100%
0%
R
BD
D
L
F
E
A0016933
10 Configuration parameters for level measurement in liquids
R Reference point of measurement
D Distance
L Level
E "Empty calibration" parameter (= 0%)
F "Full calibration" parameter (= 100%)
9.6.2 Commissioning with the Commissioning wizard
In FieldCare, DeviceCare, SmartBlue and on the display, the Commissioning wizard is
available to guide the user through the initial commissioning steps.
Complete this wizard to commission the device.
For each parameter, enter the appropriate value or select the appropriate option.
NOTE
If you exit the wizard before completing all required parameters, the changes you made
will be saved. For this reason, the device may be in an undefined state!
In this case, a reset to the default settings is recommended.
9.7 Recording the Echo curve
Record the current Echo curve as a reference echo curve for subsequent diagnostic
purposes
After the measurement has been configured, it is recommended to record the current Echo
curve as a reference echo curve.
The Save reference curve parameter in the Echo curve submenu is used to record the
Echo curve.
Diagnostics → Echo curve → Save reference curve
‣
Under the Save reference curve parameter, activate the Customer reference curve
option
9.8 "Simulation" submenu
Simulation of a process variable, a pulse output or a diagnostic event.