Auto-sync current (will only show when A01 is set to LEGACY). When the charge current
is below this percentage of the battery capacity (see Function F1.1), the battery will be
considered as fully charged. Make sure that this value is always slightly greater than
the current at which the charger maintains the battery or stops charging.
Default: 2.0% Range: 0.5 - 10.0% Step size: 0.1%
A04
Auto-sync time (will only show when A01 is set to LEGACY). This is the time that both
Auto-sync parameters A02 and A03 must be met in order to consider the battery as
fully charged.
Default: 240sec Range: 0 – 3600sec Step size: variable
A05 Auto-sync sensitivity (will only show when A01 is set to LEGACY). Only change this
setting when A02, A03 and A04 are set correctly and automatic synchronization still
fails. If automatic synchronization takes too long or does never occur, lower this value.
When the battery monitor synchronizes too early, increase this value.
Default: 5 Range: 0 – 10 Step size: 1
A06 Reserved
Default: - Range: - Step size: -
A07
Bank 1 series cell count. Allows you to edit the number of internal series cells of your
used batteries that was automatically determined after completing the Setup Wizard.
See table 2 in chapter 2.2 for more information.
Default: dynamic Range: 2 – 30 Step size: 1
A08
Bank 2 series cell count (will only show when F2.0 is set to AUX.BAT). Allows you to edit
the number of internal cells of your used batteries, that was automatically determined
after completing the Setup Wizard. See table 2 in chapter 2.2 for more information.
Default: dynamic Range: 2 – 30 Step size: 1
A09
Bank 3 series cell count (will only show when F3.0 is set to AUX.BAT). Allows you to edit
the number of internal cells of your used batteries, that was automatically determined
after completing the Setup Wizard. See table 2 in chapter 2.2 for more information.
Default: dynamic Range: 2 – 30 Step size: 1