Enerdrive ePRO Plus Battery Monitor Owners Manual (Rev. 1.02)Page 28
6.7 Global Properties
F10.0
Backlight timer. Represents the duration of backlight activation in seconds after
keypress. The backlight can also be set to be always “ON” or always “OFF”.
Default: 30sec
Range: OFF / 5 – 300sec /
ON
Step size: variable
F10.1 Backlight auto on. When set to “ON”, The backlight is automatically activated when
the charge / discharge current exceeds 1Amp.
Default: OFF Range: OFF / ON
F10.2
Alarm contact polarity. Enables selection between a normally open (NO) or normally
closed (NC) contact.
Default: N/O Range: N/O – N/C
F10.3
Temperature units. Enables selection between degrees Celsius (°C) and degrees
Fahrenheit (°F) in the temperature readout.
Default: °C Range: °C / °F
6.8 Advanced Properties
A01
Auto-sync mode. Choose which mode to use to automatically synchronize the ePRO
Plus with your battery when it is fully charged. The default mode is STANDARD which
is the preferred setting for most applications. The setting LEGACY represents an
autosync mode as used in the ePRO and eLITE battery monitors. This mode can be
selected when the installer wishes to have more control over the auto-sync conditions.
These conditions can be set in Functions A02, A03, A04 and A05 once A01 is set to
LEGACY. Only when the conditions of A02 and A03 are both met during the time period
set in A04, the battery is considered fully charged and the SoC value is set to 100%.
Default: STANDARD Range: STANDARD / LEGACY
A02 Auto-sync voltage (will only show when A01 is set to LEGACY). The battery voltage
must be above this level to consider the battery as fully charged. This value must be
slightly below your battery charger’s oat voltage (0.1 – 0.3V), which is the last stage
of the charging process. The default value can be multiplied by 2 or 4 if respectively
24V or 48 systems are connected to the ePRO Plus.
Default: 13.2V Range: 7.0 – 70.0V Step size: 0.1V