Installer: Leave this manual with the appliance. Consumer: Retain this manual for future reference. Operating Instructions and Owner’s Manual HEATSTAR High-Intensity Infrared Heaters Models HS4040 HS9100S HS8060 HS9120 4000 & 8000 Models WARNING: READ INSTRUCTIONS CAREFULLY: Read and follow all instructions. Place instructions in a safe place for future reference. Do not allow anyone who has not read these instructions to assemble, light, adjust or operate the heater.
Carbon Monoxide Poisoning: WARNING: Improper installation, adjustment, Early signs of carbon monoxide poisoning resemble the flu, with headaches, dizziness, or nausea. If you have these signs, the heater may not be working properly. Get fresh air at once! Have heater serviced. Some people are more affected by carbon monoxide than others. These include pregnant women, persons with heart or lung disease or anemia, those under the influence of alcohol, and those at high altitudes.
1. GENERAL INFORMATION edition, or Figure 1; the larger dimension of ANSI/NFPA No. 409 or Figure 1 is to be used. In Canada refer to CCA B149-1-M91 and B149.2. a. Your heater comes fully assembled and is tested at the factory for proper gas and input as stated on the name plate. WARNING: Maintain clearances as shown in Figure 1 or on heater nameplate, in garage installations where parked vehicles are directly below the heater. b. Before proceeding with the installation, be sure to inspect for damages.
b. Where natural (gravity) ventilation is provided for exhaust, the openings must be distributed above the heaters (preferably at the peak of the roof) and the areas of openings shall not be less than 300 square inches for every 100,000 BTU input. a separate regulator must be installed ahead of the heater. Refer to Figure 2 for maximum allowable pressure for stated model and gas. See heater rating plate for minimum gas supply pressure “For the Purpose of Input Adjustment” 9.
CONNECTION DIAGRAM FOR FLAME ROD CURRENT FOR FLAME RECTIFICATION SYSTEMS (DSP-5, A5) Microammeter Gas Flame Control Flame Rod Terminal For Flame Rod Loadwire Flame Rod Assy. G Figure 3 – Using a microammeter to prove adequate grounding area. NOTE: MEANS OF PROVING ADEQUATE GROUNDING AREA 1. Read all control data sheet supplied with this heater. The proper flame-rod-to-ground-area ratio cannot always be determined by visual examination or physical measurement.
COMBINED LOAD: 1.5 AMP. PILOT BURNER SPARK ELECTRODE / FLAME SENSOR IGN SP745 PV GND TR PV/MV TH LOGIC BOX MAIN BURNER MV 24 VOLT THERMOSTAT OPTIONAL THERMOSTAT NOT BY HEAT STAR PV PV/MV MV GAS VALVE 120 VAC 24 VAC TRANSFORMER (SHIPPED LOOSE) VR8204 A5 CONNECTION DIAGRAM REF. B2984-1 PILOT BURNER COMBINED LOAD: 1.
Replacement Parts List For Heaters 4000 Series Models / Less Control Item No. No. Req’d. Stock No. Description 1 1 00435 A Reflector Assembly 2 1 02523 A Burner Assembly 3 1 03397 P Venturi 5 1 05437 Orifice – Br. N.G. 4040 6 1 05443 Orifice – Br. N.G. 4030 1 2 1 2 4 7 1 05449 Orifice – Br. L.P. 4040 8 1 05452 Orifice – Br. L.P. 4030 9 1 12366 Gasket – Venturi 10 11 4040 Nat. Gas 1 3 5 or 9 2 9 3 4040 Nat.
Replacement Parts List For Heaters 9000 Series Models / Less Control 1 Item No. No. Req’d. Stock No. Description 1 1 00444 A Reflector Assembly 2 2 02694 Burner Assembly 3 2 03421 P Venturi 2 05428 Orifice – Br. N.G. 9140 2 11 4 5 6 7 2 05429 Orifice – Br. N.G. 9120 8 2 05430 Orifice – Br. N.G. 9100 9 2 05443 Orifice – Br. L.P. 9120 10 2 05445 Orifice – Br. L.P.
Replacement Parts List For Heaters 9100S Series Models / Less Control 2 Item No. No. Req’d. Stock No. Description 1 1 00443 A Reflector Assembly 2 2 02508 A Burner Assembly 3 2 03421 P Venturi 6 2 05431 Orifice – Br. N.G. 9100S 7 2 05432 Orifice – Br. N.G. 9090 8 2 05437 Orifice – Br. N.G. 9080 9 2 05446 Orifice – Br. L.P. 9100S 10 2 05447 Orifice – Br. L.P. 9090 11 2 05449 Orifice – Br. L.P.
