SdH
Battery under-voltage setting is set to HIGH (setting to avoid battery over discharge when
connected to car start battery)
Under-voltage alarm: ................................. 12.1 Vdc
Under-voltage alarm recovery: ............... 12.3 Vdc
Under-voltage shutdown: ........................ 11.8 Vdc
Under-voltage shutdown recovery: ....... 12.6 Vdc
Alarm Setting
AL0
Fault and the warning audible alarm is disabled. The display panel only shows error code
and the audible alarm will not sound.
AL1 Audible alarm will sound when fault or warning occurs.
Manufacturing Default
Fd Reset all the settings to the manufacturing default settings (PS1, SdL, AL1)
Enter the Function Menu for unit setting:
To enter the unit Function Menu, press and hold “Power” and “Select” buttons together for about 5
seconds until a beep is heard.
When you are in the Function Menu:
•
Press ‘Power’ button for 1 second to toggle between dierent Function Menus like ‘In’, ‘Sd’, ‘AL’,
and ‘Fd’ etc.
• Press ‘Select’ button for 1 second to enter Individual Function Menu and you can make changes to
the settings.
•
The unit will EXIT to the Main Menu automatically if ‘Power’ or ‘Select’ buttons are not triggered
within 5 seconds.
When you are in Individual Function Set Menu:
• Press ‘Select’ button for 1 second to toggle between dierent setting values.
• Press ‘Select’ button for 5 seconds to set selected setting and exit to next menu
See more details on ow chart in Appendix I.