SAFTRONICS/EMERSON PARAMETERS (NO ENCLOSURE)
00.03 Acceleration Time 5.0
00.04 Deceleration Time 10.0
00.06 Motor Rated current HP dependent *
00.08 Motor rated Voltage 480 or 240
00.10 Security Level L3
00.16 Analog input T2 4 to 20
00.23 Speed Display units Cd
00.24 Custom Defined Scaling 0.056
00.27 Power up keypad reference LASt
00.30 Ramp mode select STD.HV
00.39 Motor rated Frequency 60
00.32 Dynamic V to F select ON
00.33 Catch a spinning motor select 1
00.41 Voltage mode select FD
00.42 Low Frequency Voltage Boost 1.0
01.01 Minimum Speed 15
01.14 Drive Configuration A1.A2
01.15 Preset speed selector 6
01.28 Preset speed 8 5.0
01.41 Analog Reference 2 select on
05.09 Motor rated Voltage 480
06.40 Enable Sequencer Latching Off
07.10 Analog Input Destination 18.11
14.03 PID main ref. source 18.12
14.04 PID feedback source 18.11
14.05 PID ref. source invert on
14.06 PID feedback source invert on
14.08 PID Enable on
14.09 PID Enable signal 10.02
14.11 PID Integral 0.400
14.14 PID low limit 0.0
14.16 PID output Dest. 1.26
Monitor Parameters
00.81 Set Point Frequency Should read 5.0 Hz
00.85 Output Frequency Will vary with suction pressure
00.88 Output amps Should not exceed motor rated current
00.94 Analog Input 1(T2) Signal from Pressure transducer
* Motor current need to be set for proper motor thermal protection.