User Manual

www.enerdrive.com.au Page 25
T.LOW
(bank1)
0°C C -20°C..
+50°C
Low battery temperature. When the
temperature falls below the On value,
the associated alarm will be activated.
When the temperature rises above the
O value, this alarm will be deactivated
again.
T.HIGH
(bank1)
40°C 39°C
High battery temperature. When the
temperature exceeds the On value,
the associated alarm will be activated.
When the temperature falls below the
O value, this alarm will be deactivated
again.
MIDPNT
(bank1)
2.0% 0.5% 0.0% -
50.0%
Midpoint voltage deviation. When the
deviation exceeds the On value, the
associated alarm will be activated. When
the deviation falls below the O value,
this alarm will be deactivated again. For
more information on midpoint voltage
measurement and setup, please see
appendix 1 in Section 13, page 39 of this
user manual.
V.LOW
(bank2)
10.5V 11.0V 7.0V -
70.0V
Low battery voltage. When the voltage
falls below the On value, the associated
alarm will be activated. When the voltage
rises above the O value, this alarm will
be deactivated again.
V.HiGH
(bank2)
16.0V 15.5V High battery voltage. When the voltage
rises above the On value, the associated
alarm will be activated. When the voltage
falls below the O value, this alarm will