FOR HEAT STAR SERIES 4000, 8000 REPLACEMENT PARTS LIST FOR CONTROL SYSTEM SUFFIX NDSP-5 or ITEM NO. NO. REQ’D STOCK NO. DESCRIPTION 1 1 00028 IGNITION CONTROL #SP715A 2 1 00037 GAS VALVE DSP-5/VR8204A2001/ SWC 3 1 00228 CONTROL ASSY. NDSP-5 4 1 05573 ORIFICE PILOT NG. 5 1 08353 TRANSFORMER 40VA 6 1 09374 PROBE T/C 1 5/32” LONG 7 1 09375 PROBE LEAD 4000, 8000, 9000 HTRS. 8 1 11403 PILOT BURNER ASSY. 9 1 14606 BRACKET MTG. SP715A RS.L. & HON.V.
FOR HEAT STAR SERIES 4000, 8000 REPLACEMENT PARTS LIST FOR CONTROL SYSTEM SUFFIX LA5 ITEM NO. NO. REQ’D STOCK NO. DESCRIPTION 3 2 1 1 1 00036 GAS VALVE A5/VR8204A2092/11” WC 2 1 00039 CONTROL LOGIC /A5/ #SP745NL36005 3 1 00329 CONTROL ASSY. LA5 4 1 05577 ORIFICE PILOT – LP 5 1 08353 TRANSFORMER 40VA 6 1 11407 PILOT BURNER ASSY. 7 1 14615 BRACKET MTG. A5, 745RS.L. & HON.V.
FOR HEAT STAR SERIES 9000, 9000S 5 REPLACEMENT PARTS LIST FOR CONTROL SYSTEM SUFFIX NPP, LPP 1 2 ITEM NO. NO. REQ’D STOCK NO. DESCRIPTION 1 1 00024 COMB. GAS VALVE (PP) NG. 1/2x1/2 NPT 2 1 00025 COMB. GAS VALVE (PP) LP.
Figure 4 CLEARANCES TO COMBUSTIBLES CEILING SEE CHAIN KIT #17374 TOP or threaded rod BACK SIDE F114581 Hanging Bracket Kit BELOW HORIZONTAL MOUNT WALL FLOOR SEE INSTALLATION INSTRUCTIONS FOR DETAILED CLEARANCES INFORMATION Figure 5 mounting TYPICAL WALL MOUNT ANGLE IRON SEE CHAIN KIT #17374 or recommend using heater hanging bracket f114581 threaded rod 45° FROM HORIZONTAL MAXIMUM HEATER SIDE REFLECTOR MUST BE PARALLEL TO THE FLOOR TYPICAL BEAM MOUNT BEAM CLAMP THREADED ROD or chain kit 17374
Figure 6 TYPICAL LOW PRESSURE STANDARD INSTALLATION ON THREADED PIPES USE A PIPE COMPOUND WHICH IS RESISTANT TO THE ACTION OF ALL GASES MUST BE RESISTANT TO PROPANE pipe nipple ½ PSI MAX. HEATER rigid or flexible gas line to heater SHUT-OFF VALVE TEE DRIP LEG CAP MOUNTING HOLES-4 REQ’D SIDE VIEW LOW PRESSURE, MAIN GAS LINE see figure 2 for proper inlet pressures FOR HIGHER PRESSURES THAN SHOWN ABOVE CONTACT FACTORY FOR PROPER REGULATOR HIGH ALTITUDE OPERATION 1.
THIS PAGE INTENTIONALLY LEFT blank Enerco Group, Inc.
Operating Instructions and Owner’s Manual HEATSTAR High-Intensity Infrared Heaters Models HS4030 HS4040 HS8050 HS8060 HS8070 HS9100 HS9080 HS9120 HS9090 HS9140 HS9100S READ INSTRUCTIONS CAREFULLY: Read and follow all instructions. Place instructions in a safe place for future reference. Do not allow anyone who has not read these instructions to assemble, light, adjust or operate the heater. WARNING: USE ONLY MANUFACTURER’S REPLACEMENT PARTS. USE OF ANY OTHER PARTS COULD CAUSE INJURY OR DEATH.
Guide d'utilisation et instructions de fonctionnement Appareils de chauffage infrarouge haute intensité HEATSTAR Modèles HS4030 HS4040 HS8050 HS8060 HS8070 HS9100 HS9080 HS9120 HS9090 HS9140 HS9100S LISEZ SOIGNEUSEMENT LES INSTRUCTIONS. Lisez et observez toutes les instructions. Conservez les instructions pour vous y référer ultérieurement. Interdisez à quiconque n'ayant pas lu les présentes instructions d'assembler, d'allumer, de régler ou de faire fonctionner cet appareil de chauffage.
