Operating Instructions
Table Of Contents
- Table of contents
- 1 Document information
- 2 Basic safety instructions
- 3 Product description
- 4 Incoming acceptance and product identification
- 5 Mounting
- 5.1 General instructions
- 5.2 Mounting requirements
- 5.3 Mounting the measuring device
- 5.3.1 Encapsulated antenna, PVDF40 mm (1.5 in)
- 5.3.2 Drip-off antenna PTFE 50 mm (2 in)
- 5.3.3 Integrated antenna, PEEK 20 mm (0.75 in)
- 5.3.4 Integrated antenna, PEEK 40 mm (1.5 in)
- 5.3.5 Turning the housing
- 5.3.6 Turning the display module
- 5.3.7 Changing the installation position of the display module
- 5.3.8 Closing the housing covers
- 5.4 Post-mounting check
- 6 Electrical connection
- 7 Operation options
- 8 System integration
- 9 Commissioning
- 10 Operation
- 11 Diagnostics and troubleshooting
- 11.1 General troubleshooting
- 11.2 Error - SmartBlue operation
- 11.3 Diagnostic information on local display
- 11.4 Diagnostic event in the operating tool
- 11.5 Adapting the diagnostic information
- 11.6 Queued diagnostic messages
- 11.7 Diagnostic list
- 11.8 List of diagnostic events
- 11.9 Event logbook
- 11.10 Resetting the device
- 11.11 Device information
- 11.12 Firmware history
- 12 Maintenance
- 13 Repair
- 14 Accessories
- 14.1 Weather protection cover 316L
- 14.2 Plastic weather protection cover
- 14.3 Mounting bracket, adjustable
- 14.4 M12 socket
- 14.5 Remote display FHX50B
- 14.6 Gas-tight feedthrough
- 14.7 Commubox FXA195 HART
- 14.8 HART Loop Converter HMX50
- 14.9 FieldPort SWA50
- 14.10 Wireless HART adapter SWA70
- 14.11 Fieldgate FXA42
- 14.12 Field Xpert SMT70
- 14.13 DeviceCare SFE100
- 14.14 FieldCare SFE500
- 14.15 Memograph M
- 14.16 RN42
- 15 Technical data
- Index
Diagnostics and troubleshooting Micropilot FMR60B HART
44 Endress+Hauser
Diagnostic
number
Short text Remedy instructions Status
signal
[from the
factory]
Diagnostic
behavior
[from the
factory]
412 Processing download Download active, please wait C Warning
420 HART Device
Configuration Locked
Check device locking configuration. S Warning
421 HART Loop Current fixed Check Multi-drop mode or current
simulation.
S Warning
431 Trim required Carry out trim C Warning
435 Linearization faulty Check linearization table F Alarm
437 Configuration
incompatible
1. Update firmware
2. Execute factory reset
F Alarm
438 Dataset different 1. Check data set file
2. Check device parameterization
3. Download new device
parameterization
M Warning
441 Current output out of
range
1. Check process
2. Check current output settings
S Warning
484 Failure mode simulation
active
Deactivate simulation C Warning
485 Process variable
simulation active
Deactivate simulation C Warning
491 Current output
simulation active
Deactivate simulation C Warning
495 Diagnostic event
simulation active
Deactivate simulation S Warning
538 Configuration Sensor
Unit invalid
1. Check sensor configuration
2. Check device configuration
F Alarm
585 Simulation distance Deactivate simulation C Warning
586 Record map Recording of mapping
please wait
C Warning
Diagnostic of process
801 Supply voltage too low Increase supply voltage F Alarm
802 Supply voltage too high Decrease supply voltage S Warning
805 Loop current faulty 1. Check wiring
2. Replace electronics
F Alarm
806 Loop diagnostics 1. Check supply voltage
2. Check wiring and terminals
M Warning
1)
807 No Baseline due to insuf.
volt. at 20 mA
Increase supply voltage M Warning
825 Electronics temperature 1. Check ambient temperature
2. Check process temperature
S Warning
826 Sensor temperature out
of range
1. Check ambient temperature
2. Check process temperature
S Warning
846 HART Non-Primary
Variable Out of Limit
Check device specific diagnosis. S Warning
847 HART Primary Variable
Out of Limit
Check device specific diagnosis. S Warning
848 HART Device Variable
Alert
Check device specific diagnosis. S Warning
941 Echo lost Check parameter 'DC value' S Warning
1)