SAFTRONICS/EMERSON PARAMETERS (ENCLOSED BOX)
Parameter Comparison Listing
Project: My Project : evalentin
Drive Name: Drive (Commander SK)
Drive Mode: Open loop
Drive Address: 1
Parameter Description Default Memory Units
01.41 Analog reference 2 select OFF On
01.51 Power-up keypad reference 0 LASt
02.04 Ramp mode select Std Std.HV
02.11
A
cceleration rate 1 5.0 10.0 s/100 Hz
05.07 Motor rated current 0.00 1.20 A
05.08 Motor rated full load rpm 1800 1700 RPM
05.14 Voltage mode select Ur I Fd
05.15 Low frequency voltage boost 3.0 1.0 %
05.34 Speed displa
y
units Fr Cd
05.50 Security unlock 0 1
06.09 Catch a spinnin
g
motor select 0 1
06.40 Enable sequencer latching OFF On
07.06 Analog input 1 mode (terminal T2) 4-.20 VoLt
07.14 Analog input 2 destination 1.37 0.00 menu.param
08.22 Terminal B4 di
g
ital input destination 6.29 6.39 menu.param
08.23 Terminal B5 digital input destination 6.30 6.34 menu.param
08.24 Terminal B6 digital input destination 6.32 6.31 menu.param
11.21 Customer defined scaling 1.000 0.056
11.44 Security status L1 L3
14.03 PID reference source 0.00 18.12 menu.param
14.04 PID feedback source 0.00 1.36 menu.param
14.05 PID reference source invert OFF On
14.06 PID feedback source invert OFF On
14.08 PID enable OFF On
14.09 Optional PID enable source 0.00 10.02 menu.param
14.11 PID integral gain 0.500 0.400
14.14 PID lower limit -100.0 0.0 %
14.16 PID output destination 0.00 1.37 menu.param
18.12 Application menu 1 read-write integer 0 5000