CETTE PAGE EST LAISSÉE BLANCHE INTENTIONNELLEMENT Enerco Group, Inc.
Figure 6 INSTALLATION STANDARD BASSE PRESSION SUR LES CONDUITES FILETÉES, UTILISEZ UN COMPOSÉ À CONDUITE RÉSISTANT À L'ACTION DE TOUS LES GAZ DOIT ÊTRE RÉSISTANT AU PROPANE RACCORD DE CONDUITE ½ PSI MAX.
Figure 4 DISTANCES DES MATÉRIAUX COMBUSTIBLES PLAFOND VOIR L'ENSEMBLE DE CHAÎNE Nº 17374 DESSUS ou tige filetée ARRIÈRE CÔTÉ F114581 Ensemble de ferrure de suspension DESSOUS FIXATION HORIZONTALE MUR PLANCHER CONSULTEZ LES INSTRUCTIONS D'INSTALLATION POUR OBTENIR DES RENSEIGNEMENTS DÉTAILLÉS SUR LES DISTANCES DE SÉCURITÉ Figure 5 fixation CORNIÈRE FIXATION MURALE TYPE IL EST RECOMMANDÉ D'UTILISER LA FERRURE DE SUSPENSION D'APPAREIL DE CHAUFFAGE F114581 VOIR L'ENSEMBLE DE CHAÎNE Nº 17374 OU LA TIGE
APPAREILS DE CHAUFFAGE HEAT STAR DE SÉRIES 9000 ET 9000S LISTE DE PIÈCES DE RECHANGE POUR LE SYSTÈME DE COMMANDE À SUFFIXE NPP OU LPP 2 LPP 1 NPP 1 8 1 7 1 6 1 5 1 4 1 3 1 2 1 1 QUANTITÉ NÉCESSAIRE N° D'ARTICLE 4 3 5 5 NUMÉRO DE RÉFÉRENCE 00024 00025 05384 05383 09360 10367 11385 16425 6 6 7 7 1 NPP 1 8 1 7 1 7 1 6 1 5 1 4 1 3 1 2 1 1 QUANTITÉ NÉCESSAIRE N° D'ARTICLE NUMÉRO DE RÉFÉRENCE 5 6 5 6 5 2 6 8 7 3 4 5 DESCRIPTION 1 2 ROBINET DE GAZ C
APPAREILS DE CHAUFFAGE HEAT STAR DE SÉRIES 4000 ET 8000 LISTE DE PIÈCES DE RECHANGE POUR LE SYSTÈME DE COMMANDE À SUFFIXE LA5 1 8 1 7 1 6 1 5 1 4 1 3 1 2 1 1 QUANTITÉ NÉCESSAIRE N° D'ARTICLE LA5 NUMÉRO DE RÉFÉRENCE 00036 00039 00329 05577 08353 11407 14615 16425 DESCRIPTION ROBINET DE GAZ A5/ VR8204A2092/11” WC 2 4 5 6 7 3 2 1 7 LOGIQUE DE COMMANDE / A5/ #SP745NL36005 COMMANDE LA5 AJUTAGE VEILLEUSE – GAZ DE PÉTROLE LIQUÉFIÉ TRANSFORMATEUR 40 VA BRÛLEUR VEILLEUSE FERRURE DE MON
APPAREILS DE CHAUFFAGE HEAT STAR DE SÉRIES 4000 ET 8000 LISTE DE PIÈCES DE RECHANGE POUR LE SYSTÈME DE COMMANDE À SUFFIXE NDSP-5 3 1 NDSP-5 1 10 1 9 1 8 1 7 1 6 1 5 1 4 1 3 1 2 1 1 QUANTITÉ NÉCESSAIRE N° D'ARTICLE NUMÉRO DE DESCRIPTION RÉFÉRENCE 00028 00037 00228 05573 08353 09374 09375 11403 14606 16425 4 5 6 7 2 9 COMMANDE D'ALLUMAGE #SP715A 1 ROBINET DE GAZ DSP-5/ VR8204A2001/SWC COMMANDE NDSP-5 AJUTAGE VEILLEUSE GAZ NATUREL TRANSFORMATEUR 40 VA SONDE THERMOCOUPLE DE 1 5
Liste de pièces de rechange pour les appareils de chauffage des modèles de série 9100S / moins la commande 2 3 2 2 1 1 Quantité nécessaire Nº d'article Nº de référence 00443 A 02508 A 03421 P Description 2 1 Réflecteur Brûleur Venturi 12 4 5 2 13 2 12 2 11 2 10 2 9 2 8 2 7 2 6 05431 05432 05437 05446 05447 05449 06398 12366 Ajutage – brûleur gaz naturel 9100S Ajutage – brûleur gaz naturel 9090 Ajutage – brûleur gaz naturel 9080 16 15 Ajutage – brûleur L.P.
