User's Manual
Table Of Contents
- Table of contents
- Important document information
- Terms and abbreviations
- Registered trademarks
- Function and system design
- Input
- Output
- Power supply
- Performance characteristics
- Installation
- Environment
- Process
- Mechanical construction
- Operability
- Certificates and approvals
- CE mark
- RoHS
- RCM-Tick marking
- Ex approval
- Dual seal according to ANSI/ISA 12.27.01
- Functional safety
- WHG
- Pressure equipment with allowable pressure ≤ 200 bar (2
- Marine approval
- Radio standard EN 302729-1/2
- Radio standard EN 302372-1/2
- FCC
- Industry Canada
- CRN approval
- Test, certificate
- Hard-copy product documentation
- Other standards and guidelines
- Ordering information
- Application Packages
- Accessories
- Supplementary documentation
Micropilot FMR67
Endress+Hauser V. 1, Rev. 3, 11-04-2017 69
Heartbeat Verification Availability
Available for the following options of feature 540 "Application Package":
•
EH: Heartbeat Verification + Monitoring
• EJ: Heartbeat Verification
Device functionality checked on demand
• Verification of the correct functioning of the measuring device within specifications.
• The verification result provides information about the condition of the device: Passed or Failed.
• The results are documented in a verification report.
• The automatically generated report supports the obligation to demonstrate compliance with
internal and external regulations, laws and standards.
• Verification is possible without interrupting the process.
Advantages
• No onsite presence is required to use the function.
• The DTM
11)
triggers verification in the device and interprets the results. No specific knowledge is
required on the part of the user.
• The verification report can be used to prove quality measures to a third party.
• Heartbeat Verification can replace other maintenance tasks (e.g. periodic check) or extend the
test intervals.
SIL/WHG-locked devices
12)
• The Heartbeat Verification module contains a wizard for the proof test which must be performed
at appropriate intervals for the following applications:
– SIL (IEC61508/IEC61511)
– WHG (German Water Resources Act)
• To perform a proof test, the device must be locked (SIL/WHG locking).
• The wizard can be used via FieldCare, DeviceCare or a DTM-based process control system.
In the case of SIL-locked and WHG-locked devices, it is not
possible to perform verification
without additional measures (e.g. by-passing of the output current) because the output current
must be simulated (Increased safety mode) or the level must be approached manually (Expert
mode) during subsequent re-locking (SIL/WHG locking).
Detailed description
SD01870F
11) DTM: Device Type Manager; controls device operation via DeviceCare, FieldCare or a DTM-based process control system.
12)
Only relevant for devices with SIL or WHG approval: order code 590 ("Additional approval"), option LA ("SIL") or LC ("WHG").