FieldPort SWA50
Endress+Hauser 11
1
32
A0043240
10 Example of remote mounting
1 FieldPort SWA50 "remote mounting" version
2 Cable
3 HART field device
1
32
A0043241
11 Example of direct mounting
1 Cable
2 FieldPort SWA50 "direct mounting" version
3 HART field device
Mounting instructions
• Pay attention to range. → 6
• Observe a distance of at least 6 cm from walls and pipes. Pay attention to the expansion of the
Fresnel zone.
• Avoid mounting in close proximity to high-voltage devices.
• Pay attention to the effect of vibrations at the mounting location. → 12
Additional mounting information for Bluetooth version:
Mount within the visual range of a FieldEdge SGC200.
Additional mounting information for WirelessHART version:
Mount within the visual range of a WirelessHART adapter, such as SWA50, SWA70, or a
WirelessHART gateway, such as SWG70.
Lightning protection
• Do not mount the FieldPort SWA50 at the highest point of the system.
• Ground the housing of the FieldPort SWA50.