Liste de pièces de rechange pour les appareils de chauffage des modèles de série 9000 / moins la commande 1 2 3 2 2 00444 A 1 1 Nº de Description référence Quantité nécessaire Nº d'article 02694 03421 P Réflecteur 2 Brûleur Venturi 11 4 5 2 12 2 11 2 10 2 9 2 8 2 7 2 6 05428 05429 05430 05443 05445 06396 12366 Ajutage – brûleur gaz naturel 9140 15 Ajutage – brûleur gaz naturel 9120 Ajutage – brûleur gaz naturel 9100 Ajutage – brûleur L.P. 9120 14 Ajutage – brûleur L.P.
Liste de pièces de rechange pour les appareils de chauffage des modèles de série 4000 / moins la commande 1 1 3 1 2 00435 A 1 1 Nº de référence Quantité nécessaire Nº d'article 02523 A 03397 P 2 Description Réflecteur Brûleur Venturi 4 1 9 1 8 1 7 1 6 1 5 05437 05443 05449 05452 12366 Ajutage – brûleur gaz naturel 4040 Ajutage – brûleur gaz naturel 4030 Ajutage – brûleur L.P. 4040 Ajutage – brûleur L.P.
CHARGE COMBINÉE : 1,5 A ALLUMAGE SP745 ROBINET VEILLEUSE BOÎTIER DE LOGIQUE MISE À LA TERRE TRANSFORMATEUR BRÛLEUR VEILLEUSE ÉLECTRODE / DÉTECTEUR DE FLAMME BRÛLEUR PRINCIPAL ROBINET VEILLEUSE/ROBINET PRINCIPAL THERMOSTAT ROBINET PRINCIPAL THERMOSTAT THERMOSTAT NON FOURNI PAR HEAT STAR 24 VOLTS EN OPTION ROBINET VEILLEUSE ROBINET VEILLEUSE/ROBINET PRINCIPAL ROBINET PRINCIPAL ROBINET DE GAZ 120 V C.A. 24 V C.A. TRANSFORMATEUR (EXPÉDIÉ NON FIXÉ) VR8204 DIAGRAMME DE RACCORDEMENT A5 RÉF.
DIAGRAMME DE RACCORDEMENT POUR MESURE DU COURANT À L'ÉLECTRODE DE DÉTECTION DE FLAMME DANS LES DISPOSITIFS DE REDRESSEMENT DU COURANT (DSP-5, A5) Microampèremètre Flamme au gaz Électrode de détection de flamme Commande Borne pour fil de charge de l'électrode de détection de flamme Mise à la terre Ensemble d'électrode de détection de flamme Figure 3 – Utilisation d'un microampèremètre pour vérifier que la surface de mise à la terre est adéquate.
5. PRESSION DU GAZ Lorsque la pression du gaz dépasse le maximum recommandé et qu'elle est maintenue dans la conduite de gaz principale, il est recommandé d'installer un régulateur séparé en aval de l'appareil de chauffage. Consultez la figure 2 pour connaître la pression maximale permise selon le modèle de l'appareil et le gaz utilisé.
1. RENSEIGNEMENTS GÉNÉRAUX : a. Votre appareil de chauffage est livré entièrement assemblé et a été préalablement inspecté en usine pour approuver le type de gaz utilisé et la bonne marche de l'appareil, conformément à la plaque signalétique. b. Avant de procéder à l'installation, effectuez une inspection pour déceler la présence de dommages. La compagnie de transport doit être avisée de tous les dommages; exigez qu'une inspection soit effectuée par la compagnie de transport.
AVERTISSEMENT : Une installation incorrecte, un réglage inadéquat, une modification, une réparation ou un entretien inappropriés peuvent causer des dommages, des blessures, voire même la mort. Lisez les instructions d'installation, de fonctionnement et d'entretien avant de procéder à l'installation ou à l'entretien de cet équipement. Pour obtenir de l'aide ou des renseignements supplémentaires, consultez un installateur qualifié, un fournisseur de services d'entretien ou un fournisseur de gaz.
À l'installateur : rangez ce manuel avec l'appareil. Au consommateur : conservez ce manuel pour vous y référer ultérieurement. Guide d'utilisation et instructions de fonctionnement Appareils de chauffage infrarouge haute intensité HEATSTAR Modèles HS4040 HS9100S HS8060 HS9120 Modèles 4000 et 8000 LISEZ SOIGNEUSEMENT LES INSTRUCTIONS. Lisez et observez toutes les instructions. Conservez les instructions pour vous y référer ultérieurement.